T8611G CHRONOTHERM

® 

DELUXE ZONING HEAT PUMP THERMOSTAT

11

69-1414—2

TROUBLESHOOTING GUIDE (TABLE 7)

Table 7. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display does not 
come on.

Thermostat is not being 
powered.

•  Check for 24 Vac between R and C terminals.

— If missing 24 Vac:

—  verify that the thermostat is correctly wired to the zone 

control panel.

— R on thermostat to R on the TZ-3 and C to M1.
— R on thermostat to R on the EMM-3U and TZ-4 and 
C to C.

—  verify that the thermostat is correctly wired to the zone 

control panel.

—replace any broken wires and tighten any loose 

connections.

—  If 24 Vac is present, proceed with troubleshooting

Thermostat is not fully 
connected to wallplate.

Verify that thermostat is correctly positioned and securely 

latched to wallplate.

Temperature 
display is incorrect.

Room temperature display has 
been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for °F 
or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature 
settings do not 
change. (Example: 
Cannot set the 
heating higher or 
the cooling lower.)

The upper or lower temperature 
limits were reached. 

Check the temperature setpoints:

•  Heating limits are 40 to 90°F (4.5 to 32°C).
•  Cooling limits are 48 to 99°F (7 to 37°C).

The setpoint temperature range 
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the 
setpoint stops.

Heating or cooling 
does not come on.

No power to the thermostat.

Use action listed under “Display will not come on.”

Thermostat minimum off time is 
activated.

Wait up to five minutes for the system to respond.
Enter Installer Setup number 33.
Reconfigure the minimum off time, if required.

System selector is set to off.

Verify that the system selector is set for Heat, Cool or Auto.

Thermostat is not calling for 
heat or cool.

Verity that the heat or cool icon (flame or snowflake) is present. 
If not, raise or lower the setpoint to make a call for cool or heat.

System on indicator 
(flame=heat, 
snowflake=cool) is 
displayed, but no 
warm or cool air is 
coming from the 
registers.

Thermostat is not wired 
correctly to the zone panel.

Verify wiring. Check if other zones can bring on the heat or cool.

Zone panel is not correctly 
configured or wired correctly.

If no zones can bring on the heat, verify equipment configuration 
and wiring.

Outdoor tempera-
ture not displayed

a

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must 
have OT terminals and a C7089B1000 installed.

Outdoor 
temperature 
display is incorrect

a

Outdoor sensor is connected 
incorrectly.

Refer to C7089B1000 Installation Instructions and check wiring 
between the thermostat and sensor.

Wrong sensor.

Replace sensor with C7089B1000 Sensor.

a

Select models.

Содержание T8611G Chronotherm

Страница 1: ...o make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 1 5m 5 ft above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by ...

Страница 2: ...n the wallplate and connect the system wires See Fig 5 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat The two OC terminals can be wired to the TZ 4 panel for remote operation of the Zone A Lone feature duri...

Страница 3: ...ing thermostat on wallplate NORMALLY WIRE E ON THERMOSTAT TO W1 E ON PANEL ALTERNATIVELY INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1 E ON PANEL CONNECT O B JUMPER ON TZ 4 PANEL WHEN O B TERMINAL ON THERMOSTAT IS CONFIGURED AS O CONNECT THE OC TERMINALS ONLY IF THE ZONE A LONE UNOCCUPIED FEATURE IS DESIRED SEE TZ 4 INSTALLER INSTRUCTIONS FOR EXPLANATION TZ 4 THERMOSTAT CONNECTORS 1...

Страница 4: ...ruments like a pen or pencil point can damage the keyboard Temperature Settings Refer to Table 3 for the default program If the daytime energy savings period is not used press the period key Leave or Return until the time is blank See Owner s Guide form number 69 1400 for complete instructions on changing the program NOTE For most applications the thermostat factory settings do not require changin...

Страница 5: ... Setup is complete review the settings to confirm that they match the system Period Time Heat Setpoint Cool Setpoint Fan Setting Wake 6 00 AM 70 F 21 C 78 F 25 5 C Auto Leave 8 00AM 62 F 16 5 C 85 F 29 5 C Auto Return 5 00 PM 70 F 20 C 78 F 25 5 C Auto Sleep 10 00 PM 62 F 16 5 C 82 F 28 C Auto M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em...

Страница 6: ...reversing valve in heating Deadband 30 3 Heating and cooling setpoints can be set no closer than 3 F 1 5 C 2 thru 10 Heating and cooling setpoints can be set no closer than the chosen value 2 2 F 2 C 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31 thru 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum...

Страница 7: ...F 1 5 C higher than actual room temperature 1 0 5 Display adjusts to 1 F 0 5 C lower than actual room temperature 2 1 0 Display adjusts to 2 F 1 0 C lower than actual room temperature 3 1 5 Display adjusts to 3 F 1 5 C lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 off 1 10 days 3 60 days 4 120 days Time is counted when heat cool or fan is runnin...

Страница 8: ...f days remaining at any time by pressing the i key three or four times If more than one timer is active all active timers show sequentially when pressing the i key several times M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Ru...

Страница 9: ... Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test 70 79 Thermostat information including date code and software versions are displayed M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 T...

Страница 10: ...ain to display the software identification code Example 02 software ID code 2 sy 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the self test The self test times out after four minutes without any key presses C...

Страница 11: ... limits are 48 to 99 F 7 to 37 C The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating or cooling does not come on No power to the thermostat Use action listed under Display will not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 33 Reco...

Страница 12: ...COOL or AUTO Cooling O G Y Snowflake Symbol Fan Symbol AUTO HEAT or AUTO None B None AUTO HEAT or AUTO Stage 1 Heating B Y Flame Symbol Fan Symbol AUTO HEAT or AUTO Stage 2 Heating B Y W2 Flame Symbol Fan Symbol AUX HEAT AUTO EM HEAT None L EM HEAT AUTO EM HEAT Stage 1 Heating L E Flame Symbol Fan Symbol EM HEAT AUTO EM HEAT Stage 2 Heating L E W2 Flame Symbol Fan Symbol EM HEAT AUX HEAT AUTO AUTO...

Отзывы: