Input Calibration
5.4.4 Radiamatic, Millivolts, Volts or Thermocouple Differential Inputs
Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-6.
Table 5-6 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts or
Thermocouple Differential Inputs (Except 0-10 Volts)
Step
Action
1
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-5.
2
Place current/voltage source at zero before switching on.
3
Do not switch current/voltage source ON/OFF while connected to the instrument.
ATTENTION
For Radiamatic inputs only, set Emissivity value to 1.0.
See:
Set Up prompt INPUT 1, function prompt EMISSIV 1
Set Up prompt INPUT 2, function prompt EMISSIV 2
XXXX
Millivolt or
Volt Source
+
_
26 +
27 -
25
23 +
24 -
22
Input 1
Input 2
Figure 5-5 Wiring Connections for Radiamatic, Thermocouple Differential,
Millivolts or Volts (Except 0 to 10 Volts)
138
UDC3200 Universal Digital Controller Product Manual
12/04