Advanced programming
Setup functions
Settings & Options
(factory default in
bold
)
130
Program Start Time
(appears only if ISU125=1)
15 min increments
5:00 PM
135
Program End Time
(appears only if ISU125=1)
15 min increments
9:00 AM
140
ASHRAE: # of Bedrooms
1-6 bedrooms;
2
145
ASHRAE: Home’s Sq Ft
10=1,000 Sq Ft;
up to 50=5,000 Sq Ft
150
ASHRAE: CFM Setting
3=30 CFM;
4=40 CFM, up to 20=200 CFM
155
Maximum Vent
00
; 30%–95%. (
00
setting runs to ASHRAE 100%)
160
Vent Shut-offs
0=Auto vent regardless of outdoor conditions
1=Off at 75°F dew point or 99°F air temp
2=Low speed at 65°F dew point or 85°F air temp. Off at
75°F dew point or 99°F air temp
Note:
If option 1 or 2 is selected, then ASHRAE 62.2
Standard will not be met.
165
Dehumidification Via
Fresh Air Ventilator
0=Do not use ventilation for dehum
1=Allow vent for dehum per outdoor conditions.
With dehum installed, control to setpoint. Without
dehum installed, control to the Hum se10%
(max 60%).