Move the temperature setting lever about 10

°

 F [6

°

 C]

below room temperature. Cooling and fan should start
immediately. Move temperature setting lever about 10

°

 F

[6

°

 C] above room temperature. Cooling and fan should

stop immediately.

RECALIBRATION

These thermostats are calibrated at the factory and should

not need recalibration. If the thermostat seems out of ad-
justment, first check for accurate leveling. To check cali-
bration, proceed as follows:

1. Move the temperature setting lever to the low end of

the temperature scale.

2. Remove the thermostat cover. Move the setting lever

until the switch just makes contact. The mercury in the
switch will drop to the contact end of the tube.

3. Replace the cover and wait five minutes for the cover

and the thermostat to lose the heat it has gained from your
hands. If the thermometer pointer and the setting lever
indicator read approximately the same, no recalibration is
needed.

If recalibration appears necessary, proceed as follows:
1. Place the temperature setting lever at the same setting

as the thermometer. Remove cover.

2. Insert 104994A Calibration Wrench (order separately)

onto the hex nut under the coil. See Fig. 7. Holding the
setting lever so it does not move, turn the wrench clock-
wise

  until the switch just breaks contact.

Remove wrench and replace cover.

3. Move the setting lever to a low setting. Wait at least

five minutes for temperature to stabilize.

4. Slowly move the setting lever until it reads the same

as the thermometer.

5. Remove cover. Holding the setting lever so it does

not move, reinsert wrench and carefully turn counter-
clockwise

      until the mercury just rolls to the left end

of the tube, but 

no

 

farther

.

6. Recheck calibration. Set thermostat system switch

for desired operation and replace the cover.

Fig. 7—Recalibration procedure.

CALIBRATION
WRENCH

COIL SHOWN WITHOUT
HEAT ANTICIPATOR

M2044

www.honeywell.com/yourhome

Automation and Control Solutions

Honeywell Internationals Inc.

Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, Minnesota  55422

Scarborough, Ontario  M1V 4Z9

Содержание T8022D

Страница 1: ...ion T822A D F TS822A and T8022D Thermostats pro vide control of heating systems T822G provides control of AC heating or cooling appliances The T822A two wire switch thermostat provides low voltage control of heating systems and features a fixed heat anticipator The T822D and T8022D two wire mercury switch thermostat provides low voltage control of heating systems and features an adjustable heat an...

Страница 2: ...R R G W FAN RELAY HEAT RELAY 1 FAN SWITCH ON AUTO 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M5512 T822G L1 HOT L2 TEMP FALL H1 H1 ANTICIPATOR R Y W COOL RELAY HEAT RELAY 1 1 C1 C1 ANTICIPATOR 2 USE EITHER W OR Y TERMINAL BUT NOT BOTH 2 4 Remove thermostat cover by pulling outward on bottom edge of cover until it snaps free of the thermostat base Carefully remove a...

Страница 3: ...d mount the thermostat Continue with system checkout NOTE For best performance the heat anticipator may require further adjustment To lengthen burner on time move the indicator in the direction of the longer ar rows not more than one half scale marking at a time To shorten burner on time move indicator in opposite direction Checkout CAUTION CAUTION Do not check thermostat operation by shorting acr...

Страница 4: ...ppears necessary proceed as follows 1 Placethetemperaturesettingleveratthesamesetting as the thermometer Remove cover 2 Insert104994ACalibrationWrench orderseparately onto the hex nut under the coil See Fig 7 Holding the setting lever so it does not move turn the wrench clock wise until the switch just breaks contact Remove wrench and replace cover 3 Move the setting lever to a low setting Wait at...

Отзывы: