background image

3

69-0329—4

LOCATION

The combination gas control is mounted in the appli-

ance vestibule on the gas manifold. If this is a replacement
application, mount the gas control in the same location as
the old control.

Locate the combination gas control where it cannot be

affected by steam cleaning, high humidity, or dripping
water, corrosive chemicals, dust or grease accumulation or
excessive heat. To assure proper operation, follow these
guidelines:

• Locate gas control in a well-ventilated area.
• Mount gas control high enough above the cabinet

bottom to avoid exposure to flooding or splashing
water.

• Assure the ambient temperature does not exceed the

ambient temperature ratings for each component.

• Cover gas control if appliance is cleaned with water,

steam, or chemicals or to avoid dust and grease
accumulation.

• Avoid locating gas control where exposure to corro-

sive chemical fumes or dripping water are likely.

Install Piping to Gas Control

All piping must comply with local codes and ordinances

or with the National Fuel Gas code (ANSI Z223.1 NFPA
No. 54), whichever applies. Tubing installation must com-
ply with approved standards and practices.

1. Use new, properly reamed pipe free from chips. If

tubing is used, assure the ends are square, deburred and
clean. All tubing bends must be smooth and without defor-
mation.

2. Run pipe or tubing to the control. If tubing is used,

obtain a tube-to-pipe coupling to connect the tubing to the
control.

3. Install sediment trap in the supply line to the gas

control. See Fig. 2.

Install Control

1. This control can be mounted 0-90 degrees, in any

direction, from the upright position of the gas control knob,
including vertically.

2. Mount the control so gas flow is in the direction of

the arrow on the bottom of the control.

3. Thread pipe into control. Do not thread pipe to far.

Valve distortion or malfunction may result if the pipe is
inserted too deeply, refer to Table 4.

TABLE 4—NPT PIPE THREAD LENGTH IN in.

OUTLET
PRESSURE 
TAP

INLET

OUTLET

WIRING
TERMINALS (2)

INLET
PRESSURE TAP

PRESSURE REGULATOR
ADJUSTMENT (UNDER 
CAP SCREW)

GAS CONTROL KNOB

M3094B

Fig. 4—Top view of gas control.

TWO IMPERFECT 
THREADS

GAS CONTROL

THREAD PIPE THE AMOUNT 
SHOWN IN TABLE 4 FOR 
INSERTION INTO GAS CONTROL 

APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).

M3075A

PIPE

4. Apply a moderate amount of good quality pipe com-

pound (do not use Teflon tape) to pipe only, leaving two
end threads bare. On LP installations, use compound resis-
tant to LP gas. See Fig. 3.

5. Remove seals over control inlet and outlet if neces-

sary.

6. Connect pipe to control inlet and outlet. Use wrench

on the square ends of the control. If a flange is used, place
wrench on flange rather than control. Refer to Figs. 4 and 5.

Fig. 2—Sediment trap installation.

GAS
CONTROL

GAS
CONTROL

HORIZONTAL

DROP

PIPED
GAS
SUPPLY

PIPED
GAS
SUPPLY

3 INCHES
[76]
MINIMUM

3 INCHES
[76]
MINIMUM

RISER

GAS
CONTROL

TUBING
GAS
SUPPLY

HORIZONTAL

DROP

3 INCHES
[76]
MINIMUM

RISER

M3077

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

Fig. 3—Use moderate amount of pipe com-
pound.

Pipe  

Size

Thread Pipe

This Amount

Maximum Depth Pipe

Can Be Inserted  

Into Control

3/8

9/16

3/8

1/2

3/4

1/2

3/4

13/16

3/4

Содержание V8205

Страница 1: ...0 6 393690 16 Elbow 393690 3 393690 13 3 4 in NPT Straight 393690 4 393690 14 Elbow 393690 5 393690 15 Model No Suffix Letter Ambient Temperature Range Regulator Type A 0 F to 175 F Standard 18 C to 79 C C Step opening H Slow opening K 40 F to 175 F 40 C to 79 C M Standard P Step opening Model Voltage Frequency Number of Automatic Operators Gas Control Knob Positions Current Draw V8205 24V 60 Hz O...

Страница 2: ... controls are factory set for natural and manufactured or LP gas Do not attempt to use a control set for natural manufactured gas on LP gas or a control set for LP on natural manufac tured gas Gas controls with standard or slow opening regulators can be converted from one gas to the other with a conver sion kit ordered separately Order part no 393691 to convert from natural manufactured to LP gas ...

Страница 3: ...y direction from the upright position of the gas control knob including vertically 2 Mount the control so gas flow is in the direction of the arrow on the bottom of the control 3 Thread pipe into control Do not thread pipe to far Valve distortion or malfunction may result if the pipe is inserted too deeply refer to Table 4 TABLE 4 NPT PIPE THREAD LENGTH IN in OUTLET PRESSURE TAP INLET OUTLET WIRIN...

Страница 4: ...age 1 Check the power supply rating on the gas control and make sure it matches the available supply Install the trans former thermostat and other controls as required 2 Connect control circuit to gas control terminals See Figs 4 6 and 7 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve operator Fig 7 Wiring connections for 24 volt control in S89 direct ignition system WHITE BL...

Страница 5: ...operly adjusted for complete combustion Followinstructionsofappliancemanufacturer 2 IF CHECKING GAS INPUT BY CLOCK ING GAS METER Make certain there is no gas flow through the meter other than to the appliancebeingchecked Otherappliancesmust remain off with their pilots extinguished or their consumption must be deducted from the meter reading Convert flow rate to Btuh as described in Gas Controls H...

Страница 6: ...htoff characteristics TABLE 5A PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa CHECK SAFETY LOCKOUT SLOW OPENING CONTROLS ONLY 1 With the system power off and the thermostat set to call for heat manually shut off the gas supply 2 Energize ignitor control and start timing safety lock out time When spark ignition terminates stop timing When using the VR8205H step opening control the specified igni...

Страница 7: ...PERSONAL INJURY OR LOSS OF LIFE 1 Before lighting smell around the appliance area for gas If the appliance uses LP bottled gas be sure to smell next to the floor because LP gas is heavier than air If you smell gas immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank Do not try to light any appliance Do not touch any electrical switch or use the phone Leave ...

Страница 8: ... LP installation immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank Don t touch any electrical switch or use the phone Leave the building and call your gas supplier If your gas supplier cannot be reached call the fire department Failure to do so may result in fire or explosion 6 If you don t smell gas turn knob on gas control counterclockwise to ON 7 Repl...

Отзывы: