MU1H-1543GE23 R0709
8
Honeywell GmbH
GB
• Bonnet
• Valve piston with seal disc
• Spring
• Remote double temperature
sensor with capillary tube
• Immersion pocket G 1/2”
(ISO 228)
6. Options
7. Assembly
7.1 Installations Guidelines
• The valve and the sensor must be
installed carefully to avoid any
damage to the capillary tube
• The opening on the blow-out
line must be clear and easy to
monitor
• Ensure no persons are in
danger when blowing off the
valve
• A sufficiently dimensioned
discharge line must be provided
7.2 Assembly instructions
1. Install a thermal discharge
safety valve into the hot water
line according to the installation
diagram
- Flow direction is marked by
an arrow
2. Push the heat sensor into the
immersion pipe up to the stop
point and secure with a round
screw to stop it being pulled out
7.3 Commissioning
TS131-3/4A
Opening temperature 95 °C
capillary tube with protection
sheath 1300 mm, with approved
construction
TS131-3/4B
Opening temperature 95 °C
capillary tube with protection
sheath 4000 mm
TS131-3/4Z
Special Versions available on
request
k
vs
-values
∆
p = 1 bar
3 m
3
/h
with 2 intact sensor
systems
2.1 m
3
/h with one sensor system
Attention!
Installation of the thermal
discharge safety valve does
not replace the diaphragm
relief value in the cold water
supply line to the water heater.
On commissioning the heating
system, the person preparing
the system must check that the
thermal discharge safety valve
is functioning perfectly.