V4043, V4044 VALVES; V8043, V8044 ZONE VALVES

3

95-6983—11

3.

IMPORTANT: Take care not to burn the plastic por-
tion of the composite adapter plate when soldering.

4.

Sweat the joints, keeping the outer surface free 
from solder. DO NOT use silver solder because of 
the high melting temperature required. 

To Install Replacement Powerhead

SYSTEMS WITH OLD STYLE VALVE BODIES (SERIES 
1-5)

To install a replacement powerhead in a system with an 
old style body (series 1-5), the valve body must be 
converted to accept the new powerhead using Part No. 
40003918 Conversion Kit. The kit includes a metal plate 
with a driveshaft and rubber plug, O-ring, and four screws. 

IMPORTANT 

Converting the valve body for use with the new 
powerhead does not require removal of the valve 
body from the pipeline. However, it is necessary 
to drain the water from the system before begin-
ning the conversion. 

1.

Disconnect the power supply before connecting the 
wiring to prevent electrical shock or equipment 
damage. 

2.

Disconnect the leadwires to the powerhead at the 
terminal block or conduit connection. Remove the 
conduit or cable connector if fitted. Label each wire 
for rewiring later. 

3.

Drain the water from the system. 

4.

Remove the old powerhead from the valve body 
(Fig. 4)
a. Place the manual opening lever (normally 

closed models only) on the old powerhead in 
the MAN. OPEN position (see Fig. 4A). 

b. Remove the cover (Fig. 4B). 
c. With the cover off, remove the four screws 

securing the powerhead to the valve body. 

d. Lift the powerhead off the valve body (Fig. 4C). 
e. Remove the O-ring from the top of the valve 

body. 

Fig. 4. Remove old powerhead from systems using old style valve bodies

5.

Install 40003918 Conversion Kit (Fig. 5)
a. Insert the new O-ring in the valve body. 
b. Place metal plate with the rubber plug on top of 

the valve body. Make sure the guide pins on the 
underside of the metal plate fit into the recesses 
on the valve body. 

c. Secure the metal plate to the valve body with 

the four screws (two sets) provided. One set of 
screws has heads with recessed threads to 

insert screws for mounting the new powerhead; 
insert this set into the larger screw openings. 
The other set has domed heads; insert this set 
into the smaller screw openings. Each set of 
screws must be inserted in opposite corners of 
the metal plate so the screws sit flat on the 
plate. Make sure the guide pins on the plate fit 
into the recesses on the valve body. 

A

AUTO

MAN

OPEN

MANUAL 
OPENING 
LEVER

COVER
RETAINING
SCREW

M10174

A

B

V8043F 1051

24V 50/60  CY

.32 AMP

 @ 60 CY

MADE IN CANADA

6

A

B

V8043F 1051

24V 50/60  CY

.32 AMP

 @ 60 CY

MADE IN CANADA

6

A

B

C

Содержание V4043

Страница 1: ... valve must be disassembled be certain that it is reassembled with the water flow in the direction of the arrow Reversal of the powerhead will result in damage to the gear train 3 On 24V systems never jumper the valve coil terminals even temporarily This may burn out the heat anticipator in the thermostat IMPORTANT Use this valve in hydronic heating systems which do not contain dissolved oxygen in...

Страница 2: ... B should be connected to the coil bypass Fig 3 Inlet and outlet ports on straight through and diverting valves FLARE FITTING MODELS Use new properly reamed pipe free from chips The valve body is threaded for standard 5 8 in OD copper 45 degree SAE flare fitting nuts These nuts are not furnished with the valve and must be obtained separately SWEAT COPPER MODELS 1 Use new properly reamed pipe free ...

Страница 3: ...emove the old powerhead from the valve body Fig 4 a Place the manual opening lever normally closed models only on the old powerhead in the MAN OPEN position see Fig 4A b Remove the cover Fig 4B c With the cover off remove the four screws securing the powerhead to the valve body d Lift the powerhead off the valve body Fig 4C e Remove the O ring from the top of the valve body Fig 4 Remove old powerh...

Страница 4: ...he valve body remains in the pipeline 1 Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage 2 Disconnect the leadwires to the powerhead at the terminal block or conduit connection Remove the conduit or cable connector if fitted Label each wire for rewiring later 3 Remove the old powerhead see Fig 7 a Place the manual opening lever normally close...

Страница 5: ...e connecting wiring to prevent electrical shock or equipment damage All wiring must comply with local codes and ordinances Connections to the individual valves are shown in Fig 8 9 See Fig 10 through 16 for typical hookups If replacing a Taco Dole Flair or White Rodgers 3 wire valve with a 2 wire V8043E or F see Fig 17 through 29 Check that the pressure rating of the new valve is appropriate for t...

Страница 6: ... CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT CONNECT V8043E RED LEADWIRES TO L1 HOT LINE AND PRIMARY CONTROL T822 T822 T822 V8043E V8043E V8043E M10169 TO OIL PRIMARY CONTROL OR TO TRANSFORMER AND LOW VOLTAGE GAS VALVE L4006A HIGH LIMIT CIRCULATOR RED BLUE YELLOW MOTOR HEATING COOLING THERMOSTAT TO POWER V4044 V8044 VALVE OPERATOR AQUASTAT CHANGEOVER CONTROL SWITCHES TO HEATING RED AT FLUID TEMPE...

Страница 7: ...A PANEL B R B W BR B R B W BR B R B W BR B R B W BR T87F L1 HOT L2 POWER SUPPLY B R B W BR RED RED YELLOW ZONE V8043E YELLOW W775A PANEL RED YELLOW RED YELLOW T87F T87F CONNECTIONS FOR V8043E LEADWIRE MODEL ZONE 1 T87F ZONE 2 ZONE 3 ZONE 4 ZONE 5 V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043E V8043E T87F T87F T87F T87F M10164 YELLOW RED YELLOW RED ...

Страница 8: ...HOT L2 1 E M5960 A B C D THERMOSTAT END SWITCH V8043F TH TR TH TR L1 HOT L2 1 E TO AUXILIARY CIRCUITS TO AUXILIARY CIRCUITS POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 L1 HOT L2 1 A B F D E THERMOSTAT DOLE VALVE TO TERMINALS T T ON BURNER RELAY 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M5977 1 2 3 4 C L1 HOT L2 1 A B C D E THERMOSTA...

Страница 9: ...OTECTION AS REQUIRED M5711 1 2 3 4 5 6 4 5 6 1 1 L1 HOT L2 THERMOSTAT TO AUXILIARY CIRCUIT YELLOW RED RED TO 6 ON THERMOSTAT TO AUXILIARY CIRCUIT YELLOW YELLOW RED RED POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM TAPE UNUSED END AND TUCK INTO HOLE 1 2 3 5 4 6 M5712 1 2 3...

Отзывы: