V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES

9

60-2133—10

IMPORTANT 

Use this valve in hydronic heating systems that do not 

contain dissolved oxygen in the system water. The 

dissolved oxygen, which is found in systems that 

have a frequent source of makeup water, causes the 

rubber plug inside the valve to deteriorate and even-

tually fail. 

MOUNTING

The valve can be mounted in any position on a vertical line. 

See Fig. 9. If the valve is mounted horizontally; the powerhead 

must be even with or above the center line of the piping. Make 

sure to leave enough room above the powerhead to remove 

the cover for servicing. 

Fig. 9. Mounting positions.

Mount the valve directly in the tube or pipe. Make sure that the 

flow through the valve is in the direction indicated by the arrow 

stamped on the valve body. 

On diverting valves, the three fittings or ports are labeled on 

the bottom of the valve body casting. See Fig. 1. Port AB is the 

inlet port and is open at all times. Port A is closed when the 

valve is de-energized; port B is open when the valve is de-

energized. Refer to the equipment manufacturer instructions to 

determine which port (A or B) should be connected to the coil 

bypass. 

FLARE FITTING MODELS

Use new, properly reamed pipe, free from chips. The valve 

body is threaded for standard 5/8 in. OD copper, 45 degree 

SAE flare fitting nuts. These nuts are not furnished with the 

valve and must be obtained separately. 

SWEAT COPPER MODELS

1.

Use new, properly reamed pipe, free from dents or corro-

sion. 

2.

Place the valve on the pipe. Set the manual opening 

lever to MAN. OPEN position before applying heat. This 

protects the plug inside the valve by removing it from the 

seat. 

3.

IMPORTANT- Take care not to burn the plastic portion of 

the composite adapter plate when soldering.

4.

Sweat the joints, keeping the outer surface free from sol-

der. DO NOT use silver solder because of the high melt-

ing temperature required. 

To Install Replacement Powerhead

SYSTEMS WITH OLD STYLE VALVE BODIES (SERIES 1-5)

To install a replacement powerhead in a system with an old 

style body (series 1-5), the valve body must be converted to 

accept the new powerhead using part no. 40003918 

Conversion Kit. The kit includes a metal plate with a driveshaft 

and rubber plug, O-ring, and four screws. 

IMPORTANT 

Converting the valve body for use with the new pow-

erhead does not require removal of the valve body 

from the pipeline. However, it is necessary to drain 

the water from the system before beginning the con-

version. 

1.

Disconnect the power supply before connecting the wir-

ing to prevent electrical shock or equipment damage. 

2.

Disconnect the leadwires to the powerhead at the termi-

nal block or conduit connection. Remove the conduit or 

cable connector if fitted. Label each wire for rewiring 

later. 

3.

Drain the water from the system. 

4.

Remove the old powerhead from the valve body (Fig. 10)

a. Place the manual opening lever (normally closed 

models only) on the old powerhead in the MAN. 

OPEN position (see Fig. 10A). 

b. Remove the cover (Fig. 10B). 

c. With the cover off, remove the four screws securing 

the powerhead to the valve body. 

d. Lift the powerhead off the valve body (Fig. 10C). 

e. Remove the O-ring from the top of the valve body. 

5.

Install 40003918 Conversion Kit (Fig. 11)

a. Insert the new O-ring in the valve body. 

b. Place metal plate with the rubber plug on top of the 

valve body. Make sure the guide pins on the under-

side of the metal plate fit into the recesses on the 

valve body. 

c. Secure the metal plate to the valve body with the four 

screws (two sets) provided. One set of screws has 

heads with recessed threads to insert screws for 

mounting the new powerhead; insert this set into the 

larger screw openings. The other set has domed 

heads; insert this set into the smaller screw open-

ings. Each set of screws must be inserted in opposite 

corners of the metal plate so the screws sit flat on the 

plate. Make sure the guide pins on the plate fit into 

the recesses on the valve body. 

6.

Install new powerhead (see Fig. 12)

a. Place the manual opening lever (normally closed 

models only) on the new powerhead in the MAN. 

OPEN position. 

b. Fit the powerhead onto the valve body, ensuring that 

the shaft seats correctly. The powerhead should be 

aligned with the manual opening lever or slot for 

lever at the port A end of the valve body. 

c. Secure the powerhead to the valve body with the two 

screws provided. 

d. If fitted, reconnect the conduit or cable. Reconnect 

the leadwires at the powerhead. 

e. Replace the powerhead cover. 

7.

Turn on power.

M10162A

VERTICAL

PIPING

HORIZONTAL

PIPING

Содержание TRADELINE : V8043A

Страница 1: ...er failure Valve returns to automatic position when power is restored Choice of sweat or flare fitting brass end connections for standard copper tubing Motor can be replaced by removing one screw without disturbing the valve body or draining the system Complete powerhead may be removed or replaced without breaking the line connections or draining the system All models can be installed without disa...

Страница 2: ... of standard models except as noted below TRADELINE Models Available V8043A E and V8043E F see Table 1 Capacity Rating nominal See Table 1 Straight through models 1 0 Cv 86 kv 3 5 Cv 3 0 kv Standard 8 0 Cv 6 9 kv Diverting models 4 0 Cv 3 5 kv Standard 7 0 Cv 6 0 kv Additional Feature End switch enclosure included Standard Models Models V4043 line voltage straight through valves V4044 line voltage...

Страница 3: ...TIONS OPENING FOR 1 2 IN CONDUIT ON MANUAL LEVER SIDE FOR V4043 V8043 OPENING ON OPPOSITE SIDE FOR V4044 V8044 1 1 6 7 8 1 6 5 2 3 4 8 1 4 3 2 7 2 3 4 7 8 7 7 1 2 3 4 5 6 7 8 M10175 V4043 V8043 SWEAT COPPER CONNECTION MODELS V4044 V8044 SWEAT COPPER CONNECTION MODELS V4044 V8044 FLARE FITTING MODELS V4043 V8043 FLARE FITTING MODELS V8043 INVERTED FLARE MODELS 2 3 8 60 7 8 DIA 22 7 8 DIA 22 1 1 2 3...

Страница 4: ...r 60 Sweat or Flare 1 2 4 0 3 4 277 60 Sweat 1 2 4 0 3 4 120 60 Sweat 3 4 7 0 6 0 240 60 Sweat 3 4 4 0 3 4 V4044Bb bottom inlet 120 60 18 in 457 mm Leadwires 1 2 in conduit opening Sweat or Flare 1 2 3 5 3 0 2 Position Diverting Port A Normally Closed 220 50 Sweat or Flare 1 2 3 5 3 0 120 60 Sweat 3 4 7 0 6 0 V8043A 24 50 60 18 in 457 mm Leadwires 1 2 in conduit opening Sweat or Flare 1 2 1 0 or 3...

Страница 5: ...s Valve Family Flow Capacity Rating Max Closeoff Pressurea Max Fluid Temperature Min Fluid Temperature Max Ambient Temperature Cv kv psi kPa V4043A B E J 1 0 86 50 345 200 F 93 C 40 F 5 C 125 F 50 C 3 5 3 0 20 138 10 0 8 6 6 5 45 V8043A B E F 3 5 3 0 20 138 8 0 7 0 8 55 1 0 8 6 6 5 45 V4044A B 4 0 3 4 20 138 7 0 6 0 10 69 V8044A B E 4 0 3 4 20 138 7 0 6 0 10 69 V4043E V8043J steam 15a 103 240 F 11...

Страница 6: ...ve when the fluid temperature is known reverse this procedure Fig 2 Maximum temperature characteristics of valves with Class F motors V8044A 40003916 032 Opposite 24 50 60 0 32 18 in 457 mm leads conduit opening Class A plated 40003916 046 Same 24 50 60 0 32 V8044B 40003916 037 Opposite 24 50 60 0 32 18 in 457 mm leads conduit opening 40003916 044 Same 24 50 60 0 32 Table 2 Replacement Powerheads ...

Страница 7: ...ig 3 Flow characteristics of 1 Cv 0 86 kv flow Fig 4 Flow characteristics of V4043A model with 2 5 Cv 2 1 kv rating and V4044A and V8044A bypass port B with 2 5 Cv 2 1 kv reduced rating Fig 5 Flow Characteristics of 3 5 Cv 3 0 kv valve PRESSURE DROP EQUIVALENT FEET OF PIPE EQUIVALENT METERS OF PIPE 500 152 140 43 120 37 100 30 90 27 600 183 700 213 750 229 50 149 40 119 30 89 5 20 60 3 4 IN PIPE 1...

Страница 8: ... 0 2 1 8 0 2 4 9 0 2 7 10 3 30 9 1 40 12 2 45 13 7 50 15 2 55 16 8 60 18 50 149 40 119 30 89 5 20 60 3 4 IN PIPE 1 2 IN PIPE 50 0 345 10 0 69 5 0 34 1 0 7 0 50 3 4 0 10 0 69 0 05 0 34 0 2 0 13 4 0 25 6 0 38 8 0 5 10 0 63 12 0 76 14 0 88 16 1 0 18 1 1 20 1 3 22 1 4 24 1 5 26 1 6 28 1 8 30 1 9 0 05 0 15 0 1 0 3 0 5 1 5 1 3 5 15 10 30 M5717B FLOW RATE GAL MIN l s PRESSURE DROP FT OF WATER psi kPa PRE...

Страница 9: ... Conversion Kit The kit includes a metal plate with a driveshaft and rubber plug O ring and four screws IMPORTANT Converting the valve body for use with the new pow erhead does not require removal of the valve body from the pipeline However it is necessary to drain the water from the system before beginning the con version 1 Disconnect the power supply before connecting the wir ing to prevent elec...

Страница 10: ...2133 10 10 Fig 10 Remove old powerhead from systems using old style valve bodies A AUTO MAN OPEN MANUAL OPENING LEVER COVER RETAINING SCREW M10174 A B V8043F 1051 24V 50 60 CY 32 AMP 60 CY MADE IN CANADA 6 A B V8043F 1051 24V 50 60 CY 32 AMP 60 CY MADE IN CANADA 6 A B C ...

Страница 11: ...ig 13B c Lift off the cover from the powerhead d Remove the two screws securing the powerhead to the valve body Fig 12 e Lift the powerhead off the valve body 4 Install the new power head see Fig 12 a Place the manual opening lever normally closed models only on the new powerhead in the MAN OPEN position b Fit the powerhead onto the valve body ensuring that the shaft seats correctly The powerhead ...

Страница 12: ... are shown in Fig 14 and 15 See Fig 16 through 22 for typical hookups If replacing a Taco Dole Flair or White Rodgers 3 wire valve with a 2 wire V8043E or F see Fig 23 through 35 Check that the pressure rating of the new valve is appropriate for the application Fig 14 Typical wiring for V8043E V8044E A AUTO MAN OPEN MANUAL OPENING LEVER COVER RETAINING SCREW M10161 A B B V8043F 1036 24V 50 60 CY 3...

Страница 13: ...IDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT T822 T822 T822 V8043A V8043A V8043A M10168 L1 HOT L2 1 1 2 2 3 2 2 3 3 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT CONNECT V8043E RED LEADWIRES TO L1 HOT LINE AND PRIMARY CONTROL T822 T822 T822 V8043E V8043E V8043E M10169 ...

Страница 14: ... more zone valves L1 HOT L2 1 1 2 2 3 2 2 3 3 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT CONNECT V8043E RED LEADWIRES TO AQUASTAT T822 T822 T822 V8043E V8043E V8043E M10170 CIRCULATOR T T 1 2 C1 TO BURNER CONTROL CIRCUIT B1 B2 C2 L1 HOT L2 ZONE 1 T87F ZONE 2 ZONE 3 V8043F END SWITCH TH TR TH TR L8124G 120 V POWER SUPPLY ...

Страница 15: ...TOR CONTROL CIRCUIT W775A PANEL B R B W BR B R B W BR B R B W BR B R B W BR T87F L1 HOT L2 POWER SUPPLY B R B W BR RED RED YELLOW ZONE V8043E YELLOW W775A PANEL RED YELLOW RED YELLOW T87F T87F CONNECTIONS FOR V8043E LEADWIRE MODEL ZONE 1 T87F ZONE 2 ZONE 3 ZONE 4 ZONE 5 V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043F END SWITCH TH TR TH TR V8043E V8043E T87F T87F T87F T87F M1016...

Страница 16: ... HOT L2 1 A B C D E 1 2 3 THERMOSTAT TACO VALVE TO AUXILIARY CIRCUITS 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M5958 L1 HOT L2 1 C A B D THERMOSTAT V8043E TO AUXILIARY CIRCUITS 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M10163 YELLOW YELLOW RED RED E A B C D THERMOSTAT END SWITCH V8043F TH TR TH TR L1 HOT L2 1 E M5960 A B C D THER...

Страница 17: ...NNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M5965 YELLOW YELLOW RED RED F A B C F THERMOSTAT END SWITCH V8043F TH TR TH TR L1 HOT L2 1 E M5966 A B C F THERMOSTAT END SWITCH V8043F TH TR TH TR L1 HOT L2 1 E TO TERMINALS T T ON BURNER RELAY TO TERMINALS T T ON BURNER RELAY D D POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 M5978 A B C D THERMOSTAT FLAIR VALVE L1 HOT ...

Страница 18: ...EQUIRED IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM TAPE UNUSED END AND TUCK INTO HOLE 1 2 3 5 4 6 M5712 1 2 3 1 L1 HOT L2 TO AUXILIARY CIRCUITS V8043F END SWITCH TH TR TH TR 5 4 6 1 2 3 THERMOSTAT L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT WIRE AUXILI...

Страница 19: ...ly opened NORMALLY OPEN MODELS When the powerhead is de energized a spring return mechanism drives the valve to the open position Fig 36A When energized the valve is closed as shown in Fig 36B A reverse acting thermostat is required to control a normally open valve NOTE Inlet Port is stamped A Outlet Port is stamped B on the valve body Fig 36 V8043 operation for normally closed valve Checkout 1 Ra...

Страница 20: ... MOTORIZED VALVES Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 60 2133 10 T D Rev 09 10 Printed in U S A ...

Отзывы: