T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT

62-0125—3

8

Thermostat Information

1.

Press the Heat/Cool Settings key to access the 
thermostat information.

2.

Press the increase

 

∆ 

key to display the production 

date code. The first two large digits are the month 
and the third digit is the last digit of the year. 
(Example: 036 = March 1996.)

3.

Press the increase

 

∆ 

key again to display the soft-

ware identification code. (Example: 02 = software 
ID code 2.)

4.

Press the increase 

∆ 

key again to display the soft-

ware revision number. (Example: 001 = revision 
number 1.)

Cooling Equipment System Test

Heat/Cool Settings

30

Change from heating or emergency heating to cooling equipment system test.

31

Stage-one cooling and system fan turn on.

32

Stage-two cool turns on. Stage-one cool and system fan remain on.

33

Stage-three cool turns on (Q7300G only). Stage-one and stage-two cool with 
system fan remain on.

32

Stage-three cool turns off.

31

Stage-two cool turns off.

30

Stage-one cool and system fan turn off.

Fan Equipment System Test

Heat/Cool Settings

40

Change from cooling to fan equipment system test.

41

Fan turns on.

40

Fan turns off.

Key Operation System Test

Heat/Cool Settings

60   2

Change from fan to key operation system test.

Unoccupied Temp

60   0

Unoccupied Temp test number is displayed.

Occupied Temp

60   1

Occupied Temp test number is displayed.

60   3

Increase test number is displayed.

60   5

Decrease test number is displayed.

Clear Start Time

60   7

Clear Start Time test number is displayed.

Day

60   8

Day test number is displayed.

Copy

60   9

Copy test number is displayed.

Unoccupied Start TIme

60   10

Unoccupied Start Time test number is displayed.

System 
(select models)

60   11

System test number is displayed.

Fan (select models)

60   12

Fan test number is displayed.

Set Current Day/Time

60   14

Set Current Day/Time test number is displayed.

Run Program

60   15

Run Program test number is displayed.

Temporary Occupied

60   16

Temporary Occupied test number is displayed.

Occupied Start Time

60   17

Occupied Start Time test number is displayed.

Continuous 
Unoccupied

60   19

Continuous Unoccupied test number is displayed.

Table 4. Installer System Test Options (Continued)

Key to Press

Test 

Number

Description

M4934

M4931

M4932A

M10229

Содержание Tradeline T7300F series 2000

Страница 1: ...te management authority for instructions regarding recycling and the proper disposal of the old thermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 I...

Страница 2: ... used by the installer to customize the thermostat to specific systems Installer Setup numbers are listed in Table 2 The table includes all the configuration options available A combination of key presses are required to use the Installer Setup feature To enter the Installer Setup press and hold the Heat Cool Settings key with both the increase and decrease keys until the first number is displayed...

Страница 3: ...PLAY COLUMN 2 OF TABLE 2 FACTORY SETTING OR OTHER CHOICE DISPLAY COLUMN 3 OR 5 OF TABLE 2 Table 2 Thermostat Installer Setup Options Select Installer Setup Number Press Unoccupied Temp Key to change Factory Setting Other Choices Press or key to change Actual Setting Display Description Display Description Not used 1 Fan operationa 2 0 Conventional applications where equipment controls fan operatio...

Страница 4: ... 20 0 No extended fan operation after the call for cool ends 1 Fan operation is extended 90 seconds after the call for cool ends Fan key adjust ment models with Fan key 21 0 Fan setting key is operational 1 Fan setting key is Auto only Remote sensing 22 0 Remote sensing not activated 1 Remote sensing activated Temperature averaging networkb 23 0 Temperature averaging disabled 1 Temperature averagi...

Страница 5: ... 32 2 2 minute minimum on time for heating and cooling 0 or 1 No minimum on time or 1 minute minimum on time for heating and cooling Minimum off time for the compressor 33 4 4 minute minimum off time for the compressor 0 1 2 3 or 5 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Temperature range stops in heating 34 90 Highest setpoint for heating 40 ...

Страница 6: ...ypad lockout is enabled and disabled by dip switch 1 on back of thermostat 40 0 0 No Installer Setup lockout 1 1 Installer Setup lockout activated Table 2 Thermostat Installer Setup Options Continued Select Installer Setup Number Press Unoccupied Temp Key to change Factory Setting Other Choices Press or key to change Actual Setting Display Description Display Description a Number 2 must be set to ...

Страница 7: ... pump models only equipment can be turned on and off 30 to 39 Cooling equipment can be turned on and off 40 to 49 Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test 70 to 79 Thermostat information including date code software versions and subbase identification are displayed Heat Auto System Fan Off Un Mon Wait Lo In Room Remote Humid Auto Sav AM PM Comm Cool Duct Only On Reco...

Страница 8: ... Fan Equipment System Test Heat Cool Settings 40 Change from cooling to fan equipment system test 41 Fan turns on 40 Fan turns off Key Operation System Test Heat Cool Settings 60 2 Change from fan to key operation system test Unoccupied Temp 60 0 Unoccupied Temp test number is displayed Occupied Temp 60 1 Occupied Temp test number is displayed 60 3 Increase test number is displayed 60 5 Decrease t...

Страница 9: ...ockout Switch The dip switch 1 on the back of the thermostat activates the lockout features The switch must be set to the ON position up to activate the lockout feature See Fig 7 The factory setting is off down Remove the thermostat from the subbase and set the switch to ON if keypad lockout is desired The level of lockout is determined by the Installer Setup numbers 25 and 40 Fig 7 Set keypad loc...

Страница 10: ... circuit is open or shorted Temperature settings will not change Example Cannot set heating higher or cooling lower Upper or lower temperature limits were reached Check the temperature setpoints Heating limits are 40 to 90 F 7 to 31 C Cooling limits are 45 to 99 F 9 to 37 C The setpoint temperature range stops were configured Check Installer Setup number 34 and 35 and reconfigure the setpoint stop...

Страница 11: ...Vac between X and R or RC and Y terminals If missing 24 Vac check if the circuit breaker is tripped if so reset the circuit breaker check if the system fuse is blown if so replace the fuse check if the system switch at the equipment is in the Off position if so set to the On position check wiring between thermostat and HVAC equipment and replace any broken wires and tighten any loose connections I...

Страница 12: ...2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: