background image

The VC hydronic valve consists of a valve body and replaceable characterized

cartridge assembly.

Depending on the valve model selected, they can be used with a VC2114 or

VC8114 series actuator to provide on-off flow control, or with a VC6930 or

VC7930 series actuator to provide proportional flow control.  Two way bodies

may be plumbed in either direction. Three-way bodies may be used in either

diverting or mixing applications.

Replacing the cartridge rebuilds the valve. The valve body should be able to

stay in the pipes indefinitely.

VC actuators, ordered separately, use cam-operated cartridge travel to resist

water hammer.  Limit switches prevent motor overrun.   These actuators are

available with conformal coated printed circuit boards for humidity resistance.

SPECIFICATIONS

The specifications following are nominal and conform to generally
accepted industry standards.  Honeywell is not responsible for damages
resulting from misapplication or misuse of its products.

Operating Ambient:

32 to 150

°

F [0 to +65

°

C].

5-95% RH (non-condensing)

Fluid temperatures:

34 to 203

°

F [1 to 95

°

C]

Shipping and Storage Temperature:

-40 to 150

°

F [-40 to +65

°

C]

Atmosphere:

Non-corrosive, non-explosive.

Valve Materials:

Body of bronze Cartridge of Ryton

 (polyphenylene sulphide) and

Noryl

 (polyphenylene oxide)

O-ring seals of EPDM rubber
Stem of stainless steel

Pressure Rating:

Static - 300 psig [20 Bar] maximum.

Burst - 1500 psig [100 Bar]
Operating Differential and Close-off - 60 psi maximum [4 bar]

Stem Travel:

0.4 inches [10 mm]

Flow Characteristics:

  Linear or equal percentage, per Table 1.

Accessories and Replacement Parts:

40007029-002: Wrench for removing VC cartridge
VCZZ1100: 2-way linear flow characteristic cartridge
VCZZ1400: 2-way equal percentage cartridge
VCZZ1500: 2-way equal percentage cartridge, very low Cv
VCZZ1600: 2-way equal percentage cartridge, low Cv
VCZZ6100: 3-way linear flow characteristic cartridge

272866B: Flush caps for system cleaning, 10 per pack

Form No.

 95C-10919

VCA,B,M, and N Series

Cartridge Valve for Use with VC Series Actuators

Figure 1 - Nominal dimensions in inches and millimetres

Table 1: VC Valve assembled dimensions

 

[4] 

                        Dimension

Pipe Fitting Sizes

mm

Inches

mm

Inches

mm

Inches

1/2" BSPP (int.) [2]
1/2" BSPT (int.)
3/4" BSPP (int.)
3/4" BSPT (int.)
3/4" BSPP (ext.)
22mm Compression [3]

112 4-7/16

140

5-1/2

1" BSPP (int.)

94 3-11/16

136 5-11/32

1" BSPP (ext.)

95 3-11/17114 4-7

/171375-11/33

1" BSPT (int.)

94 3-11/16

136 5-11/32

28mm Compression [3]

116 4-9/16

1475-13/16

3/8" FLARE [1]

98

3-7/8

136 5-11/32

1/2" SWEAT

89

3-1/2

130

5-1/8

1/2" FLARE [1]
1/2" INVERTED FLARE [1]
1/2" NPT (int.)
3/4" NPT (int.)

130

5-1/8

3/4" SWEAT

132 5-3/16

1" NPT (int.)
1" SWEAT

5-11/32

1-1/4" SWEAT
1-1/4" NPT (int.)
[1] No adapter
[2] 15 mm compression
[3] Nuts and olives not included
[4] All models not available in all countries

E

C

D

113 4-7/16

136 5-11/32

94 3-11/16

130

5-1/8

113 4-7/16

98

3-7/8

111 4-3/8

113 4-7/16

NORTH AMERICA STANDARD MODELS

98

111 4-3/8

3-7/8

5-11/32

5-5/8

136

136

110 4-5/16 118 4-5/8 142

94 3-11/16

A

B

B

AB

A

94 [3-3/4] 

94 [3-3/4] 

90 [3-9/16] 

90 [3-9/16] 

C

 

94 [3-3/4] 

94 [3-3/4] 

 

C

 

68 [2-3/4]

68 [2-3/4]

 

2003.02.24
© Honeywell Limited.

Содержание VCA Series

Страница 1: ...60 psi maximum 4 bar Stem Travel 0 4 inches 10 mm Flow Characteristics Linear or equal percentage per Table 1 Accessories and Replacement Parts 40007029 002 Wrench for removing VC cartridge VCZZ1100 2 way linear flow characteristic cartridge VCZZ1400 2 way equal percentage cartridge VCZZ1500 2 way equal percentage cartridge very low Cv VCZZ1600 2 way equal percentage cartridge low Cv VCZZ6100 3 wa...

Страница 2: ...TERISTIC APPLICATION Nominal kvs Rating 8 NORTH AMERICA STANDARD MODELS 6 0 7 0 Nominal Cv Rating 5 3 3 0 4 5 Equal Percentage On Off 7 Modulating 3 way Valve 5 Cartridge Number Pipe Fitting Sizes VCZME 1 2 BSPP int 2 3 2 VCZMN 1 2 BSPT int 3 3 VCZMH 3 4 BSPP int 5 9 VCZMJ 3 4 BSPT int 5 3 VCZMG 3 4 BSPP ext 6 9 5 7 VCZMF 22 mm Compression 3 7 1 5 9 VCZMP 1 BSPP int 6 4 VCZMQ 1 BSPP ext 6 8 VCZMT ...

Страница 3: ...rom body and solder the connecting pipes in accordance with normal soldering practices 2 After soldering and valve has cooled remove cartidge assembly from plastic bag insert into the valve body and tighten down with enclosed wrench until it bottoms out DO NOT OVER TIGHTEN maximum torque is 40 in lb The top surface of the cartridge will be flush with the top edge of the body casting See Figure 5 3...

Страница 4: ...y be done either before or after the actuator is installed Refer to the VC Actuator Installation and Instruction sheet for detailed wiring and check out instructions 1 The actuator head is automatically latched to the valve Align the coupling hole in the bottom of the actuator with the valve stem Press the actuator down towards the body with moderate hand force and turn the actuator counter clockw...

Отзывы: