Modbus Read, Write and Override Parameters plus Exception Codes
10.7.11 Alarms
Table 10-19 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Alarms.
Table 10-19 Set-up Group – Alarms
Parameter
Description
Register
Address
Access
Data Range or
Enumerated Selection
Hex
Alarm 1 Setpoint 1
Value
0009
R/W
009
FP
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 1 Setpoint 2
Value
000A 010
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 2 Setpoint 1
Value
000B 011
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 2 Setpoint 2
Value
000C 012
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 1 Setpoint 1
Type
008C 140
INT R/W
0 = None
1 = Input 1
6 = Alarm on Shed
2 = Input 2
3 = PV
4 = Deviation
5 = Output
7 = SP Event On
8 = SP Event Off
9 = Manual
10 = Remote Setpoint
11 = Failsafe
12 = PV Rate of Change
13 = Alarm on Digital
Input 1
14 = Alarm on Digital
Input 2
15 = Loop Break
16 = T/C Warning
17 = T/C Fail
18 = PV Hot Start
Data
Type
Decimal
216
UDC3200 Universal Digital Controller Product Manual
12/04