INSTALLATION INSTRUCTIONS 

BEFORE INSTALLATION 

All wiring must comply with local electrical codes and 

ordinances or as specified on installation wiring diagrams. 

 

Wall module wiring can be sized from 16 to 22 AWG (1.5 to 

0.34 mm

2

), depending on the application. The maximum 

length of wire from a device to a wall module is 1000 ft (305 

m). Twisted-pair wire is recommended for wire runs longer 

than 100 ft (30.5 m). 

 

COVER DISASSEMBLY 

The cover of the wall module is fixed in place using a tab 

located on the underside of the unit; to disassemble the 

cover and the sub-base, see Fig. 1. 

 

PRESS

LIFT

 

Fig. 1. Cover disassembly 

 

Table 1. Features of T7460 Versions 

 

Sensor

 

Setpoint

 

Bypass/ LED

 

Fan speed

T7460A 

 

- -  - 

T7460B 

 

 

- - 

T7460C 

 

 

 

T7460D 

 

 

- 5-position 

T7460E 

 

 

 

3-position 

T7460F 

 

 

 

5-position 

 

INSTALLATION 

The T7460B,C,D,E,F packages include two setpoint dials. 

By default, the “Celsius Relative” type is mounted. This can 

be easily replaced with the “Celsius Absolute” type by 

pulling the one dial off and inserting the other one. 

 

Mount the T7460A,B,C,D,E,F Wall Modules on an inside 

wall approximately 54 in. (1.3 m) from the floor (or in the 

specified location) to allow exposure to the average zone 

temperature. 

NOTE:

  Maintain a mounting clearance of approx. 4 in. 

(10 cm) to the left-hand side of the module in 
order to allow a free airflow for the temperature 
sensor and accessibility of the setpoint dial. 
 
Do not mount the wall modules on an outside wall, 
on a wall containing water pipes, or near air ducts. 
Avoid locations that are exposed to discharge air 
from registers or radiation from lights, appliances, 
or the sun. 
 
The T7460D,E,F should not be connected to 
controllers that do not support fan operation (i.e., 
the W7751, W7762, W7763, W7704, and 
XFC2xxxx/XFC3xxxx). 
 
When used with CPO-FB22344R-xxx controllers, 
either setpoint override or fan-speed adjustment is 
supported. 
 
Keep wiring at least 1 ft (305 mm) away from large 
inductive loads such as motors, line starters, 
lighting ballasts, and large power distribution 
panels. Run wall module wiring separately from 50 
Vac or greater power wiring. 

 

The wall modules can be mounted on a 60-mm wall outlet 

box using No. 6 (3.5-mm) screws or on a wall (see Fig. 2 

and Fig. 5). When mounting directly on a wall, use the type 

of screws appropriate for the wall material. 

 

 

Fig. 2. Bore-holes for T7460 wall modules in in. (mm) 

See Fig. 3 for mounting dimensions. 

 

NOTE:

  Graphics depict E/F model. Dimensions are the 

same for all six models. 

Содержание T7460A

Страница 1: ...dules on an inside wall approximately 54 in 1 3 m from the floor or in the specified location to allow exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the wall modules on an outside wall on a wall contai...

Страница 2: ...solute scale or the 5 Celsius relative scale point to the right hand side of the wall module see Fig 4 Fig 4 Mounting position of setpoint dial 7 T7460B C D E F only If the dial does not have the correct position pull the dial off again and reinsert it with the correct orientation 8 Remount the cover as depicted in Fig 5 and make sure that the tab on the underside engages Fig 5 Mounting cover of T...

Страница 3: ...minal example Excel 50 terminal example Excel 20 terminal example CPO FB22344R terminal example sensor signal 2 2 XF821 1 AI XF521 1 AI XFL521 1 AI 1 AI 33 AI 19 AI 39 AI COM GND 1 1 XF821 11 AI GND XF521 2 AI GND XFL521 18 AI GND 55 GND 34 AI GND 20 AI GND 40 AI GND SETPT 3 3 XF821 2 AI XF521 3 AI XFL521 2 AI 2 AI 35 AI 21 AI 41 AI BYP FAN no fan 4 4 XF821 3 AI XF521 5 AI XFL521 3 AI 3 AI 37 AI 2...

Страница 4: ...A 1 W77xx 1 W77xx B 2 W7753 2 W7753 3 XL500 3 XL500 SETPOINT NOTE Terminal 5 LED of the T7460C E F is reserved for connection to a 4 20 Vdc 3 5 mA LED input only hen using the T7460C E F wall module in conjunction with the Excel 10 UV Controller W7753 connect terminal 6 BYP RTN with the controller s bypass input W BYPASS BUTTON T7460C E F only IMPORTANT The gray shaded terminals are internally con...

Страница 5: ...d and allows easy access to LONWORKS or BACnet via the correspondingly wired wall module apply appropriate wiring guidelines for LONWORKS or BACnet networks as the case may be The T7460 LONJACK provides an additional 3 5 mm jack socket for a 3 5 mm jack plug Order quantity set with 5 pieces LonWorks connection terminals PC con nection 3 5 mm jack plug Fig 9 T7460 LONJACK Mounting Remove the setpoi...

Страница 6: ...chnologies Sàrl Rolle Z A La Pièce 16 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 7031 63701 Fax 49 7031 637493 http ecc emea honeywell com Subject to change without notice Printed in Germany EN1B 0291GE51 R1111B 95 7610 4 rev Nov 2011 Printed in Germany ...

Отзывы: