Honeywell Life Safety Iberia, S.L. reserves the right to do any change in this information without notice.     
For accurate and updated information go to  

www.honeywelllifesafety.es

 

Read carefully the product manual before to install this material.

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 

 
 

 

 
 
 
 
 

 

The SMB-T enclosure is designed to be installed on 
a Surface and inside some devices by using 
described holes: 

1- 

Surface 

mounting: Install the enclosure in the wall close to the 

panel by using holes marked as (1). 
2- 

Conventional panels NFS, VSN2 y ESS

: Open the panel box 

enclosure and remove the left Touch Display or user label plate. 
Install the box under the panel mains connector. Fit the box in 
the panel back box by the holes marked as 2) and slightly slide it 
downwards. 
3- Fit the UCIP Communicator in the SMB-T en closure by the 4 
screw holders marked 3).  

Installation 

SMB-T Enclosure installation 

Connections 

Standard cable holes 

Settings 

Cut the necessary holes in the SMB-T enclosure 

1- RS-232 Port or AUX Port (Panel cable link) 
2- RJ45 Ethernet port (Commissioning and  Network) 
3- GPRS antenna (UCIP GPRS only) 
4- 24Vcc External power 

Connect needed cables as below: 

     STATUS LEDS

 

Ethernet Network 
RJ45 

 

RS232 /  TTL* Serial port 

UCIP

 Uart1

 

PC Conf. 

DB9

 

DXc/ID3000 

RS232 (ISO232) 

ID60  

RS232

 

VSN&NFS  
TTL*    

RX 

TX 

TX 

RX 

GND 

0V 

4  

 
 
 

 

AUX.Port.* 

 

Jp3 Jp4

 

RS232 Config. 

The UCIP/GPRS can be configured by Ethernet port with RJ45 
network cable El UCIP/GPRS or by RS232 serial port (cable not 
provided), 

with it’s config tool, Hyperterminal or Telnet 

By default it has the following serial port and IP settings: 

 
Default Serial P. UCIP: 

Default IP address: 192.168.0.100 

 

RS232: 9600 Baud   

Mask: 255.255.255.0 

 

 

No parity    

 

Gateway:192.168.0.1 

 

 

Config. Port:23 

 

 

 
1- To configure UCIP via RS232 port, make the cable: RS232-PC Conf.DB9 
 
2- To configure UCIP via 

ETHERNET

, Configure your PC in the sane IP 

range as the UCIP: 

Windows

Start

 Control Panel

Network center 

 

Local area connection

change adapter settings

 Properties

 

Prot.Int(IPv4)

Properties

Alternative IP config: 

i.e.IP:192.168.0.50, Mask 255.255.255.0, Gateway

 

 192.168.0.1 

 

 

 

 
 
 
 
UCIP Console tool 
 
 
 
 
 
 
 
 
3-Abra la consola de config. deUCIP o el Hyperterminal de Windows y 
seleccione Puerto Serie y el puerto o TCP IP con la IP del UCIP  puerto 23: 
- Puerto Serie Com: 9600 bds,0,None,None  
- Puerto TCP IP Client: 192.168.0.100, Puerto 23 
Consola UCIP: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
4- Para acceder a Configuración , con el cursor en la ventana de conexión 
presione 3 veces la tecla "ESC" de su PC e inserte la clave "1234" 

Configuration Console / Hyperterminal 

ETHERNET UCIP local IP and Port ETHERNET 

TCPIP

 [local IP] [network Mask] [Gateway] [dhcp on/off] IP UCIP Config.: 

i.e. 

192.168.0.100,Mask:255.255.255.0,Gateway:192.168.0.1;DHCP:off

 

>TCPIP

 

192.168.0.100 255.255.255.0 192.168.0.1 off

 

 

>OK: Operation completed   

 

CONFIG

 [Port] [Parameter] : 

Set IP port i.e..

5000

 

>CONFIG TCPSERVER

 

5000

   

 

>OK: Operation completed   

Note: In TG supervisor, set in panel config. Link : TCP/IP, permits multiple link 
 

 

Config GPRS Network (i.e.FireIMT)

 

PIN 

[SIM PIN] : PIN of SIM card.. 

-Recommended to remove SIM PIN in a celular pone to 
avoid lock it on error. 

Ej. PIN XXXX. SIM must be placed to check the PIN 

>PIN

 

XXXX

 

 

>OK: Operation completed   

 
GPRS

 [APN mobile network][User][Password] 

GPRS

 

wlapn.es honeywell honeywell

  

 

>OK: Operation completed   

 

 

SMS Message sending to user Mobil

 

UCIP GPRS can send SMS messages to a SMS compatible 
Alarm Receiver or up to 2 user mobile telephones. 

 
SMS

[SMS Receiver phone][MOBILE1][MOBILE2] 

 
ej. SMS sending to user mobile phone 

699887766 

 

>SMS

 

NONE 699887766 NONE

 

>OK: Operation completed   

 

 

Panel Port settings

ID3000

: Level 3 :6)Config. 

 6) Panel Settings 

17) Isolated RS232 

Port setup: Integration protocol, 9600 baud, 11A. Half Duplex. 
Requires 24Vdc.   

ID60

: 5)Config.

1)Config.

 4)Peripherals

 2)RS232: Integration. Half 

Duplex. 
Requires 24Vdc.   

DXc:  

5)Actions

7)Commission

1)General Options

2ndSerial Port: 

TTP,9600.  
Requires 24Vdc.   
 

VSN  / NFS / RP1r (TTL*)

:  

*Requires to change Jp3 and Jp4

 in UCIP. 

 

Power 

(+)

 by 

AUX

 port

 (VSN / NFS / RP1r)

 

110
mm 

135
mm 

79m

97m

RS485 Port

 

GND

 

A

+

  

 

RS 232

:  

ID / DXc … 

TTL*

 Vision/NFS 

RS232* 
Port. 

 

%

 G

P

RS

 

GP

RS

 

S

yst

 

RX

 

TX

 

F

.CRA

 

F

.link 

  

 

 

Ou

1

 

Ou

2

 

 External Power 
 24Vdc  
 

       -  + 

GPRS antena

 

GND  

T

X

  

 

R

X

 

23 -

 

SIM 

1)

Select Port type: TCP/IP Client 

 

2)

Type the UCIP IP and Port 23 

 

3)

Clic on connection 

 

>

Type here your 

command

 

1234 

 

4) 

TYPE CONFIG COMMANDS, as described in steeps 6 

to 9, including your data (red color in the examples), 
separate and press ENTER to send it.

 

Central Receiver Alarm Center CRA IP

 

UCIP GPRS permits up to 2 IP address to send system states 
to an IP compatible Receiver CRA1 and CRA2 

 
CRA1 

[CLIENT#][IP CRA][IP PORT][Alive T] 

[Password][Channel: ETH+GPRS;ETH;GPRS] 
 
i.e. Client # 

AAAAAA

, Receiver IP 

192.168.1.100

 and port 

10001

, Alive test time 

60

seg, encrypted password 

111111

 and 

send only by GPRS channel: 

>CRA1

  

AAAAAA 192.168.1.100 10001 60 111111 GPRS

 

>OK: Operation completed   

 

CRA2 

[CLIENT#][IP CRA][IP PORT][Alive T][Password] 

[Channel_Send:GPRS+ETH;GPRS;ETH;_FAIL;_EVER] 
 
i.e. Client # 

AAAAAA

, Receiver IP 

192.168.1.102

 and port 

10002

, Alive test time 

60

seg, encrypted password 

111111

send only by GPRS channel and send on CRA1

 fail 

>CRA1

  

AAAAAA 192.168.1.102 10002 60 111111 GPRS_FAIL

 

>OK: Operation completed   

 
 

Panel connection 

Install de communicator as indicated above closet o panel linking the panel 
communication port to the corresponding on the UCIP as described in the 
table on step 3). Connection examples: 

 1234 
 RS232 

RS 232

 (Panel) to 

1+2 UCIP

 

JP3 y JP4 UCIP 

TTL mode 

Panel VSN/RP1r/Supra 

ISO232 ID3000/DXc 

ISO232

 (Panel) to 

1 UCIP

 

JP3 y JP4 UCIP   RS232 mode 

24V external required  

0V

 

TX

 

CT

S

 

RX

 

RT

S

 

DB9 (ID60) 

UCIP GPRS 

Honeywell 

Stick the provided label in the 
enclosure cover gap oriented with 
the LEDs window upwards as in 
the figure.

 