Honeywell VE4000 Series Скачать руководство пользователя страница 4

 

Honeywell 

ISTR0018  1602RA-NE 

POWER CONSUMPTION (VA)

 

 

Model 
number 

24Volt, 
50/60Hz 
nominal 

24 Volt, 
50/60Hz 
110% of 
nominal 

100-120 Volt,
50/60Hz 
nominal 

110 Volt,
50/60Hz 
110% of 
nominal 

200-240 Volt, 
50/60Hz 
nominal 

200-24- Volt,
50/60Hz 
110% of 
nominal 

VExx10, C 

15 

17 

13 -19 

14-21 

11-16 

12-18 

VExx15 15 

17 13 

-19 

14-21 

11-16 

12-18 

VExx20 21 

23 17 

-24 

19-26 

17-24 

19-26 

VExx25 21 

23 17 

-24 

19-26 

17-24 

19-26 

VExx32 start 
VExx32 work 

N.A. 
50 

N.A 
55 

125-179 
32-45 

138-197 
35-50 

129-186 
32-46 

142-205 
35-51 

VExx40 start 
VExx40 work 

N.A. 
50 

N.A 
55 

125-179 
32-45 

138-197 
35-50 

129-186 
32-46 

142-205 
35-51 

VExx50 start 
VExx50 work 

N.A 
49 

N.A. 
54 

131-188 
33-47 

144-207 
36-52 

127-183 
32-45 

140-201 
35-50 

VExx65 start 
VExx65 work 

N.A. 
72 

N.A. 
54 

205-295 
51-74 

226-325 
56-81 

190-274 
48-69 

209-301 
53-76 

VExx80B start 
VExx80 work 

N.A. 
72 

N.A. 
79 

205-295 
51-74 

226-325 
56-81 

190-274 
48-69 

209-301 
53-76 

VEx100 start 
VEx100 work 

N.A. 
N.A. 

N.A. 
N.A. 

180-259 
45-65 

198-285 
50-72 

465-657 
114-164 

512-723 
125-180 

 

POWER CONSUMPTION Version S – 200 mbar 

 

Model 
number 

12 Volt, 
50/60Hz 

nominal 

12 Volt, 
50/60Hz 
110% of 
nominal 

24Volt, 
50/60Hz 
nominal 

24 Volt,
50/60Hz 
110% of 
nominal 

24 Volt
(dc), 
nominal

a)

 

(b)

 

24 Volt
(dc), 
110% of 
nominal 

110 
Volt, 
50/60Hz 
nominal 

110 
Volt, 
50/60Hz 
110% of 
nominal 

220 
Volt, 
50/60Hz 
nominal 

220 Volt,
50/60Hz 
110% of 
nominal 

VExx20S 

 

 

16 19 17  21 14 17 16 19 

 

POWER CONSUMPTION Version S – 360 mbar 

 
 

Model 
number 

12 Volt, 
50/60Hz 

nominal 

12 Volt, 
50/60Hz 
110% of 
nominal 

24Volt, 
50/60Hz 
nominal 

24 Volt,
50/60Hz 
110% of 
nominal 

24 Volt
(dc), 
nominal

a)

 

(b)

 

24 Volt
(dc), 
110% of 
nominal 

110 
Volt, 
50/60Hz 
nominal 

110 
Volt, 
50/60Hz 
110% of 
nominal 

220 
Volt, 
50/60Hz 
nominal 

220 Volt,
50/60Hz 
110% of 
nominal 

VExx20S 

 

 

16 19 17  21 14 17 16 19 

PERFORMANCE CHARACTERISTICS

 

 

Opening time (except VE5xxx series) 

VExxxxA,B,S version: less than 1 second 
VExxxxC version: adjustable from 1 up to 30 seconds at rated capacity 
 

Closing time  

VExxxxA, B, C and S series (except VE5xxx series) 
Less than 1 second 
 

Maximum working cycles/minute 

versions:   20 

DN10–DN 25 A & B versions:   20 
DN10-DN25 C versions: 

 

DN32-DN100: 

  1 

VE5... series: 1 cycle per 2 minutes 
 

Duty cycle 

Coil suitable for permanent energization 

 
 
 

Содержание VE4000 Series

Страница 1: ...e housing The VExxxxX3xxx and VE5xxxX3xxx series gas valves are equipped at both sides with mounting holes to adapt a pilot solenoid valve combination to allow either internal or external pilot gas Furthermore these valves are equipped with two M6 mounting holes to adapt an A4020A electronic leak test The VExxxxB series gas valves have an adjustable flow rate regulator on top of the coil For the V...

Страница 2: ...egulated ON OFF VExxxxAxxxx Standard Standard Flow regulator VExxxxBxxxx Optional Optional 2 Adjustable opening and flow regulator VExxxxCxxxx Optional 1 Not available Motorized opening ON OFF VE5xxxAxxxx Not available VE5065A3xxx VE5085A3xxx Motorized opening characterized VE5xxxCxxxx Not available VE5065C3xxx VE5085C3xxx Safety relief valve ON OFF Normally Open with or without position indicatio...

Страница 3: ...alve will function between 85 and 110 of the rated voltage Electrical connection VE4xxx VE6xxx VE8xxx Option 1 Wiring on terminal block on circuit cables entering box via PG Cable Gland Option 2 Connection by means of DIN plug on DIN faced connection located on front cover according to ISO4400 DIN EN 175301 803 Electrical connection VE5xxx series See product literature fluid power actuators Enclos...

Страница 4: ...2 723 125 180 POWER CONSUMPTION Version S 200 mbar Model number 12 Volt 50 60Hz nominal 12 Volt 50 60Hz 110 of nominal 24Volt 50 60Hz nominal 24 Volt 50 60Hz 110 of nominal 24 Volt dc nominala b 24 Volt dc 110 of nominal 110 Volt 50 60Hz nominal 110 Volt 50 60Hz 110 of nominal 220 Volt 50 60Hz nominal 220 Volt 50 60Hz 110 of nominal VExx20S 16 19 17 21 14 17 16 19 POWER CONSUMPTION Version S 360 m...

Страница 5: ...n alternative In order to tighten the pipe in the valve do not use the actuator as a lever but use a suitable wrench operating on the wrench bosses Main gas connection flanged valves Take care that dirt cannot enter the gas valve during handling Ensure the gas flows in the same direction as the arrow on the housing of the gas valve Ensure that inlet and outlet flanges are in line and separated fro...

Страница 6: ...the box and tightened as shown in Fig 2 Specified torque for the nut 4 Nm Mounted PG gland shown in Fig 3 Specified torque PG gland 3 Nm Fig 2 Fig 3 After connecting wires L N PE to dedicated connectors on connector block the connection needs to closed by mounting the front cover Before placing the cover please check the correct position of seal as shown in Fig 4 The cover can only be mounted in o...

Страница 7: ... in the slot of adjustment screw which is situated in center of the valve Turn screw driver counter clockwise to increase or clockwise to decrease step pressure Replace cap on top of the coil Step pressure adjustment Fig 8 Opening speed adjustment Remove the cap from top of the coil by loosening both screws Place screw driver in the slot of adjustment screw which is of center line Turn screw drive...

Страница 8: ... 200 240 DIN BB0xxxxx VExx20 VExx25 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 PG BB0xxxxx VExx20 VExx25 24 DIN BB0xxxxx 100 120 DIN BB0xxxxx 200 240 DIN BB0xxxxx VExx32 VExx40 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 PG BB0xxxxx VExx32 VExx40 24 DIN BB0xxxxx 100 120 DIN BB0xxxxx 200 240 DIN BB0xxxxx Valve type Voltage Connection Ordering number VExx50 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 ...

Отзывы: