Honeywell TRADELINE T8090A Скачать руководство пользователя страница 7

7

69-0750—1

THERMOSTAT

This thermostat was calibrated at the factory and should

not need recalibration in the field. If recalibration seems
necessary, first be sure wallplate or subbase is accurately
leveled. Then check thermometer calibration.

To check thermostat calibration, allow several hours of

operation after installation. Then read the thermometer and
remove the cover. Push the temperature levers together to a
setting the below room temperature. Slowly move them up
the scale together until the mercury slides across the tube.
IF THE THERMOMETER READING AND THE HIGH
TEMPERATURE LEVER POSITION ARE APPROXI-
MATELY THE SAME AT THE INSTANT THE MER-
CURY MOVES TO THE OTHER END, NO
RECALIBRATION IS NEEDED.

If calibration is necessary, proceed as follows:
1. Remove the cover.
2. Place open-end calibration wrench, part no. 104994A

(ordered separately), on the hex nut under the bimetallic coil
controlled by the red lever. See Fig. 14. Hold lever so it does
not move, and gently turn the wrench clockwise           until
the mercury rests securely in the right end of the tube.

3. Put the thermostat cover on and wait ten minutes.
4. Read the thermometer. Then remove the cover. Mov-

ing both levers, place the HIGH lever at the thermometer
reading. Hold lever so it does not move, and gently turn the
wrench counterclockwise           until the mercury just slides
to the left end of the tube but no farther. Try to do this quickly
so the heat from your hands does not affect the thermostat.

5. Repeat this procedure for the blue lever.

If thermostat fails any test, refer to the Troubleshooting

Guide in the Owner’s Manual.

Reset both temperature setting levers to the desired

temperatures.

HEATING/COOLING SYSTEM

Turn on power to the furnace and cooling system.
Place the system switch lever to HEAT and fan switch

lever to AUTO.

Push both temperature setting levers together at least

5

°

  F [3

°

  C] above room temperature. The main burner

should come on. The fan will start when the furnace heats
up. (If central electric heat, fan coil or heat pump system,
fan starts immediately.)

5. If the readings are different, insert a small screwdriver

in the thermometer and turn it until the thermometers have
the same reading. See Fig. 13.

6. Replace the thermostat cover and put the system into

operation.

NOTE: Radiant heat from your hands will offset the ther-

mometer reading. After making each adjustment, wait
five or ten minutes for the thermometer to stabilize before
comparing.

Fig. 13—Thermometer calibration.

Move both levers 5

°

 F [3

°

 C] below room temperature.

The burner should shut off.

Place the system switch lever to COOL and the fan

switch lever to AUTO. The cooling equipment will oper-
ate, and the fan will start. Allow for any time delay that may
be built into the compressor control circuit.

NOTE: To avoid compressor damage, do not operate the

system when outdoor temperature is below 50

°

 F [10

°

 C].

Refer to manufacturer recommendations.

Move together both temperature setting levers at least

5

°

 F [3

°

 C] above room temperature. The cooling equip-

ment should shut off.

Place the fan switch to ON. The fan should run continu-

ously with the system switch in any position.

Place the system switch to OFF. Move both temperature

setting levers to various positions. The heating and cooling
systems should not operate.

Operate the entire system for at least one complete cycle

with the system switch at COOL and one complete cycle
with the switch at HEAT.

If thermostat fails any test, refer to the Troubleshooting

Guide in the Owner’s Manual.

Reset both temperature setting levers to the desired

temperatures.

Leave Owner’s Manual and assistance information in a

convenient place for the building occupant or provide with
other appliance manuals.

Calibration

THERMOMETER

The thermometer in your thermostat was accurately

calibrated at the factory. The thermometer should need
adjustment only if it has been dropped or shifted due to
mishandling. If the setpoint lever and the thermometer
reading do not agree:

1. Remove the thermostat cover by pulling up from the

bottom of cover until it clears the mounting slots.

2. Set the thermostat cover on a table near an accurate

thermometer.

3. Allow five minutes for cover thermometer to sense

area temperature; compare the readings. Be careful not to
touch thermometer or breathe on it.

4. If the readings are the same, replace the cover and put

the system into operation.

M5128

INCREASE 

Содержание TRADELINE T8090A

Страница 1: ...ontrol transformer common is accessible for connection to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature or limit operation b Heat Pump Compatible Assure correct subbase identity is selected for fan control and changeover control O terminal for cool and B terminal for heat c Hot Water Zone Honeywell 2 wire valves are compatible b Some non H...

Страница 2: ... heating cooling or heating cooling equipment to the new thermostat location The number of wires required to connect this thermostat to the heating cooling or heating cooling equipment de pends on how the thermostat is powered by the 24 Vac or battery or through the control system Refer to the Typical Wiring Diagrams section to determine the number of wires required for your application UNPACK THE...

Страница 3: ...CREW HOLES WITH PLASTIC ANCHORS HEATING ONLY WALLPLATE M857 AUTO OFF COOL HEAT ON FAN B O W Y R G M1555 SPIRIT LEVEL PLUMB LINE PLUMB BOB OR WEIGHT M1553A EXISTING HORIZONTAL OUTLET BOX HEATING COOLING SUBBASE AUTO OFF COOL HEAT ON FAN R G O W Y B M1554A B O W Y R G VERTICAL OUTLET BOX ADAPTER RING 1 2 NOT INCLUDED WITH UNIT ACCESSORY PARTS AVAILABLE SUBBASE OR WALLPLATE 1 2 2 COVER PLATE MOUNTING...

Страница 4: ...structionspackedwiththewallplate or subbase Fig 5 Methods of connecting terminals MOUNT THE THERMOSTAT Note the tabs on the top inside edge of the thermostat base These tabs fit the slots molded into the top of the wallplate or subbase Hang thermostat base on wallplate or subbase Insert the two captive mounting screws located in the bottom corners of the base See Fig 6 Firmly tighten the screws Fi...

Страница 5: ...ctly set the time indicator arrow Fig 8 must point to the correct time and the corresponding daytime light or nighttime dark portion of the program dial Fig 8 Set clock SET HEAT ANTICIPATOR If T8090 is used on a steam system skip to Attach Thermostat Cover section When used on any other heating system cutthetwoblackheatanticipatorjumperwires See Fig 9 Follow the remaining section steps Fig 10 Curr...

Страница 6: ...inuously AUTO Fan operates with the cooling equipment as controlledbythethermostatorwiththeheatingequip ment as controlled by the plenum switch In electric heat heat pump and fan coil systems the fan is controlled by the thermostat for heating and cooling To switch positions use thumb or index finger to slide lever to the desired position Switch lever must stop in detent over the desired function ...

Страница 7: ...small screwdriver in the thermometer and turn it until the thermometers have the same reading See Fig 13 6 Replace the thermostat cover and put the system into operation NOTE Radiant heat from your hands will offset the ther mometer reading After making each adjustment wait fiveortenminutesforthethermometertostabilizebefore comparing Fig 13 Thermometer calibration Move both levers 5 F 3 C below ro...

Страница 8: ... IF INTERRUPTED M1512B BATTERY Fig 17 Typical hookup for clock powered by system transformer Clock powered by battery when system is not powered e g power to system is off or interrupted L1 HOT L2 1 C C R W HEAT RELAY CLOCK THERMOSTAT SUBBASE 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M1513A BATTERY Fig 18 Typical hookup for clock powered through control system C...

Страница 9: ...control system Clock powered by battery when heating or cooling equipment is on clock takes power from system when cooling equipment is off Fig 20 Internal schematic and typical hookup for T8090A Thermostat 191108AJ Wallplate in heating only system H FALL C L1 HOT L2 1 2 2 1 2 H FALL C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR STEAM SYSTEM KEEP JUMPER IN PLACE F...

Страница 10: ...69 0750 1 10 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: