V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

5

60-2099—9

Install Valve

The actuator is installed directly on the V5055/V5097 body 

after the valve is installed in the gas supply line. Refer to the 

instructions packed with the V5055/V5097 Gas Valve for 

installation details. When installing the valve, assure that:

1.

Sufficient clearance is allowed for actuator installation 

and service.

2.

Ambient temperatures at the valve location do not 

exceed actuator ratings.

3.

Position of the valve permits damper hookup if one is 

controlled.

Install Accessory Switches (If Needed)

An spdt switch can be installed to operate an auxiliary load up 

to 1/2 hp (0.37 kW). The switch can be adjusted to operate at 

any point in the valve stroke.

A proof-of-closure switch can also be installed with a 

V5055/V5097C or E Valve (with double seal) on any V4062 

Actuator to provide a valve seal overtravel interlock. The spdt 

proof-of-closure switch is installed to make or break a circuit 

when the valve is in the closed position. The switch is not 

adjustable.

NOTE: Mark the actuator or valve to indicate any changes 

made.

To install the switches, proceed as follows:

1.

Remove the actuator faceplate (two screws).

2.

Remove the silver-colored barrier to expose the 

actuator stem.

3.

Insert the auxiliary switch in the position indicated in 

Fig. 2. Fasten with two screws through the actuator 

base.

4.

Insert the proof-of-closure switch in the position shown 

in Fig. 2. The proof-of-closure switch mounts against 

the side of the actuator housing. The mounting holes 

are spaced to allow mounting the switch only in the 

correct position. Fasten with two screws through the 

actuator base.

5.

If only one switch is used, install the narrow barrier 

included with the switch in the unused space.

6.

Mount the actuator before making wiring connections 

and adjustments to the auxiliary switch.

Fig. 2. V4062 Actuator with cover removed.

Mount Actuator On Valve

Check the final position of the V5055/V5097 Valve body to 

be sure that the actuator will be in the proper position when 

mounted on the valve. This is especially important when the 

actuator is used to drive a damper.

If two smaller size valves are mounted very close together, 

as in an Industrial Risk Insurers type valve train, it may be 

necessary to mount the actuators off center to provide 

adequate clearance.

Slip the bottom collar of the actuator over the valve bonnet 

assembly. Rotate the actuator to the desired position and use 

a 5/32-inch Allen wrench to securely tighten the two setscrews 

(50 to 60 lb-in. [5.7 to 6.8 N•m]). Connect the damper linkage, 

if used. Refer to the instructions packed with the damper 

crank arm.

133568
AUXILIARY
SWITCH

133569
VALVE-CLOSED
INDICATION
SWITCH

AUXILIARY
SWITCH
ADJUSTMENT
SCREW

LOW-FIRE
ADJUSTMENT CAM

M7338B

Содержание V4062A

Страница 1: ...ch meets code standard insurer requirements Damper shaft models are available with or without spring return shaft extends out both sides and rides in Delrin bushings used with standard damper crank arm part no 7616BR Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed Ambie...

Страница 2: ...e conditions are changed Models V4062A HI LO OFF Gas Valve Actuator V4062B HI LO OFF Gas Valve Actuator high pressure V4062D HI LO OFF Gas Valve Actuator with proof of closure switch Use with V5055 V5097C E double seal gas valves for valve seal overtravel interlock Do not use V4062 with V5034 Valve body Electrical Ratings Standard V4062A D Actuators Table 1 60 Hz 26 second opening 50 Hz 32 second ...

Страница 3: ...3 mm radius for 7616BR Damper Crank Arm ordered separately NOTE Damper shaft drives damper crank arm in one direction only optional return spring is available on damper shaft to turn damper crank arm in opposite direction See Table 6 Table 6 Actuator Torque With and Without Return Spring Ambient Operating Temperature Rating 40 to 150 F 40 to 66 C for 60 Hz models 10 to 158 F 23 to 70 C for 50 Hz a...

Страница 4: ...y switch and or proof of closure switch if used must not exceed the ratings given in the Specifications section 4 When replacing a V6034 Actuator with a V4062 the V5034 Valve body must be changed to a V5055 Valve 5 Do not attempt to use the V4062 Actuator with the V4055 V5034 Adapter Differences in stem travel can prevent correct low fire adjustment Valve Sizea in V5055 V5097 Dim A Dim B Dim C Dim...

Страница 5: ... in the position indicated in Fig 2 Fasten with two screws through the actuator base 4 Insert the proof of closure switch in the position shown in Fig 2 The proof of closure switch mounts against the side of the actuator housing The mounting holes are spaced to allow mounting the switch only in the correct position Fasten with two screws through the actuator base 5 If only one switch is used insta...

Страница 6: ...o control the valve When all wiring connections are complete replace the actuator faceplate CAUTION Equipment Damage Hazard Can cause equipment damage or improper and dangerous operation Label all wires prior to disconnection when servicing valves Wiring errors can cause improper and dangerous operation Fig 4 Typical hookup for V4062 Actuator Fig 5 Connecting Max Flow Limit Switch to the actuator ...

Страница 7: ...rmined low fire setting for the burner being used 5 Tighten the setscrew in the cam 6 Replace the wiring compartment cover Alternate Procedure To adjust the low fire setting after the burner is in operation use the following instructions 1 Remove the wiring compartment cover 2 Check to be sure the low fire adjustment is set at MAX to assure a safe lightoff Low fire adjustment is preset at the fact...

Страница 8: ...UTION Equipment Damage Hazard Unskilled technicians can damage the equipment Only experienced trained flame safeguard control service technicians should service or replace this control Service The actuator is not field repairable except for replacing the auxiliary switch or valve closed indication switch See Installation section for procedure Do not disassemble the valve actuator If the actuator s...

Отзывы: