T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
62-0125—3
4
System setting
adjustment
(models with
System key).
12
Depends
on
model.
System selection.
0, 1 or 2 0—System setting key is
operational.
1—Auto setting is disabled.
2—Auto only setting.
Not used.
13
—
—
—
—
—
Degree
temperature
display.
14
0
Temperature is
displayed in °F.
1
Temperature is displayed
in °C.
Displaying
temperature.
15 0
Temperature
is
displayed.
1
Temperature is not
displayed.
Clock format.
16
0
12-hour clock format.
1
24-hour clock format.
Intelligent
Fan™
operation.
17
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0 or 1
0—Fan only operates with
calls for heating or cooling
in Occupied and
Unoccupied modes.
1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
Auxiliary
Contact
Operation.
18
0
0
⎯
Time-of-day
contacts.
1
1—Economizer contacts.
Extended fan
operation in
heating
a
.
19
0
No extended fan
operation after the call
for heat ends.
1
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in
cooling.
20
0
No extended fan
operation after the call
for cool ends.
1
Fan operation is extended
90 seconds after the call for
cool ends.
Fan key adjust-
ment (models
with Fan key).
21
0
Fan setting key is
operational.
1
Fan setting key is Auto
only.
Remote
sensing.
22 0
Remote
sensing
not
activated.
1
Remote sensing activated.
Temperature
averaging
network
b
.
23 0
Temperature
averaging
disabled.
1
Temperature averaging
between local sensor and
remote sensor(s) activated.
Not used.
24
—
—
—
—
—
Keypad lockout
level (keypad
lockout is
enabled and
disabled by dip
switch 1 on
back of
thermostat).
25
0
No lockout.
1 or 2
1—Lockout all keys on
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments.
2—Lockout all keys except
set Current Day/Time,
increase
∆
and decrease
∇
keys.
3
⎯
Lockout all keys except
temporary occupied, Set
Current Day/Time (for
clock, day adjustments).
Duration of
temporary
override.
26
3
3—Three hour
override.
1, 8 or
12
1—One hour override.
8—Eight hour override.
12—Twelve hour override.
Not used.
27 thru 29
—
—
—
—
—
Table 2. Thermostat Installer Setup Options (Continued)
Select
Installer Setup
Number
(Press
Unoccupied
Temp Key to
change)
Factory Setting
Other Choices
(Press
∆
or
∇
key to change)
Actual
Setting
Display
Description
Display
Description
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.