Honeywell TRADELINE T8090A Скачать руководство пользователя страница 6

69-0750—1

6

Remove the thermostat from the wallplate or subbase.

Connect an ac ammeter of appropriate range (about 0A to
2A) between the R and W terminals on the wallplate or
subbase except for electric heat and heat pump systems.

Let the system operate for one minute.
Adjust the heat anticipator lever to match the number

that reads on the ammeter.

ATTACH THERMOSTAT COVER

Make sure the packing inserts in the thermostat base are

removed.

Place the two tabs on the upper edge of the cover into the

mounting slots in the thermostat base. See Fig. 11.

Swing the cover downward until it catches at the bottom

of the base.

Fig. 11—Attach cover.

SET TEMPERATURE CONTROL LEVERS

The two levers on top of the thermostat control the low

and high temperatures for energy savings and comfort
control. See Fig. 12. The lever on the left (blue mark)
controls the lower temperature. The lever on the right (red
mark) controls the higher temperature.

We recommend pushing the levers together at an appro-

priate temperature for either heat or cool until the occupant
programs the thermostat and makes the final temperature
selections.

Fig. 12—Temperature control levers.

SET SUBBASE SWITCHES (IF APPLICABLE)

The subbase system switch controls system operation as

follows:

HEAT: Heating system is controlled by the thermostat.

Cooling system is off.

COOL: Cooling system is controlled by the thermostat.

Heating system is off.

OFF:  Both the heating and cooling systems are off. If the

fan switch is in the AUTO position, the fan is also off.

The subbase fan switch controls fan operation as follows:
ON:  Fan operates continuously.
AUTO: Fan operates with the cooling equipment as

controlled by the thermostat or with the heating equip-
ment as controlled by the plenum switch. In electric
heat, heat pump and fan coil systems, the fan is
controlled by the thermostat for heating and cooling.

To switch positions, use thumb or index finger to slide

lever to the desired position. Switch lever must stop in
detent over the desired function indicator mark for proper
circuit operation.

Checkout

CAUTION

Do not check operation by shorting across termi-
nals of system controls. This will damage the heat
anticipator.

HEATING-ONLY SYSTEM

Turn on power to the furnace.
Push together both temperature setting levers at least 5

°

 F

[3

°

  C] above room temperature. The main burner should

come on. The fan will start when the furnace heats up.

Move both levers 5

°

 F [3

°

 C] below room temperature.

The burner should shut off.

Operate the entire heating system at least one complete

cycle.

If thermostat fails any test, refer to the Troubleshooting

Guide in the Owner’s Manual.

Reset both temperature setting levers to the desired tem-

peratures.

COOLING-ONLY SYSTEM

Turn on power to the cooling equipment.
Push both temperature setting levers together at least

5

°

 F [3

°

 C] below room temperature. The cooling equip-

ment should operate, and the fan should start. Allow for any
time delay that may be built into the compressor control
circuit.

NOTE: To avoid compressor damage, do not operate the

system when outdoor temperature is below 50

°

 F [10

°

 C].

Refer to manufacturer recommendations.

Move both levers 5

°

 F [3

°

 C] above room temperature.

The cooling equipment and the fan should shut off.

Operate the entire cooling system at least one complete

cycle.

12

6

3

9

50 60

70 80

M1519

50

60

70

80

HIGH TEMPERATURE
(RED MARK)
SET LEVER

LOW TEMPERATURE
(BLUE MARK)
SET LEVER

M859

Содержание TRADELINE T8090A

Страница 1: ...ontrol transformer common is accessible for connection to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature or limit operation b Heat Pump Compatible Assure correct subbase identity is selected for fan control and changeover control O terminal for cool and B terminal for heat c Hot Water Zone Honeywell 2 wire valves are compatible b Some non H...

Страница 2: ... heating cooling or heating cooling equipment to the new thermostat location The number of wires required to connect this thermostat to the heating cooling or heating cooling equipment de pends on how the thermostat is powered by the 24 Vac or battery or through the control system Refer to the Typical Wiring Diagrams section to determine the number of wires required for your application UNPACK THE...

Страница 3: ...CREW HOLES WITH PLASTIC ANCHORS HEATING ONLY WALLPLATE M857 AUTO OFF COOL HEAT ON FAN B O W Y R G M1555 SPIRIT LEVEL PLUMB LINE PLUMB BOB OR WEIGHT M1553A EXISTING HORIZONTAL OUTLET BOX HEATING COOLING SUBBASE AUTO OFF COOL HEAT ON FAN R G O W Y B M1554A B O W Y R G VERTICAL OUTLET BOX ADAPTER RING 1 2 NOT INCLUDED WITH UNIT ACCESSORY PARTS AVAILABLE SUBBASE OR WALLPLATE 1 2 2 COVER PLATE MOUNTING...

Страница 4: ...structionspackedwiththewallplate or subbase Fig 5 Methods of connecting terminals MOUNT THE THERMOSTAT Note the tabs on the top inside edge of the thermostat base These tabs fit the slots molded into the top of the wallplate or subbase Hang thermostat base on wallplate or subbase Insert the two captive mounting screws located in the bottom corners of the base See Fig 6 Firmly tighten the screws Fi...

Страница 5: ...ctly set the time indicator arrow Fig 8 must point to the correct time and the corresponding daytime light or nighttime dark portion of the program dial Fig 8 Set clock SET HEAT ANTICIPATOR If T8090 is used on a steam system skip to Attach Thermostat Cover section When used on any other heating system cutthetwoblackheatanticipatorjumperwires See Fig 9 Follow the remaining section steps Fig 10 Curr...

Страница 6: ...inuously AUTO Fan operates with the cooling equipment as controlledbythethermostatorwiththeheatingequip ment as controlled by the plenum switch In electric heat heat pump and fan coil systems the fan is controlled by the thermostat for heating and cooling To switch positions use thumb or index finger to slide lever to the desired position Switch lever must stop in detent over the desired function ...

Страница 7: ...small screwdriver in the thermometer and turn it until the thermometers have the same reading See Fig 13 6 Replace the thermostat cover and put the system into operation NOTE Radiant heat from your hands will offset the ther mometer reading After making each adjustment wait fiveortenminutesforthethermometertostabilizebefore comparing Fig 13 Thermometer calibration Move both levers 5 F 3 C below ro...

Страница 8: ... IF INTERRUPTED M1512B BATTERY Fig 17 Typical hookup for clock powered by system transformer Clock powered by battery when system is not powered e g power to system is off or interrupted L1 HOT L2 1 C C R W HEAT RELAY CLOCK THERMOSTAT SUBBASE 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M1513A BATTERY Fig 18 Typical hookup for clock powered through control system C...

Страница 9: ...control system Clock powered by battery when heating or cooling equipment is on clock takes power from system when cooling equipment is off Fig 20 Internal schematic and typical hookup for T8090A Thermostat 191108AJ Wallplate in heating only system H FALL C L1 HOT L2 1 2 2 1 2 H FALL C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR STEAM SYSTEM KEEP JUMPER IN PLACE F...

Страница 10: ...69 0750 1 10 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: