T8611G CHRONOTHERM

® 

DELUXE ZONING HEAT PUMP THERMOSTAT

69-1414—2

6

Degree 
temperature 
display

14

0

Temperature is 
displayed in °F

1

Temperature is displayed in 
°C

Not Used.

15

Clock format.

16

0

12-hour clock 
format.

1

24-hour clock format.

Not Used.

17 and 18

Extended fan 
operation in 
heating.

19

0

No extended fan 
operation after the 
call for heat ends.

1

Fan operation is extended 
90 seconds after the call for 
heat ends.

Extended fan 
operation in 
cooling.

20

No extended fan 
operation after the 
call for cool ends.

1

Fan operation is extended 
90 seconds after the call for 
cool ends.

Not Used.

21 thru 23

Outdoor 
temperature 
display (models 
with OT 
terminals).

24

0

No outdoor 
temperature is 
displayed.

1

Outdoor temperature is 
displayed. Needs a 
C7089B1000 Outdoor 
Temperature Sensor to 
operate.

Not Used.

25 thru 28

O/B terminal 
energized in 
heating or 
cooling.

29

0

O/B terminal 
energized for 
reversing valve in 
cooling.

1

O/B terminal energized for 
reversing valve in heating

Deadband

30

3

Heating and 
cooling setpoints 
can be set no 
closer than 3°F 
(1.5°C).

2 thru 10 Heating and cooling 

setpoints can be set no 
closer than the chosen 
value:

2—2°F (2°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)

Not Used.

31 thru 32

Minimum off 
time for the 
compressor.

33

5

5 minute minimum 
off time for the 
compressor.

0 thru 4

Minimum number of minutes 
(0 thru 5) the compressor is 
off between calls for the 
compressor.

Temperature 
range stops in 
heating.

34

90

Highest heating 
setpoint setting.

40 to 89

Temperature range (1°F 
increments) of heating 
setpoint settings.

Temperature 
range stops in 
cooling.

35

45

Lowest cooling 
setpoint setting.

46 to 99

Temperature range (1°F 
increments) of cooling 
setpoint settings.

System on 
indicator 
(flame=heat, 
snowflake= 
cool) is 
displayed.

36

0

LCD on symbol is 
displayed when 
system is 
energized

1

Icons in display are 
disabled.

Table 4. Thermostat Installer Setup Options. (Continued)

Select

Installer Setup 

Number (Press 

Time 

 key to 

change)

Factory Setting

Other Choices

(Press   or   key to change)

Actual 

Setting

Display

Description

Display

Description

Содержание T8611G Chronotherm

Страница 1: ...o make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 1 5m 5 ft above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by ...

Страница 2: ...n the wallplate and connect the system wires See Fig 5 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat The two OC terminals can be wired to the TZ 4 panel for remote operation of the Zone A Lone feature duri...

Страница 3: ...ing thermostat on wallplate NORMALLY WIRE E ON THERMOSTAT TO W1 E ON PANEL ALTERNATIVELY INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1 E ON PANEL CONNECT O B JUMPER ON TZ 4 PANEL WHEN O B TERMINAL ON THERMOSTAT IS CONFIGURED AS O CONNECT THE OC TERMINALS ONLY IF THE ZONE A LONE UNOCCUPIED FEATURE IS DESIRED SEE TZ 4 INSTALLER INSTRUCTIONS FOR EXPLANATION TZ 4 THERMOSTAT CONNECTORS 1...

Страница 4: ...ruments like a pen or pencil point can damage the keyboard Temperature Settings Refer to Table 3 for the default program If the daytime energy savings period is not used press the period key Leave or Return until the time is blank See Owner s Guide form number 69 1400 for complete instructions on changing the program NOTE For most applications the thermostat factory settings do not require changin...

Страница 5: ... Setup is complete review the settings to confirm that they match the system Period Time Heat Setpoint Cool Setpoint Fan Setting Wake 6 00 AM 70 F 21 C 78 F 25 5 C Auto Leave 8 00AM 62 F 16 5 C 85 F 29 5 C Auto Return 5 00 PM 70 F 20 C 78 F 25 5 C Auto Sleep 10 00 PM 62 F 16 5 C 82 F 28 C Auto M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em...

Страница 6: ...reversing valve in heating Deadband 30 3 Heating and cooling setpoints can be set no closer than 3 F 1 5 C 2 thru 10 Heating and cooling setpoints can be set no closer than the chosen value 2 2 F 2 C 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31 thru 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum...

Страница 7: ...F 1 5 C higher than actual room temperature 1 0 5 Display adjusts to 1 F 0 5 C lower than actual room temperature 2 1 0 Display adjusts to 2 F 1 0 C lower than actual room temperature 3 1 5 Display adjusts to 3 F 1 5 C lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 off 1 10 days 3 60 days 4 120 days Time is counted when heat cool or fan is runnin...

Страница 8: ...f days remaining at any time by pressing the i key three or four times If more than one timer is active all active timers show sequentially when pressing the i key several times M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Ru...

Страница 9: ... Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test 70 79 Thermostat information including date code and software versions are displayed M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 T...

Страница 10: ...ain to display the software identification code Example 02 software ID code 2 sy 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the self test The self test times out after four minutes without any key presses C...

Страница 11: ... limits are 48 to 99 F 7 to 37 C The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating or cooling does not come on No power to the thermostat Use action listed under Display will not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 33 Reco...

Страница 12: ...COOL or AUTO Cooling O G Y Snowflake Symbol Fan Symbol AUTO HEAT or AUTO None B None AUTO HEAT or AUTO Stage 1 Heating B Y Flame Symbol Fan Symbol AUTO HEAT or AUTO Stage 2 Heating B Y W2 Flame Symbol Fan Symbol AUX HEAT AUTO EM HEAT None L EM HEAT AUTO EM HEAT Stage 1 Heating L E Flame Symbol Fan Symbol EM HEAT AUTO EM HEAT Stage 2 Heating L E W2 Flame Symbol Fan Symbol EM HEAT AUX HEAT AUTO AUTO...

Отзывы: