V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

3

60-2099—9

Table 4. Pressure Ratings of Valve-Actuators Combinations.

a

 Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal overtravel interlock.

b

 Maximum operating pressure differential.

c

 Maximum closeoff pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be 

subjected when fully closed, and is independent of the valve body rating.

Table 5. Auxiliary Switch and Proof-of-Closure 

Switch Ratings (1/2 hp [0.37 kW]

a

).

a

Maximum total connected power to both switches (if used)

 is 1800 VA.

Mounting:

Mounts directly to V5055/V5097 Valve with two setscrews 

positioned 90 degrees apart. 

Valve and actuator can be mounted in any position 

(multipoise). 

NOTE: 220 to 240 Vac, 50/60 Hz models must be mounted 

vertically.

Mounting Dimensions:  

See Fig. 1 and Table 7.

Low-Fire Adjustment:  

0.17 inch to 0.64 inch (with respect 

to V5055/V5097B Valve) valve stem travel. 

NOTE: The low-fire position of the V5055/V5097A,C,D and 

E Valves differ from the V5055/V5097B. Check the 

valve flow curves and match the low-fire position to 

the burner design and valve application.

Nominal Opening Time:

Standard Models: 26 sec at 60 Hz; 32 sec at 50 Hz.

Fast-opening Models: 13 sec at 60 Hz; 16 sec at 50 Hz.

Closing Time:  

1 sec maximum

Damper Shaft: 

3/8 in. sq (9.5 mm) for use with 7616BR 

Damper Crank Arm (not included). Models available with or 

without damper shaft return spring.

Maximum Damper Shaft Rotation: 

52 angular degrees.

Maximum Force: 

At 2-11/16 in. (68.3 mm) radius for 7616BR 

Damper Crank Arm (ordered separately).

NOTE: Damper shaft drives damper crank arm in one 

direction only; optional return spring is available on 

damper shaft to turn damper crank arm in opposite 

direction. See Table 6.

Table 6. Actuator Torque (With 

and Without Return Spring).

Ambient Operating Temperature Rating:

-40° to 150°F (-40° to 66°C) for 60 Hz models;

-10° to 158°F (-23° to 70°C) for 50 Hz and 50/60 Hz models.

Approvals:

Underwriters Laboratories Inc. Listed: File No. MH1639, 

Guide No. YIOZ.

Factory Mutual: Approved.

International Approval Services (Joint Venture of the 

American Gas Association [AGA] and the Canadian Gas 

Association [CGA]): Certified 60 Hz models only.

Industrial Risk Insurers Acceptable.

Some V4062 Actuators are approved as Class A valves in 

accordance with EN161:

When used with V5055 Valves: Pin: CE-0063AR1359.

When used with VE5000 Series Valves: Pin: 

CE-0063AP3075.

Accessories:

133568 Auxiliary Switch Bag Assembly.

133569 Proof-of-Closure Switch Bag Assembly. (Must be 

used with a V5055/V5097C or E with double seal).

135796 Wrench (included with the actuator).

7616BR Damper Crank Arm (damper arm and clip).

Valve

V4062A,D Actuator

a

V4062B Actuator

Differential

b

Closeoff

c

Differential

b

Closeoff

c

psi

mbar

psi

bar

psi

mbar

psi

bar

V5055A,C; V5097A,C 3/4 to 3 in.

5

340

15

1

15

1000

15

1

V5055A,C 4 in.

3

200

15

1

5

340

15

1

V5055B, V5097B 3/4 to 3 in.

5

340

15

1

15

1000

15

1

V5055B 4 in.

3

200

5

1

5

340

15

1

V5055D,E, 3/4, 1, 1-1/4, 1-1/2; 

V5097D 3/4 in. to 2 in. 

5

340

75

5

25

1700

75

5

V5055D,E; V5097D,E 2, 2-1/2, 3 in. 5

340

45

3

15

1000

45

3

Load

120/v

240V

Full Load

9.8A

4.9A

Locked Rotor

58.8A

29.4A

V4062 Model

-40°F to +20°F

(-40°C to -7°C)

20°F to 150°F 

(-7°C to +66°C)

lb

N

lb

N

Without return spring 5

22.2

20

89.0

With return spring

5

22.2

10

44.5

Содержание V4062A

Страница 1: ...ch meets code standard insurer requirements Damper shaft models are available with or without spring return shaft extends out both sides and rides in Delrin bushings used with standard damper crank arm part no 7616BR Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed Ambie...

Страница 2: ...e conditions are changed Models V4062A HI LO OFF Gas Valve Actuator V4062B HI LO OFF Gas Valve Actuator high pressure V4062D HI LO OFF Gas Valve Actuator with proof of closure switch Use with V5055 V5097C E double seal gas valves for valve seal overtravel interlock Do not use V4062 with V5034 Valve body Electrical Ratings Standard V4062A D Actuators Table 1 60 Hz 26 second opening 50 Hz 32 second ...

Страница 3: ...3 mm radius for 7616BR Damper Crank Arm ordered separately NOTE Damper shaft drives damper crank arm in one direction only optional return spring is available on damper shaft to turn damper crank arm in opposite direction See Table 6 Table 6 Actuator Torque With and Without Return Spring Ambient Operating Temperature Rating 40 to 150 F 40 to 66 C for 60 Hz models 10 to 158 F 23 to 70 C for 50 Hz a...

Страница 4: ...y switch and or proof of closure switch if used must not exceed the ratings given in the Specifications section 4 When replacing a V6034 Actuator with a V4062 the V5034 Valve body must be changed to a V5055 Valve 5 Do not attempt to use the V4062 Actuator with the V4055 V5034 Adapter Differences in stem travel can prevent correct low fire adjustment Valve Sizea in V5055 V5097 Dim A Dim B Dim C Dim...

Страница 5: ... in the position indicated in Fig 2 Fasten with two screws through the actuator base 4 Insert the proof of closure switch in the position shown in Fig 2 The proof of closure switch mounts against the side of the actuator housing The mounting holes are spaced to allow mounting the switch only in the correct position Fasten with two screws through the actuator base 5 If only one switch is used insta...

Страница 6: ...o control the valve When all wiring connections are complete replace the actuator faceplate CAUTION Equipment Damage Hazard Can cause equipment damage or improper and dangerous operation Label all wires prior to disconnection when servicing valves Wiring errors can cause improper and dangerous operation Fig 4 Typical hookup for V4062 Actuator Fig 5 Connecting Max Flow Limit Switch to the actuator ...

Страница 7: ...rmined low fire setting for the burner being used 5 Tighten the setscrew in the cam 6 Replace the wiring compartment cover Alternate Procedure To adjust the low fire setting after the burner is in operation use the following instructions 1 Remove the wiring compartment cover 2 Check to be sure the low fire adjustment is set at MAX to assure a safe lightoff Low fire adjustment is preset at the fact...

Страница 8: ...UTION Equipment Damage Hazard Unskilled technicians can damage the equipment Only experienced trained flame safeguard control service technicians should service or replace this control Service The actuator is not field repairable except for replacing the auxiliary switch or valve closed indication switch See Installation section for procedure Do not disassemble the valve actuator If the actuator s...

Отзывы: