Table 2. Preprogrammed Time and 

Temperature Settings.

CHECKOUT

Heating

1.

Slide the SYSTEM switch to Heat and the FAN 
switch to Auto.

2.

Press and hold the 

 key to raise the temperature 

setting several degrees above the room tempera-

ture. After approximately ten seconds, the heating 
equipment should start. In conventional systems, 

the system turns on the fan through the use of a 
time delay relay or through a limit control. When 

using an electric heat thermostat, the fan starts 
immediately.

3.

Press the 

 key to lower the temperature setting 

below the room temperature. Heating equipment 

should stop.

Cooling

CAUTION

Low Temperature Hazard.
Operating at too low of an outdoor 
temperature may cause compressor damage.

Do not operate cooling if outdoor temperature is 
below 50°F (10°C). Refer to manufacturer’s 

recommendations. 

• Allow compressor to remain off for five minutes 

before restarting.

1.

Slide the SYSTEM switch to Cool and the FAN 
switch to Auto.

2.

Press the 

▼ 

key to lower the temperature setting 

several degrees below the room temperature. After 

approximately five minutes, the cooling equipment 
should start. The fan starts and stops with the cool-

ing equipment.

3.

Press the 

 key to raise the temperature setting 

above the room temperature. Cooling system 
should shut down.

NOTE: To bypass the 5 minute delay, see the Optional 

System Checkout section.

Fan

1.

Slide the SYSTEM switch to Off and the FAN 
switch to On. The fan should run continuously.

2.

Slide the FAN switch to Auto. In heating, the fan is 
controlled directly by the heating equipment and 

may start a few minutes after the heating equip-
ment turns on (on most systems). When using an 

electric heat thermostat, the fan starts and stops 
with the heating equipment. In cooling, the fan 

starts and stops with the cooling equipment.

Make certain all equipment responds properly to the 
thermostat.

Period

Time

Heat Setpoint Cool Setpoint

WAKE

6:00 AM

70°F (21°C)

78°F (26°C)

LEAVE

8:00 AM

62°F (17°C)

85°F (29°C)

RETURN 6:00 PM

70°F (21°C)

78°F (26°C)

SLEEP

10:00 PM

62°F (17°C)

85°F (29°C)

Содержание Tradeline T8024D

Страница 1: ...duct is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Install the thermostat about 5 ft 1 5m above the f...

Страница 2: ...e shape of the terminals permits insertion of straight or wraparound wiring connections either method is acceptable See Fig 4 The T8024 Thermostat is powered through the system transformer and is adaptable to most 24 Vac multistage heating cooling systems Refer to Fig 5 for typical wiring hookups Fig 3 Restrict wiring to shaded area 5 FEET 1 5 METERS YES NO NO NO M11338 M12202A WALL WALL ANCHORS 2...

Страница 3: ...nutes after the heating equipment turns on on most systems When using an electric heat thermostat the fan starts and stops with the heating equipment Slide the FAN switch in the bottom left corner of the thermostat to select the desired fan setting SYSTEM Switch System switch settings control thermostat operation as follows Cool The thermostat controls the cooling system Off Both heating and cooli...

Страница 4: ... 1d only pressing the key can be used to turn heat or cool outputs on and off Change the SYSTEM switch setting to test heat or cool outputs No action takes place If the system switch is in the Off position Examples System setting at HEAT If heat is on pressing the key turns it off if heat is off pressing the key turns it on System setting at COOL If cool is on pressing the key turns it off if cool...

Страница 5: ...ey to save all changes and return to normal operation Table 1 Heating Cycle Rates for Stage Two Heating a High efficiency furnace bRefer to equipment manufacturer s instructions PROGRAMMING The thermostat is flexible and can be programmed for different schedules for weekdays and weekends Four time periods are available during weekdays and weekends WAKE LEAVE RETURN and SLEEP IMPORTANT Always press...

Страница 6: ...C Refer to manufacturer s recommendations Allow compressor to remain off for five minutes before restarting 1 Slide the SYSTEM switch to Cool and the FAN switch to Auto 2 Press the key to lower the temperature setting several degrees below the room temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cool ing equipment 3 Press the key to...

Отзывы: