background image

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9

http://yourhome.honeywell.com

Automation and Control solutions

® U.S. Registered Trademark.
© 2010 Honeywell International Inc.
69-2407—01 M.S.   01-10
Printed in U.S.A

Honeywell warrants this product to be free from defects in the workmanship or materials, under normal use 
and service, for a period of five (5) years from the date of purchase by the consumer. If at any time during 
the warranty period the product is determined to be defective or malfunctions, Honeywell shall repair or 
replace it (at Honeywell’s option).
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it; or
(ii) call Honeywell Customer Care at 1-800-468-1502. Customer Care will make the determination whether 
the product should be returned to the following address: Honeywell Return Goods, Dock 4 MN10-3860, 
1885 Douglas Dr. N., Golden Valley, MN 55422, or whether a replacement product can be sent to you.
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by 
Honeywell that the defect or malfunction was caused by damage which occurred while the product was in 
the possession of a consumer.
Honeywell’s sole responsibility shall be to repair or replace the product within the terms stated above. 
HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY 
INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY 
BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some 
states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may 
not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE 
DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND 
FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE FIVE-YEAR DURATION OF THIS 
WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limi-
tation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write Honeywell Customer Relations, 1985 
Douglas Dr, Golden Valley, MN 55422 or call 1-800-468-1502. In Canada, write Retail Products ON15-02H, 
Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V4Z9.

5-Year Limited Warranty

Содержание TRUDRY DR90

Страница 1: ...Y DR90 3 8 in hex drive Drill or duct cutting tool Wire stripper cutter Standard screwdriver Duct tape 10 in round duct and starter collar 18 22 gauge 5 band thermostat wire 1 2 in diameter drain line 8 ft 1 2 in drain clamps 2 Options 1 2 in drain p trap may be required by local code Drain pan OPTIONAL CONTROLS SOLD SEPARATELY TrueDRY DR90 INCLUDED IN THIS BOX PROFESSIONAL INSTALLATION GUIDE G3 G...

Страница 2: ...ool Wire stripper cutter Standard screwdriver Duct tape 10 in round duct and starter collar 18 22 gauge 5 band thermostat wire 1 2 in diameter drain line 8 ft 1 2 in drain clamps 2 Options 1 2 in drain p trap may be required by local code Drain pan Warning Installation must be performed by a qualified service technician and must comply with local codes Remove power to the device before installing ...

Страница 3: ...tion 11 Troubleshooting 11 Refrigerant Charging 12 Compressor Capacitor Replacement 12 Parts List 13 5 Year Limited Warranty 14 The TrueDRY DR90 is designed to be installed indoors in a space that is protected from rain and flooding Install the unit with space to access the front panel for maintenance and service Avoid directing the discharge air at people or over the water in pool areas If used n...

Страница 4: ...IC RHINITIS AND ASTHMA CHEMICAL INTERACTIONS OZONE PRODUCTION ASHRAE RECOMMENDED WINTER DESIGN LEVEL 0 0 1 5 9 0 9 5 8 0 8 5 7 0 7 5 6 0 6 5 5 0 5 5 4 0 4 5 3 0 3 5 2 0 2 5 1 0 1 5 0 0 0 1 4 4 1 8 3 1 2 3 1 6 2 1 0 2 1 5 1 1 0 1 1 7 0 1 4 0 1 1 0 1 9 9 7 9 5 9 3 9 1 9 5 9 6 3 1 0 3 1 4 2 1 8 1 1 4 1 1 0 1 1 7 0 1 4 0 1 1 0 1 8 9 6 9 4 9 3 9 1 9 0 9 8 8 7 8 0 9 2 2 1 7 1 1 3 1 1 9 0 1 6 0 1 2 0 1 0...

Страница 5: ...hutdown Maintenance and service reminders Controls other indoor air quality equipment Manual Dehumidistat H8908DSPST and Automatic Ventilation Controls W8150A1000 Manual humidity control with intuitive comfort settings Integrated humidity chart for accurate control in changing outdoor conditions Automatic W8150 ventilation control to ASHRAE standard or for continuous operation Control Options The ...

Страница 6: ... nominal Input current 6 7 amps Output ratings Power transformer to R C terminals 24 VAC 0 85 A Energy Performance 2 5 liters 5 3 pints per kilowatt hour KWH Standards and approval body require ments ETL Tested per standard UL 474 ducted dehumidifier ENERGY STAR rated Dry Bulb Temp Intake Humidity Capacity Pints Day 80 F 60 RH 90 70 F 60 RH 77 60 F 60 RH 47 Home Size square ft Dehumidifier Capacit...

Страница 7: ...onal fresh air ventilator port use 6 in round insulated duct for lengths up to 50 ft Use 8 in round duct for more than 50 ft of if more than 100 CFM is required Isolated Areas Effective dehumidification may require ducting to isolated or stagnant air flow areas SUPPLY RETURN AIR HANDLER TrueDRY M27325 A Main Return to Main Return Ideal when Running TrueDRY DR90 with A C operation Minimizing discha...

Страница 8: ... specific conditioned or unconditioned area such as attic basement or crawl space Running with A C operation Minimizing DAT is preferred Connect 1 2 in drain tube to male connection drain outlet Secure drain tube to connector with hose clamp Run drain hose continuously downhill to an approved drain or condensate pump Plumbing Install to Fit Your Application continued TrueDry DR90 Dehumidification ...

Страница 9: ...ly for ventilation C DR90 24V output External 24V devices can be powered from R and C terminals 20VA max Wiring Wire the TrueDRY DR90 according to the diagram that applies to your desired opera tion TrueDry DR90 Dehumidification System 69 2407 01 7 TrueDRY HVAC THERMOSTAT G Y W R C M29839 DHUM R FAN C C Rc R H H DH DH W W2 Y Y2 G K NOTE THERMOSTAT MUST BE CONFIGURED TO DRIVE FURNACE FAN DURING DEH...

Страница 10: ...ANICAL DEHUMIDISTAT THERMOSTAT G Y W R Rc G Y W R C M29840 DRY CONTACTS FAN C DPDT RELAY 2 6A DHUM R Follow this diagram for ducted operation with external humidity and ventilation control TrueDRY HVAC MECHANICAL DEHUMIDISTAT THERMOSTAT G Y W R Rc G Y W R C M29841 DRY CONTACTS DHUM R FAN C DPDT RELAY 2 6A EARD 6 AT120 R C DAMPER AUX REMOTE W8150A G R C C W G ...

Страница 11: ...ATION CALL DHUM R FAN C C 6840 55 1215 76 In Out PM R C W Y G R C SENSOR SENSOR SWITCH W G VENT VENT DEHUM DEHUM HUM HUM OUTDOOR SENSOR PROVIDED EARD 6 TrueIAQ 1 1 2 2 TrueDRY TrueDry DR90 Dehumidification System 69 2407 01 9 Follow this diagram if using TrueDRY DR90 with a VisionPRO IAQ M29843 FAN FURNACE BOARD EQUIPMENT INTERFACE MODULE EIM G C CONV HP 1 2 3 C R RC RH W1 W2 W3 Y Y2 G O B AUX AUX...

Страница 12: ...y 1 2 3 4 Unplug TrueDRY DR90 before beginning service Remove the magnetic filter door Remove filter 50049537 005 and replace with new filter Remove the panels on each side of the TrueDRY DR90 Using a damp cloth wipe excess dust and debris from blower refrigerant coils and compres sor coils Reattach cabinet panels when finished 5 When service is complete initiate a call for dehumidification and ch...

Страница 13: ...h or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open No dehumidification Compressor does not run but fan runs when there is a call for dehumidification and the ventilation control is OFF 1 Defective compressor run capacitor 2 Bad connection in compressor circuit 3 Defective compres...

Страница 14: ...d control wiring connections from main unit 2 Connect the R and FAN contacts from the main unit together only the impeller fan should run Disconnect the wires 3 Connect the R and DHUM contacts from the main unit together the compressor and impeller fan should run 4 If these tests work the main unit is working properly You should check the control panel and field control wiring for problems next 5 ...

Страница 15: ...stat H8908DSPST 7 Automatic ventilation control W8150A1001 8 Motorized ventilation damper EARD 6 Compressor run capacitor 50049536 001 Blower assembly 50027976 001 9 Filter 50049536 003 10 6 in Duct collar 50049536 004 11 10 in Duct collar 50049536 005 12 Magnetic door 50049536 006 Compressor relay SPST 24 Vac 30A 50035445 014 Fan relay SPDT 24 Vac 15A 50035445 011 Transformer 120 24 Vac 40 VA 500...

Страница 16: ...wn by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BR...

Отзывы: