3
UWP Wiring terminal designations
S
Not used for T4
thermostat.
L/A
- A
Heat Pump fault input (most
common case)
S
O/B
Changeover valve
Y
Compressor contactor
(stage 1)
AUX -
W2
Auxiliary heat (TH4210 only)
Y2
Not used for T4
thermostat.
E
Emergency heat (TH4210
only)
G
Fan Relay
W
Heat relay (stage 1)
C
24VAC common. For 2
transformer systems,
use common wire from
cooling transformer.
K
Connect to K on Wire Saver
Module**
U
Not used for T4
thermostat.
R
24VAC power from heating
transformer*
U
Rc
24VAC power from cooling
transformer*
Note: Not all
terminals may be
used, depending
on the system
type that is being
wired. The most
commonly used
terminals are
shaded.
* Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above.
** The THP9045A1023 Wire Saver Module is used on heat/cool systems when you
only have four wires at the thermostat, and you need a fifth wire for a common wire.
Use the K terminal in place of the Y and G terminals on conventional or heat pump
systems to provide control of the fan and the compressor through a single wire—the
unused wire then becomes your common wire. See THP9045 instructions for more
information.
Set R Slider Tab.
• Use built-in jumper
(R Slider Tab)
to differentiate between one or two
transformer systems.
• If there is only one R wire, and it is
connected to the
R
,
Rc
, or
RH
terminal, set
the slider to the up position
(1 wire)
.
• If there is one wire connected to the
R
terminal and one wire connected to the
Rc
terminal, set the slider to the down position
(2 wires)
.
NOTE:
Slider Tabs for U terminals should be
left in place for T4 Pro models.
Setting Slider Tabs (built-in jumper)
R/Rc Slider Tab
(built-in jumper)
UWP Mounting System