Move the system switch to COOL and the fan switch to

AUTO. Press COOLER key until the setting is about
10

°

 F [6

°

 C] below room temperature. The cooling equip-

ment and fan should start. Press WARMER key until the
setting is about 10

°

 F [6

°

 C] above room temperature. The

cooling equipment and fan should stop.

FAN

Move the system switch to OFF, and the fan switch to

ON. The fan should run continuously. When the fan switch
is in the AUTO position, fan cycles with the heating or
cooling system.

EXTERNAL ACCESS AND CONTROL

A triangle 

 symbol is displayed on the lower right

corner of the LCD when the T8631 setting has been
adjusted through the TotalHome system.  See Fig. 11.

INSTALLER SELF-TEST (OPTIONAL)

NOTE: Thermostat must have AC power to perform

self-test.

Perform the following test as a check of all thermostat

functions.  If thermostat does not respond as indicated,
thermostat must be replaced.

1. Press AHEAD and BACK keys at the same time.

While holding keys down, all segments of the display
should be on. See Fig. 11.

2. Set system switch to OFF. Press AHEAD and BACK

and PRESENT SETTING keys at the same time to enter
self-test.

3. Press each key as listed below, and look for re-

sponses listed as key is held down and released.

Look For This Response

Press This Key

Key Down

Key Released

PRESENT SETTING

15

see note

a

following

SKIP NEXT PERIOD

07

blank

CHANGE TO LAST

03

blank

PERIOD
COOLER

02

blank

WARMER

06

serial number
transmitted
on HBus

BACK

04

blank

AHEAD

05

blank

RETURN

00

blank

LEAVE

01

control micro-
processor mask
number and
revision number

SLEEP

08

blank

WAKE

12

see note

b

following

SET HEAT/COOL

09

blank

DAY

13

interface
micro-
processor
mask number
and revision
number

HOLD TEMP

10

blank

SET PRESENT

14

see note

c

DAY/TIME

following

RUN PROGRAM

11

normal operat-
ing display

NOTES:

a

If the system switch is in COOL, the following se-
quence will occur:

6

Fig. 11—All segments on display.

SUN MON TUE WED THU FRI SAT COOL ON HEAT ON

WAKE LEAVE RETURN SLEEP TEMPORARY

REPL

BAT

AM
PM

SET
PT

M410C

Содержание T8631A

Страница 1: ...tion is complete check out product operation as provided in these instructions 5 Allow thermostat to warm to room temperature before operating IMPORTANT Afterwiringiscomplete pushexcesswire back into the hole and plug hole with nonhardening caulk putty or insulation to prevent drafts from affecting thermostat operation LOCATION Install thermostat and subbase about 5 ft 1 5 m above the floor in an ...

Страница 2: ...es Fig 1 Removing thermostat from subbase AUX HEAT HEAT AUTO COOL OFF ON AUTO FAN M3060 SYSTEM Fig 2 Mounting subbase on wall WIRES THROUGH WALL OPENING WALL WALL ANCHORS 2 SUBBASE MOUNTING HOLES MOUNTING SCREWS 2 M3061 HBUS SWITCH FAN OPERATIONAL SWITCH FOR T8631A ONLY 1 2 1 2 SWITCH UP DISCONNECTS THE HBUS FAN CAN BE SET FOR ELECTRIC HEAT OR CONVENTIONAL Fig 3 T8631A 1 stage heat 1 stage cool th...

Страница 3: ...RELAY EMERGENCY HEAT RELAY STAGE 1 HEAT RELAY COMPRESSOR CONTACTOR E HIGH LIMIT L E HEAT HIGH LIMIT TRANSFORMER E HEAT RED AUX HEAT GREEN HEAT 2 M3065A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE JUMPER IF PRESENT FOR SYSTEM WITH ISOLATED STAGE 1 HEATING AND COOLING CONNECTIONS DENOTES THERMOSTAT TO SUBBASE INTERCONNECT DO NOT CONNECT H BUS WIRES TO THERMOSTAT ...

Страница 4: ...naces it can be necessary to change the cycle rate to the hot water setting Cooling cycle rate is not adjustable but heating can be adjusted by turning one or both 1A and 1B screws on the back of the thermostat See Fig 8 for adjustments The screw should only be backed out about one half turn or be turned in until tight ADAPTIVE INTELLIGENT RECOVERY CON VENTIONAL RECOVERY CONVERSION The T8631A and ...

Страница 5: ...check to see that system power is on check to see that voltage between R and C is 20 to 30 Vac Fig 10 Mounting the thermostat on subbase M3059 PM RETURN MON HEAT ON SYSTEM AUTO PM RETURN MON HEAT ON SYSTEM RUN PROGRAM TIME TEMPERATURE PRESENT SETTING SKIP NEXT PERIOD CHANGE TO LAST PERIOD SET PRESENT DAY TIME HOLD TEMP DAY SET HEAT COOL SLEEP LEAVE AHEAD WARMER RETURN BACK COOLER WAKE A B C HEAT A...

Страница 6: ... AHEAD and BACK keys at the same time While holding keys down all segments of the display should be on See Fig 11 2 SetsystemswitchtoOFF PressAHEADandBACK and PRESENT SETTING keys at the same time to enter self test 3 Press each key as listed below and look for re sponses listed as key is held down and released Look For This Response Press This Key Key Down Key Released PRESENT SETTING 15 see note...

Страница 7: ...O OWNER S MANUAL FOR PROGRAM MING INSTRUCTIONS AND HOMEOWNER TROUBLESHOOTING 7 69 0689 2 This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations CRC c 1374 CAUTION Do NOT operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recommendations First press cooling system and SYSTEM LED on Second press cooling system and SYST...

Страница 8: ...ding Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in Taiwan R O C ...

Отзывы: