UCIP-GPRS
HLSI-MA-192_05
Honeywell Life Safety Iberia, S.L. reserves the right to do any change in this information without notice.
For accurate and updated information go to
Read carefully the product manual before to install this material.
The SMB-T enclosure is designed to be installed on
a Surface and inside some devices by using
described holes:
1-
Surface
mounting: Install the enclosure in the wall close to the
panel by using holes marked as (1).
2-
Conventional panels NFS, VSN2 y ESS
: Open the panel box
enclosure and remove the left Touch Display or user label plate.
Install the box under the panel mains connector. Fit the box in
the panel back box by the holes marked as 2) and slightly slide it
downwards.
3- Fit the UCIP Communicator in the SMB-T en closure by the 4
screw holders marked 3).
Installation
1
2
4
SMB-T Enclosure installation
3
Connections
Standard cable holes
Settings
Cut the necessary holes in the SMB-T enclosure
1- RS-232 Port or AUX Port (Panel cable link)
2- RJ45 Ethernet port (Commissioning and Network)
3- GPRS antenna (UCIP GPRS only)
4- 24Vcc External power
Connect needed cables as below:
STATUS LEDS
Ethernet Network
RJ45
RS232 / TTL* Serial port
UCIP
Uart1
PC Conf.
DB9
DXc/ID3000
RS232 (ISO232)
ID60
RS232
VSN&NFS
TTL*
RX
3
TX
2
2
TX
2
RX
3
3
GND
5
0V
5
4
AUX.Port.*
Jp3 Jp4
RS232 Config.
The UCIP/GPRS can be configured by Ethernet port with RJ45
network cable El UCIP/GPRS or by RS232 serial port (cable not
provided),
with it’s config tool, Hyperterminal or Telnet
By default it has the following serial port and IP settings:
Default Serial P. UCIP:
Default IP address: 192.168.0.100
RS232: 9600 Baud
Mask: 255.255.255.0
No parity
Gateway:192.168.0.1
Config. Port:23
1- To configure UCIP via RS232 port, make the cable: RS232-PC Conf.DB9
2- To configure UCIP via
ETHERNET
, Configure your PC in the sane IP
range as the UCIP:
Windows
Start
Control Panel
Network center
Local area connection
change adapter settings
Properties
Prot.Int(IPv4)
Properties
Alternative IP config:
i.e.IP:192.168.0.50, Mask 255.255.255.0, Gateway
192.168.0.1
UCIP Console tool
3-Abra la consola de config. deUCIP o el Hyperterminal de Windows y
seleccione Puerto Serie y el puerto o TCP IP con la IP del UCIP puerto 23:
- Puerto Serie Com: 9600 bds,0,None,None
- Puerto TCP IP Client: 192.168.0.100, Puerto 23
Consola UCIP:
4- Para acceder a Configuración , con el cursor en la ventana de conexión
presione 3 veces la tecla "ESC" de su PC e inserte la clave "1234"
Configuration Console / Hyperterminal
ETHERNET UCIP local IP and Port ETHERNET
TCPIP
[local IP] [network Mask] [Gateway] [dhcp on/off] IP UCIP Config.:
i.e.
192.168.0.100,Mask:255.255.255.0,Gateway:192.168.0.1;DHCP:off
>TCPIP
192.168.0.100 255.255.255.0 192.168.0.1 off
>OK: Operation completed
CONFIG
[Port] [Parameter] :
Set IP port i.e..
5000
>CONFIG TCPSERVER
5000
>OK: Operation completed
Note: In TG supervisor, set in panel config. Link : TCP/IP, permits multiple link
7
Config GPRS Network (i.e.FireIMT)
PIN
[SIM PIN] : PIN of SIM card..
-Recommended to remove SIM PIN in a celular pone to
avoid lock it on error.
Ej. PIN XXXX. SIM must be placed to check the PIN
>PIN
XXXX
>OK: Operation completed
GPRS
[APN mobile network][User][Password]
GPRS
wlapn.es honeywell honeywell
>OK: Operation completed
5
6
9
SMS Message sending to user Mobil
UCIP GPRS can send SMS messages to a SMS compatible
Alarm Receiver or up to 2 user mobile telephones.
SMS
[SMS Receiver phone][MOBILE1][MOBILE2]
ej. SMS sending to user mobile phone
699887766
>SMS
NONE 699887766 NONE
>OK: Operation completed
2
1
1
Panel Port settings
:
ID3000
: Level 3 :6)Config.
6) Panel Settings
17) Isolated RS232
Port setup: Integration protocol, 9600 baud, 11A. Half Duplex.
Requires 24Vdc.
ID60
: 5)Config.
1)Config.
4)Peripherals
2)RS232: Integration. Half
Duplex.
Requires 24Vdc.
DXc:
5)Actions
7)Commission
1)General Options
2ndSerial Port:
TTP,9600.
Requires 24Vdc.
VSN / NFS / RP1r (TTL*)
:
*Requires to change Jp3 and Jp4
in UCIP.
Power
(+)
by
AUX
port
(VSN / NFS / RP1r)
1
1
1
2
110
mm
135
mm
79m
m
97m
m
1
1
2
2
3
3
3
3
RS485 Port
GND
B
-
A
+
RS 232
:
ID / DXc …
TTL*
:
Vision/NFS
RS232*
Port.
+
%
G
P
RS
GP
RS
S
yst
RX
TX
F
.CRA
F
.link
Ou
t
1
Ou
t
2
External Power
24Vdc
- +
GPRS antena
GND
T
X
R
X
+
23 -
SIM
1)
Select Port type: TCP/IP Client
2)
Type the UCIP IP and Port 23
3)
Clic on connection
>
Type here your
command
1234
4)
TYPE CONFIG COMMANDS, as described in steeps 6
to 9, including your data (red color in the examples),
separate and press ENTER to send it.
8
Central Receiver Alarm Center CRA IP
UCIP GPRS permits up to 2 IP address to send system states
to an IP compatible Receiver CRA1 and CRA2
CRA1
[CLIENT#][IP CRA][IP PORT][Alive T]
[Password][Channel: ETH+GPRS;ETH;GPRS]
i.e. Client #
AAAAAA
, Receiver IP
192.168.1.100
and port
10001
, Alive test time
60
seg, encrypted password
111111
and
send only by GPRS channel:
>CRA1
AAAAAA 192.168.1.100 10001 60 111111 GPRS
>OK: Operation completed
CRA2
[CLIENT#][IP CRA][IP PORT][Alive T][Password]
[Channel_Send:GPRS+ETH;GPRS;ETH;_FAIL;_EVER]
i.e. Client #
AAAAAA
, Receiver IP
192.168.1.102
and port
10002
, Alive test time
60
seg, encrypted password
111111
,
send only by GPRS channel and send on CRA1
fail
:
>CRA1
AAAAAA 192.168.1.102 10002 60 111111 GPRS_FAIL
>OK: Operation completed
Panel connection
Install de communicator as indicated above closet o panel linking the panel
communication port to the corresponding on the UCIP as described in the
table on step 3). Connection examples:
1234
RS232
RS 232
(Panel) to
1+2 UCIP
JP3 y JP4 UCIP
TTL mode
Panel VSN/RP1r/Supra
ISO232 ID3000/DXc
ISO232
(Panel) to
1 UCIP
JP3 y JP4 UCIP RS232 mode
24V external required
0V
TX
CT
S
RX
RT
S
DB9 (ID60)
3
4
2
1
UCIP GPRS
Honeywell
Stick the provided label in the
enclosure cover gap oriented with
the LEDs window upwards as in
the figure.