MU0H-2327GE23 R0618
5
Honeywell GmbH
2.1.4Technical Data
*
1
no condensation
2.1.5Installation
If the actuator M5004 is purchased with the valve Honeywell
V5004TF, it is already installed onto the valve. If it is bought
as a spare part, follow the next procedure:
1.
Completely open the valve with an 8 mm spanner (max
torque 7 Nm)
2.
Install the actuator in the same position of that has been
previously removed
3.
Insert the three pins in the specific buttonholes on the
fixing plate
4.
Turn the fixing ring
5.
Close the valve by means of the actuator which has to
be electrically connected
6.
If the actuator reaches the end-stroke before the valve
is completely closed, adjust the actuator mounting
position
7.
Unplug and plug the power to the actuator to perform a
new Zero Detection cycle.
Be sure the actuator is not mounted upside down to avoid any
damage due to condensation from the valve stem. Please
note that care must be taken to actuator installation: little
angular deviations can compromise the correct actuator
operation
2.1.6Settings
Actuator M5004 is delivered already set at max flow rate of
the valve where it is mounted (SET 4); if it is bought as spare
part, the customer must inform Honeywell about valve type
the actuator will be mounted on, allowing Honeywell's
technicians to properly set it.
When the actuator is powered, the valve V5004TF
corresponding code is displayed on the 4 digits screen. Verify
using the table at the end of the next page that the shown
code corresponds the installed valve. If an issue occurs,
contact Honeywell’s technicians.
To set the actuator, use the 3 buttons and the display on the
upper side. When it is switched on, the Zero Detection
function automatically starts: the display shows “Go 0“. Do not
carry out any operation while the actuator is running and the
end stroke is found: finally it displays “0”. To enter the settings
browser, push the button MODE. Use UP and DOWN buttons
to select the parameter, then push MODE to show different
options (option browsing is carried out through UP and
DOWN buttons); push MODE to confirm the selection.
Operating temperatures
Ambient temperature range: -20°C…+60°C*
1
Storage temperature range: -20°C...+80°C*
1
Specifications
Weight: 0.975
kg
Power supply:
24V AC/DC – 50/60 Hz
Connecting cable:
18 AWG
Connection to valve:
8mm square. Easy fitting
gear
Operating life:
50.000 cycles
Control signal:
0(2)-10V 0(4)-20mA
(with 500
Ω
resistor*)
ON/OFF
3 points floating PWM
Power consumption:
5 W; 2.5 W stand-by
Nominal torque:
10 Nm Max, self-limited at 7
Nm
Current absorption:
80 mA, Load max 380 mA
Feedback:
0(4) - 20 mA and 0(2) – 10 V
Manual Override:
Through release button and
6mm Allen key
Protection class / IP Rating: II / IP54
Motor: Brushless
DC
motor
Running speed:
Selectable: 1 RPM or 1.5
RPM
Fail safe:
Through additional battery
SET1
Input indication selection with internal
control signal
SET2
Control signal selection
SET3
Min. flow setting
SET4
Max. flow setting
SET5
Setting display mode during operation
SET6
Rotation angle compensation
SET7
Flow offset compensation
SET8
Power failure mode
SET9
Flow rate unit selection
SET10
Control curve selection
SET11
Max. voltage control signal
SET12
Min. voltage control signal
SET13
Actuator rotation speed
SET14
Feedback signal selection