INSTALLATION INSTRUCTIONS

Place Bar Code Here

95-6983-11

V4043, V4044 Valves; 
V8043, V8044 Zone Valves

APPLICATION

These valves consist of an actuator motor and valve 
assembly for controlling the flow of hot and/or cold water. 
The V4043 and V8043 provide two-position, straight-
through control of supply water. The V4044 and V8044 
provide two-position, diverting control of supply water. 
The valves are designed for use with fan coil and other 
units requiring quiet, compact water valves. The V8043E 
and F also control supply water for baseboard radiators 
and convectors. The V4043E and V8043J provide 
straight-through control of steam only. Models are 
available with 125 or 300 psi operating pressure.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition. 

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application. 

3.

Installer must be a trained, experienced service 
technician. 

4.

After installation is complete, check out product 
operation as provided in these instructions

CAUTION

1.

Disconnect power supply before connecting 
wiring to prevent electrical shock of equip-
ment damage.

2.

Normally it is not necessary to remove the 
powerhead from the valve body during instal-
lation. If the valve must be disassembled, be 
certain that it is reassembled with the water 

flow in the direction of the arrow. Reversal of 
the powerhead will result in damage to the 
gear train. 

3.

On 24V systems, never jumper the valve coil 
terminals even temporarily. This may burn 
out the heat anticipator in the thermostat. 

IMPORTANT 

Use this valve in hydronic heating systems 
which do not contain dissolved oxygen in the 
system water. The dissolved oxygen, which is 
found in systems that have a frequent source of 
makeup water, causes the rubber plug inside 
the valve to deteriorate and eventually fail. 

LOCATION

Install the valve in an area with adequate clearance to:

Move the manual opening lever on the side of the 
powerhead.

Remove the powerhead cover.

Wire the powerhead.

Replace the powerhead motor.

The valve location should be in an area where the 
temperature does not exceed the maximum valve 
operating temperature as shown in Fig. 1. The maximum 
valve operating temperature depends on the maximum 
ambient temperature at the valve location and the 
maximum fluid temperature. Using the graph in Fig. 1, 
the maximum valve operating temperature can be found 
as follows:

1.

Measure ambient temperature at valve and locate 
this temperature on the ambient temperature scale 
on the graph.

2.

Draw a line from this ambient temperature, parallel 
with the fluid temperature scale, to the maximum 
fluid temperature line.

3.

Draw a line from this point down to the fluid temp-
erature scale to find maximum operating tempera-
ture. (Note the example, shown by the dashed line 
in Fig. 1).

Содержание V4043

Страница 1: ... valve must be disassembled be certain that it is reassembled with the water flow in the direction of the arrow Reversal of the powerhead will result in damage to the gear train 3 On 24V systems never jumper the valve coil terminals even temporarily This may burn out the heat anticipator in the thermostat IMPORTANT Use this valve in hydronic heating systems which do not contain dissolved oxygen in...

Страница 2: ... B should be connected to the coil bypass Fig 3 Inlet and outlet ports on straight through and diverting valves FLARE FITTING MODELS Use new properly reamed pipe free from chips The valve body is threaded for standard 5 8 in OD copper 45 degree SAE flare fitting nuts These nuts are not furnished with the valve and must be obtained separately SWEAT COPPER MODELS 1 Use new properly reamed pipe free ...

Страница 3: ...emove the old powerhead from the valve body Fig 4 a Place the manual opening lever normally closed models only on the old powerhead in the MAN OPEN position see Fig 4A b Remove the cover Fig 4B c With the cover off remove the four screws securing the powerhead to the valve body d Lift the powerhead off the valve body Fig 4C e Remove the O ring from the top of the valve body Fig 4 Remove old powerh...

Страница 4: ...he valve body remains in the pipeline 1 Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage 2 Disconnect the leadwires to the powerhead at the terminal block or conduit connection Remove the conduit or cable connector if fitted Label each wire for rewiring later 3 Remove the old powerhead see Fig 7 a Place the manual opening lever normally close...

Страница 5: ...e connecting wiring to prevent electrical shock or equipment damage All wiring must comply with local codes and ordinances Connections to the individual valves are shown in Fig 8 9 See Fig 10 through 16 for typical hookups If replacing a Taco Dole Flair or White Rodgers 3 wire valve with a 2 wire V8043E or F see Fig 17 through 29 Check that the pressure rating of the new valve is appropriate for t...

Страница 6: ... CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT CONNECT V8043E RED LEADWIRES TO L1 HOT LINE AND PRIMARY CONTROL T822 T822 T822 V8043E V8043E V8043E M10169 TO OIL PRIMARY CONTROL OR TO TRANSFORMER AND LOW VOLTAGE GAS VALVE L4006A HIGH LIMIT CIRCULATOR RED BLUE YELLOW MOTOR HEATING COOLING THERMOSTAT TO POWER V4044 V8044 VALVE OPERATOR AQUASTAT CHANGEOVER CONTROL SWITCHES TO HEATING RED AT FLUID TEMPE...

Страница 7: ...A PANEL B R B W BR B R B W BR B R B W BR B R B W BR T87F L1 HOT L2 POWER SUPPLY B R B W BR RED RED YELLOW ZONE V8043E YELLOW W775A PANEL RED YELLOW RED YELLOW T87F T87F CONNECTIONS FOR V8043E LEADWIRE MODEL ZONE 1 T87F ZONE 2 ZONE 3 ZONE 4 ZONE 5 V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043E V8043E T87F T87F T87F T87F M10164 YELLOW RED YELLOW RED ...

Страница 8: ...HOT L2 1 E M5960 A B C D THERMOSTAT END SWITCH V8043F TH TR TH TR L1 HOT L2 1 E TO AUXILIARY CIRCUITS TO AUXILIARY CIRCUITS POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 L1 HOT L2 1 A B F D E THERMOSTAT DOLE VALVE TO TERMINALS T T ON BURNER RELAY 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M5977 1 2 3 4 C L1 HOT L2 1 A B C D E THERMOSTA...

Страница 9: ...OTECTION AS REQUIRED M5711 1 2 3 4 5 6 4 5 6 1 1 L1 HOT L2 THERMOSTAT TO AUXILIARY CIRCUIT YELLOW RED RED TO 6 ON THERMOSTAT TO AUXILIARY CIRCUIT YELLOW YELLOW RED RED POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM TAPE UNUSED END AND TUCK INTO HOLE 1 2 3 5 4 6 M5712 1 2 3...

Отзывы: