UCIP-GPRS
HLSI-MA-192_05
Honeywell Life Safety Iberia, S.L. reserves the right to do any change in this information without notice.
For accurate and updated information go to
Read carefully the product manual before to install this material.
Technical features
UCIP / UCIP GPRS Default Settings
Status LEDs:
ALRM1
DL1-RED
- EXISTING DATA WITH CRA
ALRM2
DL2 RED
- EXIXTING DATA WITH PANEL
ALRM3
DL3-RED
-GPRS BIDIRECTIONALITY ACTIVE
ALRM4
DL4-RED
-TCP/IP BIDIRECTIONALITY ACTIVE
BLINK
DL5-GREEN
SOFTWARE WORKING
ON: Powered inactive process
Slow blinking : Process running OK
Off: Inoperative Process
COBER
DL6- BICOLOR
GSM Coverture
-
GREEN MAXIMUM COVERTURE
-
ORANGE MEDIUM COVERTURE
-
RED LOW COVERTURE
-
BLINK GPRS SERVER CONNECTED
TX MOD
DL7-GREEN
GSM MODEM CONNECTED
GPRS / GSM activity
ON: Modem Active(Calling)
IND01
DL9
– GREEN
OUTPUT 1 STATE ( Off means CRA link failure , after 5 retries)
IND02
DL8 - GREEN
OUTPUT 2 STATE (Off means Panel link fault)
TECHNICAL FEATURES:
Power
12 a 30 Vdc (not polarized) external or via Aux port
Current
45mA min / 150mA max.
Communication Ports
1 x RS232 (Rx,Tx GND from 1200 to 115200 Bds)
1 x Ethernet (ADSL, LAN, etceteras...)
1 x Modem GSM (GSM, SMS, GPRS)
1 x I2C double connector and power
1 x RS485
Configuration
Terminal console commands / Telnet over Ethernet and GPRS. Permits SMS message commands.
Serial port 232
Rx,Tx y GND. Configurable speed and parity (1200 to 115200 Bds)
Compatible Panels with SMS or Contact ID
NFS Supra, Vision Plus, Vision 2Plus, ID50, ID3000 and DXC CONNEXION
CRA Protocol and security
Double channel de transmission over Ethernet and GPRS
Connectivity checking (stay alive) and bidirectionality.
Ademco Contact ID protocol IP/GPRS to CRA over ALWON 128 encrypted AES128 compatible
protocol. Communicator switch security and config password key.
IP Connectivity
DNS compatible, DHCP and dynamic IP (IP update by alive string)
Firmware update
Via RS232 or GPRS by UCIP Consola Tool
Dimensions (w.o. box)
86mm height x102mm width x25mm depth
Enclosure Dimensions
102mm height x143mm width x39mm depth
Approvals
EN50136 SPT 1-6, Type X/Y
REQUIRED DATA TO CONNECT THE DEVICE:
For Ethernet:
UCIP IP in local network
Local Mask + Gateway
For GPRS:
APN GPRS net name
User
Password
SIM card PIN (or remove)
To a CRA:
Client Number/code
CRA IP
IP port
ALIVE time
Encryptation password
Information for the CRA
UCIP Production Serial #
S/N:
Protocol UCIP
Honeywell R TCPv9.0.2;R20;Lopez Bellov9.0.2 Receiver - Protocol Alwon 128 (Contact ID)
INFORMACIÓN DE PRODUCTO
:
The UCIP and UCIP-GPRS Communicator permits to connect panels via IP by Ethernet or/and GPRS.
UCIP/UCIP GPRS is compatible to connect to an IP Central Receiver Alarm center the Honeywell Fire Alarm Panels: Notifier:ID3000,
ID50, NFS Supra; Morley-IAS: CONNEXION, VSN-2Plus and ESSER: ESS-2PLUS.
UCIP-GPRS is shipped to be connected to the Honeywell GPRS APN to be linked to the FireIMT online server and associated services.
When UCIP is connected to he compatible panels it recognizes the panel protocol and its serial port is automatically set to communicate
with it. SIM card is detected at the device start up to start the GPRS modem. In some panels it is necessary to configure the Integration
protocol.
The UCIP SERIAL NUMBER is different on each device and must be indicated to the Central Alarm Receiver center to configure client.
DEFAULT SETTINGS:
Default settings includes:
-
Serial Port
to Fire panel link : 9600 Baud, no parity, to panel port RS232 or TTL (depending on port Jumpers).
-
GPRS Network
: SIM is required, configured to connect to Fire IMT server (port 5000) Requires SIM card provibed by Honeywell and
client settings)
-
ETHERNET
to remote link by port 5000 (TG):
IP UCIP: 192.168.0.100, Mask 255.255.255.0, Gateway 192.168.0.1, Ethernet port: 5000
-
CRA
: Requires CRA IP address configuration, by default sends System Alarm and Fault by zones state.
-
SMS
: SIM is required. No phone is configured: Sends complete information and device labels configured in the ID and DXc panels.
.
Configuration checking:
The device configuration can be checked by using the CONFIG command connected to device in the configuration mode.
>config
SERIAL NUMBER-
xxxxxxx
CRA1- Suscriber:, IP:0.0.0.0, Puerto:0, Alive:0, Key:, Channel:GPRS+ETH
CRA2- Suscriber:, IP:0.0.0.0, Puerto:0, Alive:0, Key:, Transmission: On fail of CRA 1; Channel:GPRS+ETH
SMS/DAY- Without limit ,Send: 0
TCP/IP- MAC:00-04-A4-01-00-05, IP:192.168.0.100, Mask:255.255.255.0, Gateway:192.168.0.1, DHCP:ON, Host:E20_5
TELNET- Port:23
UART1- Speed:9600, Parity:NONE
I2C- Local Address:40, Remote Address:0
RS485-Local Address:3, Remote Address:0
UDP-Address:0.0.0.0, Port:1
TCP SERVER-Port:5000
TCP CLIENT-Address:0.0.0.0, Port:1
GPRS- wlapn.com, User: honeywell, Password: honeywell
GPRS SOCKET-NONE
GPRS SERVER- Local Address:0.0.0.0, Local Port:5000
SMS ALARM- CRA:, User1:, User2:
Configuration commands:
CRA1
ACCOUNT IPADDRESS PORT ALIVE KEY: Configure the CRA account number, central IP,key and Alive period
CRA2
ACCOUNT IPADDRESS PORT ALIVE KEY TRANSMISSION: Configure the CRA2 account number, central IP,key and Alive period
CONFIG
PORT PARAM1 PARAM2:Config Port or display configuration
EVENT
EVENT CODE: Config ContactID event codes
EVENTNAME
EVENT NAME: Config event name
EXIT
:Exit program console
FAULT
FAULT CODE: Config fault codes
GSM
Modem GSM Communication console
GPRS
APN USER PASSWORD:Config GPRS network
INI
:Reset configuration (no borra IP ETH)
OUT
OUTPUT STATUS TIMER: Enable or disable digital output
PIN
PIN: SIM PIN settings
RESET
System Reset, Cold start
SMS
CENTRAL_PHONE USER_PHONE1 USER_PHONE2 MAXSMS: SMS parameters configuration
TCPIP
ADDRESS MASK GATEWAY DHCP:Config TCP/IP
ZONE
ZONE SENSOR MODULE FAULT DISABLE:Config zone event codes
ZONENAME
ZONE NAME: Config zone name
TCPIP
INI : Set default IP. The INI command does not change device IP.
CRA
X OFF: Erase CRA X(1 o 2) settings
Note
: Before to install the system, check and read carefully device
and connected panel manuals and don’t make any action before to understand them.