Section 3 - Startup
3-30
to the PLC configuration without changing the relay
assignments.
Shift
Alarm relay definitions move down to fill the space
created by fewer fault relays or move up to accommodate
the additional fault relays.
Changing the number of fault relays from 14 to 16 will
cause the alarm relay assignments to move two relays
up. Card 5, relay 2 definition moves to card 5, relay 4;
card 5, relay 3 moves to card 5 relay 5; card 5 relay 15
moves to card 6, relay 1, etc.
Changing the number of fault relays from 16 to 14
moves relay assignment down by 2 positions. Card
5, relay 4 definition moves to card 5, relay 2; card 5,
relay 5 moves to card 5 relay 3; card 6, relay 1 moves
to card 5, relay 15, etc.
Pad
Padding leaves most alarm relay definitions unchanged.
Some existing alarm definitions may be overwritten or
undefined relays may become available.
Changing the number of fault relays from 14 to 16 will
cause the alarm definitions on card 3, relay 14 and
card 3, relay 15 to be overwritten by the fault relay
assignments.
Changing the number of fault relays from 14 to 12 will
result in two additional (and undefined) alarm relays
being available at card 3 relays 12 and 13. Existing
relay definitions are not moved.
3.6.7 Set Alarm Relays
A relay configured for a Level 1 trigger will activate for
both Level 1 and Level 2 alarms. A Level 2 trigger will
only activate for Level 2 alarms.
None of the relays are defined as general or point
specific alarms until they are programmed or associated
with one or more points in an analyzer.
Note:
Set the number of fault relays before setting alarm
relay definitions. If you change the number of fault re-
lays, the current alarm relay definitions may change
and must be redefined. See
Section 3.6.6 Configure
PLC
.
Defining a point for association with a relay is a four-
step process:
1. Choose the relays to which you want to
associate with a point.
2. Choose L1 Alarm or L2 in the Change To...
area.
3. Click the square representing the point or
points to associate with the relay. The point
changes color to indicate the change.
4. Choose Accept make the change the change
to the configuration profile. Choosing cancel
leaves the alarm definition unchanged.
Repeat the steps for all contacts.
To verify a contacts association to analyzer points,
choose the contact. The associated point display
changes color.
Содержание Vertex M
Страница 8: ...1 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook 1 Introduction ...
Страница 25: ...Vertex MTM 24 Point Continuous Monitor Section 1 Introduction 1 18 ...
Страница 26: ...2 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook 2 Installation ...
Страница 35: ...Vertex MTM 24 Point Continuous Monitor Section 2 Installation 2 10 ...
Страница 36: ...3 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook 3 Startup ...
Страница 40: ...Vertex MTM 24 Point Continuous Monitor Section 3 Startup 3 5 Figure 3 1 Vertex M Main Screen ...
Страница 77: ...4 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook 4 Operation ...
Страница 93: ...Vertex MTM 24 Point Continuous Monitor Section 4 Operation 4 17 Figure 4 9 Filter Options ...
Страница 109: ...Vertex MTM 24 Point Continuous Monitor Section 4 Operation 4 33 ...
Страница 125: ...5 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook 5 Maintenance ...
Страница 134: ...Vertex MTM 24 Point Continuous Monitor Section 5 Maintenance 5 10 ...
Страница 140: ...Vertex MTM 24 Point Continuous Monitor Section 5 Maintenance 5 16 ...
Страница 141: ...6 1 Vertex M TM Technical Handbook 6 Troubleshooting ...
Страница 164: ...Section 6 Troubleshooting 6 24 ...
Страница 165: ...A 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Installation Drawings ...
Страница 166: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 2 A 1 Introduction ...
Страница 167: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 3 A 2 Floor Space Requirements ...
Страница 168: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 4 A 3 General Considerations and Cooling ...
Страница 169: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 5 A 4 General Wiring ...
Страница 170: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 6 ...
Страница 171: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 7 A 5 4 Port Manifold Option ...
Страница 172: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 8 A 6 Floor Mounting Option ...
Страница 173: ...Vertex MTM 24 Point Continuous Monitor Appendix A Installation Drawings A 9 ...
Страница 174: ...B 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Specifications ...
Страница 178: ...C 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Detectable Gases ...
Страница 190: ...D 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Replacement and Consumable Items ...
Страница 193: ...Vertex MTM 24 Point Continuous Monitor Appendix A Replacement and Consumable Items D 4 ...
Страница 194: ...E 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Optional Relay Specifications ...
Страница 198: ...F 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Network Interface and Options ...
Страница 226: ...Vertex MTM 24 Point Continuous Monitor Appendix A Network Interface and Options F 29 Figure A 18 Custom Permissions ...
Страница 237: ...G 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A 4 20mA Analog Output Option ...
Страница 240: ...Vertex MTM 24 Point Continuous Monitor Appendix A 4 20mA Analog Output Option G 4 ...
Страница 241: ...H 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Line Integrity Test Option ...
Страница 247: ...I 1 Vertex MTM 24 Point Continuous Monitor Vertex M TM Technical Handbook A Warranty Statement ...
Страница 250: ...Vertex MTM 24 Point Continuous Monitor Appendix A Warranty Statement I 4 ...