68-0047—2

2

VR8204; VR4204

SPECIFICATIONS • ORDERING INFORMATION

Ordering Information

When purchasing replacement and modernization products from your TRADELINE

®

 wholesaler or your distributor, refer to the price

sheets for complete ordering number, or specify:

1. Order number, TRADELINE, if desired.
2. Natural or LP gas.
3. Step pressure on VR4204C,P and VR8204C,P.
4. Accessories, if desired.
5. Order separately: pilot burner, igniter-sensor, transformer, limit controller, and thermostat or controller as required.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Division Customer Satisfaction

Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitee, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales
and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,
Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Specifications

IMPORTANT: The specifications given in this publica-

tion do not include normal manufacturing toler-
ances. Therefore, this unit may not exactly match the
listed specifications. Also this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be ex-
pected if those conditions are changed
.

TRADELINE

®

 MODELS

TRADELINE controls are selected and packaged to

provide ease of stocking, ease of handling and maximum
replacement value. TRADELINE model specifications are
the same as those of standard models except as noted
below.
TRADELINE MODEL AVAILABLE: VR8204A Dual

Automatic Combination Gas Control for Intermittent
Pilot Systems. Models for natural or LP gas.

TABLE 1—MODEL SPECIFICATIONS.

Model No.

Opening

Charac-

Type  

Standard Factory

Regulator Settings

Optional Factory

Regulator Settings

Range of Field

Adjustment

Suffix Letter

teristic

of Gas

in. wc

kPa

in. wc

kPa

in. wc

kPa

VR8204A,M

Standard

Natural

3.5

0.9

3 to 5

0.7 to 1.2

3 to 5

0.7 to 1.2

VR4204M

LP

10.0

2.5

8 to 12

2 to 3

8 to 12

2 to 3

VR8204C,P
VR4204P

Step-
opening

Natural

Step—0.7, 0.9,

1.2 or 1.7,

as ordered

a

Full Rate—3.5

Step—0.17 0.22,

0.30 or 0.48

as ordered

a

Full Rate—0.9

Step—0.7,
0 9, 1.2 or

1 7 as ordered

a

Full Rate—3 to 5

Step—0.17 0.22,

0.30 or 0.48,

as ordered

a

Full Rate—

0.7 to 1.2

Step—

none;

Full

Rate—

3-5

Step—

none;

Full

Rate—

0.7 to 1.2

  

LP

Step—1.4, 2.5,

4.0 or 5.5,

as ordered

a

Full Rate—10

Step—0.35, 0.62,

0.99 or 1.37

as ordered

a

Full Rate—2.5

Step—1.4, 2.5,

4.0 or 5.5,

as ordered

a

Full Rate—

8 to 12

Step—0.35, 0.62,

0.99 or 1.37,

as ordered

a

Full Rate—2 to 3

Step—

none;

Full

Rate—

8-12

Step—

none;

Full

Rate—

2 to 3

VR8204H,K

Slow-

Natural

3.5

0.9

3 to 5

0.7 to 1.2

3 to 5

0.7 to 1 2

VR4204H

opening

LP

10.0

2.5

8 to 12

2 to 3

8 to 12

2 to 3

a

Step pressure is not adjustable.

ADDITIONAL FEATURES:

• 3/8 in. bushing.
• 3/4 in. straight flange assembly (with O-ring and

screws).

• Tool for flange hex screws.
• Pilot compression fitting.

STANDARD MODELS
MODELS: VR8204 and VR4204 Dual Automatic Valve

Combination Gas Controls for use in Intermittent Pilot
Systems. VR8204 for use with S8600, S8610 and S8620
Modules. VR4204 for use with 120 Vac modules. See
Table 1 for model specifications.

SUPPLY VOLTAGE:

VR4204: 120 Vac, 60 Hz.
VR8204: 24 Vac, 60 Hz.
(50/60 Hz models available on request.)

Содержание TRADELINE VR8204A

Страница 1: ...supply is interrupted Two position gas control knob has ON and OFF posi tions All adjustments and wiring connections are accessible from top of the control Compact size Straight throughbodypattern rightangleadaptersavail able for inlet and outlet 1 2 in inlet and 1 2 in outlet adapters available for 3 8 or 3 4 in Adjustable servo regulator effectively maintains almost constant gas output pressure ...

Страница 2: ...dling and maximum replacement value TRADELINE model specifications are the same as those of standard models except as noted below TRADELINE MODEL AVAILABLE VR8204A Dual Automatic Combination Gas Control for Intermittent Pilot Systems Models for natural or LP gas TABLE 1 MODEL SPECIFICATIONS Model No Opening Charac Type Standard Factory Regulator Settings Optional Factory Regulator Settings Range o...

Страница 3: ...G Can be mounted 0 to 90 degrees in any direction including vertically from the upright position of the gas control knob TEMPERATURE RATING VR8204A C H and VR4204H 0 F to 175 F 18 C to 79 C VR8204M P K and VR4204M P 40 F to 175 F 40 C to 79 C DIMENSIONS See Fig 1 APPROVALS AmericanGasAssociationdesigncertificate L2025006 CanadianGasAssociationdesigncertificate L2025006 Australian Gas Association d...

Страница 4: ...MAGE SEVERE INJURY OR DEATH 1 Do not use a gas control set for natural gas on an LP gas system or a gas control set for LP gas on a natural gas system 2 When making conversion main pilot burner orifices must be changed to meet appliance manufacturer specifications Refer to appliance manufacturer instructions for orifice specifications and changeover procedure Gas controls are factory set for natur...

Страница 5: ...inances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must com ply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without defor mation 2 Run pipe or tubing to the control If tubing is used obtain a tube to pip...

Страница 6: ...IS USED M3079 Connect Pilot Gas Tubing 1 Cut tubing to desired length and bend as necessary for routing to pilot burner Do not make sharp bends or deform the tubing Do not bend tubing at control after compression nut has been tightened because this may result in gas leakage at the connection 2 Square off and remove burrs from end of tubing 3 Unscrew brass compression fitting from the pilot outlet ...

Страница 7: ...ig 2 5 Adjust thermostat heat anticipator as instructed in the appliance manual i e usually 0 1A for VR4204 0 5A for VR8204 Fig 8 Wiring connections for 24 volt control in intermittent ignition system with S8600 MV MV PV PV GND BURNER 24V GND 24V SPARK S8600 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM WIRE LENGTH 3 ft 9 m CO...

Страница 8: ... main burner in operation paint pipe joints including adapters and control inlet with rich soap and water solution 5 If another leak is detected tighten adapter screws joints and pipe connections 6 Replace part if leak cannot be stopped ADJUST PILOT FLAME The pilot flame should envelop 3 8 to 1 2 in 10 to 13 mm of the tip of the igniter sensor See Fig 10 To adjust pilot flame 1 Remove pilot adjust...

Страница 9: ...ired outlet pressure or flow rate cannot be achieved to adjusting the gas control check gas control inlet pressure using a manometer at the gas control inlet pressure tap If inlet pressure is in the nominal range see Table 4A or 4B replace gas control Otherwise take the necessary steps to provide proper gas pressure on the control Slow opening and Step opening Pressure Regulators 1 Check the full ...

Страница 10: ...stem should be replaced if It does not perform properly on checkout or trouble shooting The gas control knob is hard to turn The gas control is likely to have operated for more than 200 000 cycles Operation The VR8204 VR4204 gas controls provide ON OFF manual control of gas flow In the OFF position gas flow to both pilot and main burners is mechanically blocked In the ON position gas flows to the ...

Страница 11: ...servo pressure regulator pro vides close control of outlet pressure even if inlet pressure and flow rate vary widely Any outlet pressure change is immediately reflected back to the pressure regulator dia phragm which repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly ...

Страница 12: ...outlet pressure as described for the standard regulator The step model requires approximately 60 seconds to reset once the main burner goes off If it is re energized within 60 seconds it may bypass or shorten the length of the low pressure step The burner may relight at the full flow rate WHEN THE CALL FOR HEAT ENDS When the call for heat ends the first automatic valve and the second automatic val...

Страница 13: ...at the gas control knob is in the ON position 2 Adjust thermostat several degrees above room tem perature 3 Using ac voltmeter check for voltage at gas control If pilot lights measure across MV PV and MV If pilot does not light measure across MV PV and PV before safety lockout occurs 4 If voltage is incorrect or not present check control circuit for proper operation 5 If voltage is present replace...

Страница 14: ...l application but the specific controls used and the procedures outlined by the manufac turer of your appliance may differ requiring special instructions TO TURN ON FURNACE STOP Read the safety information above 1 The lighting sequence on this appliance is automatic do not attempt to manually light the pilot 2 If the furnace does not come on when the thermostat is set several degrees above room te...