PRODUCT DATA

31-00403-02

UVL-FCU Ultraviolet Lamp Kits for 
Fan Coil and PTAC Units

APPLICATION

Honeywell UVL-FCU kits make it possible to realize all the 
benefits of germicidal UV light in limited space 
applications including most of the fan coil units and 
PTACs found on the market today. The kit features a low-
profile lamp with metal shield and mounting magnet as a 
means for locating the UV light within these units for 
optimum UV exposure particularly where space is limited.

FEATURES

• UV-C light irradiates coil, killing mold, bacteria and 

viruses

• Installs in the tightest spaces such as PTACs and Fan 

Coil Units

• Weather resistant remote mountable UV lamps with 

magnetic mounting shield

• 18-32 or 110-277 VAC power supply with flexible 

mounting options

• Reduces system maintenance
• Kit includes power supply, 6 foot lamp cable, UV lamp 

and shield, magnetic mounting hardware and panel 
indicator

SPECIFICATIONS

Models:

See Table 1.

Efficiencies:

99.9% disinfection of irradiated surfaces when properly 

positioned

Approvals:

ETL/CSA, RoHS standard 2011/65/EU
EPA Est. No. 075179-FL-2

Electrical Ratings:

Power Rating:

UVL-FCU-LINE: 120-277 Vac, 50/60 Hz
UVL-FCU-LOW: 18-32 Vac, 60Hz

Current Rating:

UVL-FCU-LINE: 0.51 A @ 120 Vac, 0.22 A @ 277 Vac
UVL-FCU-LOW: 0.68 A, 16 VA

Dimensions:

Power Supply:

UVL-FCU-LINE: 5.0 in x 1.1 in x 2.4 in (127 mm x 27.9 

mm x 61.0 mm)

UVL-FCU-LOW: 4.1 in x 1.7 in x 1.8 in (104 mm x 43.2 

mm x 45.7 mm)

Bulb: 1 inch diameter x 14 inch length (25.4 mm diameter 

x 356 mm length)

Spectrum:

100% 254 nm Germicidal UV-C

Bulb Type:

Shielded Quartz Hot Filament

Bulb Life:

18000 hours

Accessories:

UVL-FCU-LAMP Replacement UV-C lamp

* Power supply not available for purchase outside of kit

Table 1. Models.

Part Number

Description

Replacement Lamp

Power Supply*

UVL-FCU-LINE

FCU/PTAC 110-277 Vac, 50/60 Hz

UVL-FCU-LAMP 
(MFG# TUVL-200EZ)

(MFG# TUVP-ST-CE)

UVL-FCU-LOW

FCU/PTAC 18-32 Vac, 60 Hz

UVL-FCU-LAMP 
(MFG# TUVL-200EZ)

(MFG# TUVP-ER)

Содержание UVL-FCU-LINE

Страница 1: ...ic mounting hardware and panel indicator SPECIFICATIONS Models See Table 1 Efficiencies 99 9 disinfection of irradiated surfaces when properly positioned Approvals ETL CSA RoHS standard 2011 65 EU EPA Est No 075179 FL 2 Electrical Ratings Power Rating UVL FCU LINE 120 277 Vac 50 60 Hz UVL FCU LOW 18 32 Vac 60Hz Current Rating UVL FCU LINE 0 51 A 120 Vac 0 22 A 277 Vac UVL FCU LOW 0 68 A 16 VA Dime...

Страница 2: ...se Kit includes one power supply LOW or LINE depending on model Fig 1 Parts WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cau...

Страница 3: ...d Can cause electrical shock or equipment damage Do not connect to power before installation is complete Installation in PTACs and Fan Coils 1 Determine the best position for placement of the UV lamp and power supply Fig 2 Fig 4 2 Position lamp for best UV exposure and to minimize light leakage into the room 3 Locate lamp so it irradiates wet side of coil and or blower areas where fouling is prese...

Страница 4: ...uded slit loom tubing for addi tional protection of the power supply wires that may be mounted near the heating elements Find a suitable location for the power supply inside the control panel of the air handler Install using the self tapping screws Fig 5 Power Supply Installation Sight Glass Installation Sight glass may not be needed if reflected UV light is visible 1 Find a suitable location on t...

Страница 5: ...f grease or other contaminants and are NOT affected by humidity They are warranted for 2 years of UVC output to 60 of their original output Sizing guidelines are based on the end of lamp life output levels Honeywell UV lamps are rated for two years germicidal effectiveness The visible blue light will continue to illuminate but does NOT have any germicidal effectiveness Bulbs must be replaced on sc...

Отзывы: