HE360 HUMIDIFIER AND INSTALLATION KIT
13
69-2631ES—01
IMPORTANT
All wiring must comply with applicable local code, ordinances and regula-
tions.
Wire the humidifier solenoid valve, pressure switch, humidistat and transformer. See
Fig. 13.
Fig. 13. Wiring the controls.
1.
Run the two-strand thermostat wire from the humidifier to the humidistat, and
from the humidistat to the pressure switch.
2.
Cut lengths of thermostat wire to reach between components, leaving adequate
wire at both ends for connections.
NOTE: Humidistat and pressure switch can be wired in any order.
3.
At the humidifier, connect the black and white conductors to the two yellow
humidifier wires. (The red wires from the humidifier are not used.)
4.
At the humidistat, connect both black conductors to the two humidistat terminals.
Use a wire nut to connect together the two white conductors.
5.
At the pressure switch, connect the black and white conductors to the C and NO
pressure switch terminals (NC terminal is not used).
M28974
HUMIDIFIER
SOLENOID
VALVE
Humidity Control
Régulateur d'humidité
-20 ¡F
-10 ¡F
0 ¡F
+10 ¡F
+20 ¡F
Over 20 ¡F
15%
20%
25%
30%
35%
40%
HUMIDITY
SETTING
OUTDOOR
TEMPERATURE
-30 ¡C
-25 ¡C
-20 ¡C
-10 ¡C
-5 ¡C
Over 0 ¡C
HUMIDISTAT
AIR PRESSURE
SWITCH
TRANSFORMER