T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER

63-2248—4

14

temperature goes down, the control point goes down). The
type of ratio is selected by using the two DIP switches
provided.

The four possible reset operating configurations are illustrated
and explained in Fig. 18. Switches 1 and 2 are shown but
switches 3 and 4 are unused; however, the location of these
DIP switches is shown in Fig. 5.

CAUTION

A reset ratio lower than one can result in unstable
control. Widening the throttling range and/or
differential minimizes this effect.

Propor Integral Modulating Control

Propor Integral (P+I) control provides fast, responsive
operation of the controlled devices in reacting to temperature
changes by providing an output signal proportional to the
deviation between setpoint and actual temperature. An
integral proportion also provides a time dependent output
signal that is dependent on the length of time of the deviation
between actual set point and sensed temperature.

The P + I algorithm places the control setpoint in the middle
of the throttling range. A deadband around setpoint exists and
is proportional to the throttling range. For the T775, this
deadband is 1/8 of the throttling range.

There are three modulation options available for the T775J
(see Fig. 20 for modulating output connecting terminals).

Fig. 18. Reset switch configuration.

Fig. 19. Summary of action/direction switches.

PWB

SWITCH

SWITCH

PWB

OPEN

CLOSED

SIDEVIEW

OPEN

CLOSED

RESET DIRECTION SWITCH

RESET ACTION SWITCH

RESET DIRECTION SWITCH: WILL RESET
THE COUNTROL POINT UP (WHEN 
OPEN) OR DOWN (WHEN CLOSED).

RESET ACTION SWITCH: RESET IF THE
OUTDOOR TEMPERATURE (SENSOR B) IS 
ABOVE (WHEN CLOSED) OR BELOW 
(WHEN OPEN) THE OUTDOOR 
TEMPERATURE SETPOINT.

1

2

OPEN

CLOSED

OPEN

CLOSED

OPEN

CLOSED

OPEN

CLOSED

RESET DIRECTION SWITCH CLOSED

RESET ACTION SWITCH CLOSED 

IF THE OUTSIDE SENSOR (B) 
TEMPERATURE IS ABOVE THE OUTSIDE
TEMPERATURE SETPOINT,THE CONTROL 
POINT WILL BE DECREASED BY THE 
RESET RATIO.

1

2

RESET DIRECTION SWITCH OPEN

RESET ACTION SWITCH CLOSED 

IF THE OUTSIDE SENSOR (B) 
TEMPERATURE IS ABOVE THE OUTSIDE
TEMPERATURE SETPOINT,THE CONTROL 
POINT WILL BE INCREASED BY THE 
RESET RATIO.

1

2

RESET DIRECTION SWITCH CLOSED

RESET ACTION SWITCH OPEN 

IF THE OUTSIDE SENSOR (B) 
TEMPERATURE IS BELOW THE OUTSIDE
TEMPERATURE SETPOINT,THE CONTROL 
POINT WILL BE DECREASED BY THE 
RESET RATIO.

1

2

RESET DIRECTION SWITCH OPEN

RESET ACTION SWITCH OPEN 

IF THE OUTSIDE SENSOR (B) 
TEMPERATURE IS BELOW THE OUTSIDE
TEMPERATURE SETPOINT,THE CONTROL 
POINT WILL BE INCREASED BY THE 
RESET RATIO.

1

2

M8110A

Содержание T775J

Страница 1: ...ng and operation Accuracy is within 1 F C at nominal input voltage nominal sensor ambient temperature 77 F 25 C operating ambient Accuracy can vary as parameters deviate from nominal Stages independently programmed for heating or cooling 24 120 240 Vac voltage inputs Spdt relay outputs IMPORTANT The T775 is an operating control not a limit or safety control When used in applications requiring safe...

Страница 2: ...40 F 34 C to 60 C Sensor 45 F to 225 F 43 C to 107 C Throttling Range for Modulating Output Adjustable 2 to 30 F or C Differential Range for Staged Output Adjustable 1 to 30 F Reset Ratio Adjustable between 1 to 30 and 30 to 1 Operating Humidity 5 to 95 percent relative humidity noncondensing Sensor Positive coefficient platinum type 4 8 ohms F 1000 feet maximum distance between sensor and solid s...

Страница 3: ...3 16 97 4 3 4 121 8 1 2 216 5 7 32 134 1 1 4 32 1 1 4 32 2 3 8 60 7 8 22 DIAMETER CAUTION Disconnect power before installation to prevent electrical shock or equipment damage Location and Mounting Mount the controller in any convenient interior location using the two mounting holes provided Mounting screws are not included Use controller dimensions in Fig 1 as a guide Sensor Location The 193987GA ...

Страница 4: ...rd conduit knockouts A C located around the enclosure perimeter NOTE Hole A should only be used for remote sensor wiring low voltage wiring and access to modulating output When wiring the input power only one source of power can be applied to the T775J e g 24 or 120 or 240 Vac Knockouts B and C can be used to gain access to 120 or 240 Vac input terminals and the load relay output terminals The T77...

Страница 5: ...r to the T775 when an electrically noisy environment exists See Fig 6 SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F T775 GROUND SHIELD TO T775 CASE OR TO GROUNDING SCREW SHIELDED CABLE SHIELDED CABLE GROUNDING SCREW NOTE DO NOT GROUND SHIELDED CABLE AT SENSOR END NOTE TO MINIMIZE NOISE PICKUP MAKE CONNECTION FROM SHIELDED ...

Страница 6: ...NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F M8111 SENSOR A 24 VAC SENSOR B LOAD 1 LOAD 2 SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F M8112 SENSOR A 120 VAC SENSOR B LOAD 1 LOAD 2 BLK WHT SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 ...

Страница 7: ...M SLIDEWIRE DEVICES PROPER OUTPUT LEVELS CAN BE CHECKED BY MEASURING THE OPEN CIRCUIT VOLTAGE BETWEEN TERMINALS 1 W AND 2 R MINIMUM DRIVE CLOSED 0 17 VDC MAXIMUM DRIVE OPEN 1 7 VDC ELECTRONIC SERIES 90 MODUTROL MOTOR T775J NOTE B R W Fig 11 Reset control with 24 Vac input Series 90 and 24 Vac loads SELECT SET ENTER OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C...

Страница 8: ...WITCHES FOR SENSOR TO LOAD SELECTION M954 OR M955 MODUTROL MOTOR M4717 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 USE 1300 OHM RESISTOR FOR 2 MOTORS 910 OHMS RESISTOR FOR 3 MOTORS 4047EAU RESISTOR KIT SHIPPED WITH M954 M955 MOTORS INCLUDES 1300 OHM AND 910 OHM RESISTORS 2 B R W SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 ...

Страница 9: ...user to program for both heating and cooling loads to be energized at the same time If this situation results cooling loads will be energized and heating loads will be prevented from also energizing The number 1 2 of these nonenergized loads will flash along with the word HEAT to indicate a call for both heating and cooling loads controlled by one sensor has occurred and to alert the user to repro...

Страница 10: ...memory 쐄 Press Select to display the current stage throttling range or switching differential 쐂 Press Set up arrow to increase or Set down arrow to decrease the display to the desired throttling range or switching differential 쐆 Press Enter to enter the displayed value into memory 쐊 Repeat steps 2 through 7 to program each additional stage IMPORTANT After initial programming altering the setpoint ...

Страница 11: ...sed for calibrating the device in column B following the example in column A Calibration Setpoint for Cooling Mode Fig 13 Setpoint for calibrating the lower voltage level closed position A B Sensed Temperature 78 Add 3 F or C to above 3 Calibration Setpoint 81 Calibration Setpoint for Heating Mode A B Sensed Temperature 78 Subtract 3 F or C from above 3 Calibration Setpoint 75 Calibrate the Lower ...

Страница 12: ...NSOR INPUT TOD AND 24 VAC TERMINALS 1 2 34 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB VOLTMETER CONNECT THE MODULATING VOLTAGE OUTPUT TO A VOLTMETER USING A SCREWDRIVER ADJUST THE LOWER LIMIT OF THE VOLTAGE TO THE DESIRED LEVEL ACCORDING TO THE STEPS OUTLINED IN CLAIBRATION PROCEDURE FOR 0 TO18 VDC OUTPUT NO COM NC OUTPUT 1 OUTPUT 2 NOCOM NC 120V COM 240V 0 18 STEP 3 1 2 3 1 2 3 4 3 14 17 8 OPEN GE...

Страница 13: ...modulating or relay outputs for reset control Each stage of the T775J has its own independent setpoint that can be configured to operate in the cooling or heating mode The mode of operation for each stage is user determined by the programming keys For reset control with two outputs one of which is modulating the modulating output will be designated as stage 1 on the LCD display Although the modula...

Страница 14: ... 1 8 of the throttling range There are three modulation options available for the T775J see Fig 20 for modulating output connecting terminals Fig 18 Reset switch configuration Fig 19 Summary of action direction switches PWB SWITCH SWITCH PWB OPEN CLOSED SIDEVIEW OPEN CLOSED RESET DIRECTION SWITCH RESET ACTION SWITCH RESET DIRECTION SWITCH WILL RESET THE COUNTROL POINT UP WHEN OPEN OR DOWN WHEN CLO...

Страница 15: ...OOR TEMPERATURE DROPS BELOW SETPOINT B RIGHT RESETS AS IT RISES ABOVE IT C SWITCHES 3 AND 4 ARE NOT USED RESETS CONTROL SETPOINT A DOWN WHEN SENSOR B OUTSIDE TEMPERATURE IS BELOW SETPOINT RESETS CONTROL SETPOINT A DOWN WHEN SENSOR B OUTSIDE TEMPERATURE IS ABOVE SETPOINT RESETS CONTROL SETPOINT A UP WHEN SENSOR B OUTSIDE TEMPERATURE IS BELOW SETPOINT RESETS CONTROL SETPOINT A UP WHEN SENSOR B OUTSI...

Страница 16: ...e F mode Remove the jumper plug for the C mode Remove and reapply power if the jumper is removed with the device powered DIP Switch Selections DIP switches see Fig 18 are provided for assignment of the reset configurations A second set of DIP switches provides voltage range selection for 0 to 18 Vdc modulating devices The span corresponding to each switch is given on the printed wiring board below...

Страница 17: ... SF Sensor Failure The display flashing SF indicates an out of range sensor Make sure the sensors are properly connected For the T775J stage 2 load will be de energized when this error message is flashing for Sensor B When this message is flashing for Sensor A only stage 1 will not be de energized EF EEPROM Failure The values read back from the EEPROM are not the same as written into the EEPROM Th...

Страница 18: ...a reset condition exists d If no reset condition exists On Off Control Values have not been changed e Go to step 11 f If a reset condition exists calculate the amount of reset using Formula 2 g Divide Reset Ratio B value by Reset Ratio A value h Multiply the result in step g by Temp Diff step a i If Reset Direction Switch is set to increase disregard any negative signs and add the amount of reset ...

Страница 19: ... 80 Off 76 On 80 78 Off 74 On 120 Off 116 On 80 118 Off 80 Setpoint B ____________ Reset Direction __________ Setpoint B 30 Reset Direction Increase Sensor B _____________ Reset Action ____________ Sensor B 10 Reset Action Below Reset Ratio A _________ Reset Ratio B ___________ Reset Ratio A 1 Reset Ratio B 2 FORMULA 1 FORMULA 1 EXAMPLE Sensor B Sensor B 10 F Setpoint B Setpoint B 30 F Temp Diff _...

Страница 20: ...rld Home and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 63 2248 4 Rev 9 95 Printed in U S A www honeywell com building components QUALITY IS KEY Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Отзывы: