background image

T8400C1099, T8401C1031 ELECTRONIC THERMOSTATS

69-1484-2

6

NOTE: In installer setup mode only, each press of the 

 key momentarily displays 01. Each press of 

the 

 key momentarily displays 02. When the 

keys are released, these two-digit codes are no 
longer displayed. 

3.

Press the 

 key. Factory information is displayed. 

A typical example is shown, but information dis-
played varies by model. This information is for fac-
tory use only.

4.

Press the 

 key again to display °C or °F.

5.

Press the

  ▼

 key to change the °C or °F indication.

6.

Press the 

 key to display the heat cycle rate of 1, 

3, 4, 5, 6, 9, or 12. To change the heat cycle rate, 
press the 

 key to scroll between 1, 3, 4, 5, 6, 9, or 

12. Stop scrolling when the desired rate is dis-
played. See Table 1 for the cycle rate options and 
the corresponding system equipment.

7.

Press the 

 key to display heating/cooling temper-

ature control default..

8.

Press the 

 key again to change heating/cooling 

temperature control to C1 or C3.

C1 = Standard heating/cooling temperature 

control.

C3 = Aggressive heating/cooling temperature 

control (can cause room temperature to 
overshoot the setpoint).

9.

Press the 

 key again. Factory information (varies 

by model) is shown.

Table 1. Heating Cycle Rates.

a

High efficiency furnace.

b

Refer to equipment manufacturer’s instructions.

10.

Press the 

 key to save all changes, exit installer 

setup mode and return to normal operation.

NOTE: After exiting installer setup mode, slide the   

System switch to the desired position and 
change the setpoint to the desired room       
temperature.

CHECKOUT

Heating

1.

Slide the SYSTEM switch to Heat and the FAN 
switch to Auto.

2.

Press and hold the 

 key to raise the temperature 

setting several degrees above the room tempera-
ture. After approximately ten seconds, the heating 
equipment should start. In conventional systems, 
the system turns on the fan through the use of a 
time delay relay or through a limit control. When 
using an electric heat thermostat, the fan starts 
immediately.

3.

Press the 

 key to lower the temperature setting 

below the room temperature. Heating equipment 
should stop.

Cooling

CAUTION

Low Temperature Hazard.
Operating at too low of an outdoor 
temperature may cause compressor damage.

Do not operate cooling if outdoor temperature is 
below 50°F (10°C). Refer to manufacturer’s 
recommendations. 

• For compressor protection, during power 

interruption and on initial startup, the T8400 
and T8401 Thermostats go into a five-minute 
delay. During this delay, the cooling icon (a 
snowflake 

) flashes.

1.

Slide the SYSTEM switch to Cool and the FAN 
switch to Auto.

2.

Press the 

▼ 

key to lower the temperature setting 

several degrees below the room temperature. After 
approximately five minutes, the cooling equipment 
should start. The fan starts and stops with the cool-
ing equipment.

M14687

M14688

M14689

M14690

M18419A

M18420

System

Cycles Per Hour

Steam, gravity

1

Hydronic heat, condensing gas 
furnace

a

3

Gas or oil forced air

6

Electric heat

9

Special applications

b

4, 5, 12

Содержание T8400C1099

Страница 1: ... Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power su...

Страница 2: ...e maximum wire to wire the T8400 and T8401 Thermostats All wiring must comply with local electrical codes and ordinances Disconnect the power supply to prevent electrical shock or equipment damage NOTE To ensure proper mounting of thermostat restrict all wiring to the shaded area See Fig 4 The shape of the terminals permits insertion of straight or wraparound wiring connections either method is ac...

Страница 3: ...SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER M13275 Y G Rc W R B O 2 2 Y G Rc W 2 4 R B O M12562A L1 HOT L2 FAN RELAY HEAT RELAY L1 HOT L2 COMPRESSOR CONTACTOR HEATING TRANSFORMER COOLING TRANSFORMER HEAT DAMPER COOL DAMPER 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSF...

Страница 4: ...ent In heating the fan is controlled directly by the heating equipment and may start a few minutes after the heating equipment turns on on most systems When using an electric heat thermostat the fan starts and stops with the heating equipment Slide the FAN switch in the bottom left corner of the thermostat to select the desired fan setting L1 HOT L2 1 FAN RELAY COOL RELAY HEAT RELAY 24V M20881 TRA...

Страница 5: ... degrees 4 To decrease the temperature setpoint press the key Each press changes the setpoint one degree press and hold to change the setpoint several degrees Setting F C Indication and Heat Cycle Rate NOTE To save changes to the F C indication the heat cycle rate and the C3 C1 temperature control tap the key until exiting the installer setup To set the F C indication the heat cycle rate and the C...

Страница 6: ...OTE After exiting installer setup mode slide the System switch to the desired position and change the setpoint to the desired room temperature CHECKOUT Heating 1 Slide the SYSTEM switch to Heat and the FAN switch to Auto 2 Press and hold the key to raise the temperature setting several degrees above the room tempera ture After approximately ten seconds the heating equipment should start In convent...

Страница 7: ...M switch to Off and the FAN switch to On The fan should run continuously 2 Slide the FAN switch to Auto In heating the fan is controlled directly by the heating equipment and may start a few minutes after the heating equip ment turns on on most systems When using an electric heat thermostat the fan starts and stops with the heating equipment In cooling the fan starts and stops with the cooling equ...

Страница 8: ...www honeywell com yourhome T8400C1099 T8401C1031 ELECTRONIC THERMOSTATS Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: