PRODUCT DATA
60-2099-9
® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
V4062A,B,D
HI-LO-OFF Fluid Power
Gas Valve Actuator
APPLICATION
The V4062 Gas Valve Actuator in combination with a V5055,
VE5000
a
or V5097 Gas Valve provides three-position control
of the gas supply to commercial and industrial burners.
FEATURES
• When energized, the V4062 Actuator opens the
V5055/VE5000/V5097 Gas Valve to the low-fire
position. The actuator opens the valve to the fully open
position when the line voltage contacts are made.
a
VE5000 is a European manufactured and approved valve for
European use only.
• When used with the V5055, V5097 or VE5000
a
Gas
Valve, the combination is rated for final safety shutoff
service.Although the V4062 can be used with all V5055
or V5097 Valve models, the V5055/V5097B with
characterized guide is recommended for optimum
control and low-fire repeatability.
• The standard model has an opening time of
26 seconds at 60 Hz, or 32 seconds at 50 Hz. A
fast-opening model is available, with timings of
13 seconds at 60 Hz, or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard, insurer requirements.
• Damper shaft models are available with or without
spring return; shaft extends out both sides and rides
in Delrin bushings; used with standard damper crank
arm (part no. 7616BR).
• Red OPEN indicator attached to the actuator stem
shows when the valve is even slightly open; yellow
SHUT indicator on the valve stem shows only when
the gas valve is fully closed.
• Ambient temperature range is -40° to 150°F (-40° to
66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for
50 Hz and 50/60 Hz models.
• Models available with factory adjusted, field-
adjustable, single-pole-double throw (spdt) auxiliary
switch rated at 1/2 hp (0.37 kW). Auxiliary switch can
be added in the field.
• Low-fire position is adjustable with adjusting wrench,
part no. 135796 (included with the actuator).
• Standard enclosure meets NEMA 1 (IP30) general
purpose requirements.
• V4062/V5055C,E and V4062/V5097C,E combinations
available with a proof-of-closure switch and double
valve seal (valve seal overtravel interlock) to meet
specific code/standard/insurer requirements.
• Model available to be used with series 60 floating type
controller.
• Model available with adjustable maximum flow switch.
Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Adjustments ......................................................................
Operation ..........................................................................
Service and Checkout ......................................................