69-0931—3

3

Q7100A,C,D THERMOSTAT SUBBASES

Fig. 6. Nine T7047C Sensors providing a

temperature averaging network for a

T7100/Q7100 Thermostat/Subbase.

Subbase Installation

The subbase can be mounted horizontally on the wall or
a 2 in. x 4 in. wiring box. Position the subbase horizon-
tally on the wall or on a 2 in. x 4 in. wiring box.

1. Position and level the subbase (for appearance

only). The thermostat will function properly even
when not level.

2. Use a pencil to mark the mounting holes. See Fig. 7.

3. Remove the subbase from the wall and drill two

3/16 inch holes in the wall (if drywall) as marked. For
firmer material such as plaster or wood, drill two
7/32 inch holes. Gently tap anchors (provided) into
the drilled holes until flush with the wall.

4. Position the subbase over the holes, pulling wires

through the wiring opening.

5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.

WIRING

All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 9 through 15 for typical
hookups. A letter code is located near each terminal for
identification.

CAUTION

Disconnect power before wiring to prevent
electrical shock or equipment damage.

1. Loosen the terminal screws on the back of the

thermostat and connect the system wires. See
Fig. 8.

IMPORTANT

Use 18 gauge, color-coded thermostat cable for
proper wiring.

2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to

prevent drafts from affecting the thermostat.

M4842

T

T

T

T

SUBBASE

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

WIRES 
THROUGH WALL

WALL

LEDS

MOUNTING 
HOLES

MOUNTING 
SCREWS

M6531

WALL
ANCHORS
(2)

Fig. 7. Mounting the subbase.

Fig. 8. Proper wiring technique.

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

1

1

L1
(HOT)

L2

M4831A

HEAT 
RELAY OR 
VALVE COIL

COMPRESSOR
CONTACTOR

RC

O

G

X

W

COOL 
DAMPER

SUBBASE

B

HEAT
DAMPER

Y

FAN 
RELAY

RH

M4826

FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).

FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).

Fig. 9. Typical hookup of Q7100A1044 in a one-stage

heat and one-stage cool conventional system.

Содержание TRADELINE Q7100A

Страница 1: ...ions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Disconnect power supply to prevent electrical shock or equipment damage Location Subbase without Remote Mounted Temperature Sensor Install the subbase about 5 ...

Страница 2: ...iding a temperature averaging network for a T7100 Q7100 Thermostat Subbase M4838 T T SUBBASE T T T7047G T7047G T T M4839 T T SUBBASE T T T7047C T T T7047C T T T7047G M4840 T T T T SUBBASE T7047C T T T7047C T T T7047C T T T7047C Fig 4 Four T7047C Sensors providing a temperature averaging network for a T7100 Q7100 Thermostat Subbase M4841 T T SUBBASE T T T7047G T T T7047G T T T7047G T T T7047G T T T...

Страница 3: ... to Fig 9 through 15 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the back of the thermostat and connect the system wires See Fig 8 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 ...

Страница 4: ...ELAY 1 Y2 RH T D REMOTE TEMPERATURE SENSOR HEAT RELAY 2 W1 B T COMPRESSOR CONTACTOR 2 HEAT DAMPER L1 HOT L2 2 COMPRESSOR CONTACTOR 1 3 2 3 REMOTE SETBACK TIMER L1 HOT L2 M11089 COMPRESSOR CONTACTOR FAN RELAY O G Y1 COOL CHANGEOVER VALVE HEAT CHANGEOVER VALVE SUBBASE X HEAT RELAY AUX HEAT RELAY EM HT RELAY W1 R T T D D SENSOR TIMER EQUIPMENT MONITOR X1 E B W2 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNE...

Страница 5: ... temperature sensor and remote setback timer L1 HOT L2 M4834B FAN RELAY D O E W3 Y2 COOL CHANGEOVER VALVE SUBBASE 2 X B G EM HT RELAY R T D REMOTE TEMPERATURE SENSOR AUX HT RELAY Y1 T COMPRESSOR CONTACTOR 2 CAUTION EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED SELECT MODELS HAVE LEDS X4 NEEDS TO BE JUM...

Страница 6: ...Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 69 0931 3 Rev 2 98 L C Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com ...

Отзывы: