Honeywell SUPER TRADELINE S8610U Скачать руководство пользователя страница 16

S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL

69-1955

16

Step 1: Perform Visual Inspection.

1.

With power off, make sure all wiring connections 
are clean and tight.

2.

Turn on power to appliance and ignition control 
module.

3.

Open manual shutoff valves in the gas line to the 
appliance.

4.

Perform a gas leak test ahead of gas control if pip-
ing has been disturbed.

GAS LEAK TEST: 

Paint the gas control gasket edges and all pipe 
connections upstream of the gas control with a rich 
soap and water solution. Bubbles indicate gas 
leaks. Tighten the joints and screws or replace 
component to stop gas leak. Recheck with soap 
and water solution.

Step 2: Verify Ignition Control System Ground.

The igniter, flame sensor, and ignition control module 
must share a common ground with the pilot burner. Use 
thermoplastic insulated wire with a minimum rating of 
221°F (105°C) for the ground wire; asbestos insulation is 
not acceptable. If the temperature at the wire could 
exceed 221°F (105°C), use a shield to protect the wire 
from radiant heat generated by the burner. Connect the 
ground wire as follows:

1.

Fit one end of the ground wire with a female 1/4 in. 
quick-connect terminal and connect it to the male 
quick-connect GND (BURNER) terminal on the igni-
tion control module.

2.

Strip the other end of the wire and fasten it under 
the igniter bracket mounting screw. If necessary, 
use a shield to protect the ground wire from radiant 
heat.

3.

The burner serves as the common grounding area. 
If there is not good metal-to-metal contact between 
the burner and ground, run a lead from the burner 
to ground.

NOTE: Earth ground is not required.

Step 3: Review Normal Operating Sequence and 
Ignition Control Module Specifications.

— See “Operation” section on this page and “Specifi-

cations” on page 3. 

Step 4: Reset the Ignition Control Module.

1.

Turn the thermostat to its lowest setting.

2.

Wait one minute.

As you perform the remaining steps, watch for points 
where operation deviates from normal. To correct 
problems, refer to the “Troubleshooting Guide” on 
page 21.

Step 5: Check Safety Shutoff Operation.

1.

Turn gas supply off.

2.

Set thermostat or controller above room tempera-
ture to “Call for Heat.”

3.

Watch for spark at pilot burner. Time spark from 
start to shutoff. Spark should shut off after 15 or 90 
seconds (selectable with Dip Switch SW1). See 
device label and “Settings and Adjustments” on 
page 15.

4.

Wait 5 minutes. Ignition sequence should start 
again followed by shutoff. 

5.

Open manual gas cock and make sure no gas is 
flowing to pilot or main burner.

6.

Set thermostat below room temperature and wait 
one minute before continuing.

Step 6: Check Normal Operation.

1.

Turn on the gas supply.

2.

Set thermostat or controller above room tempera-
ture to “Call for Heat.”

3.

Make sure pilot lights smoothly when gas reaches 
the pilot burner.

4.

Make sure main burner lights smoothly without 
flashback.

5.

Make sure burner operates smoothly without float-
ing, lifting, or flame rollout to the furnace vestibule 
or heat buildup in the vestibule.

6.

Perform a gas leak test in the appliance.

GAS LEAK TEST: 

Paint the gas control gasket edges and all pipe 
connections downstream of the gas control, 
including the pilot tubing connections, with a rich 
soap and water solution. Bubbles indicate gas 
leaks. Tighten the joints and screws or replace 
component to stop gas leak. Recheck with soap 
and water solution.

7.

Turn the thermostat or controller below the room 
temperature. Make sure the main burner and pilot 
flames go out.

OPERATION

Fig. 8 on page 17 summarizes the normal operating 
sequence for installations with and without vent dampers. 
The ignition control module’s operation can be 
conveniently divided into two phases. 

• Trial for pilot ignition
• Main burner operation

Trial for Pilot Ignition

On a “Call for Heat”, the ignition control module energizes 
the spark source and the pilot valve relay simultaneously. 
The pilot valve opens, allowing gas to flow to the pilot 
burner for the ignition trial time. The spark lights the pilot 
flame when pilot gas is present. A flame rectification 
circuit confirms the presence of the pilot flame, shuts off 
the spark source, and energizes the main valve relay.

The ignition control module uses a two-level pilot flame 
proving sequence. When a sufficient flame current is 
sensed, the spark is turned OFF. However, the pilot flame 
must generate a higher level of flame current to energize 
the main valve. This approach assures a stable pilot flame 
to support reliable burner lightoff. If the pilot flame is weak 
or unstable, the spark may turn back ON. However, the 
trial for pilot ignition will not exceed the stated ignition trial 
time.

Main Burner Operation

When the main valve opens, gas flows to the main burner 
where it is lit by the pilot flame. There is a short flame 
stabilization period as the main valve opens to allow the 
pilot flame to stabilize as the main gas lights. The system 
is now in the run mode with the presence of the pilot flame 
continuously monitored by the flame rectification circuit. If 
the pilot flame goes out, the ignition control module 
senses loss of pilot flame and shuts off both the pilot valve 
relay and the main valve relay. Flow of gas to pilot and 
main burners stops as the valves close (100% shutoff).

Содержание SUPER TRADELINE S8610U

Страница 1: ... adapt the existing spark cable Rajah stud nail or other to the spark terminal on the control module It also help assure proper marking of the wires attached to the existing control and a label with LED code information that can be affixed in the appliance IMPORTANT The S8610U control module is not designed to replace controls with Flame sensing other than by flame rectification White Rodgers Cycl...

Страница 2: ...610C1013 S8610C3001 S8610F1008 S8610F1016 S8610F1024 S8610F1032 OFF OFF S8610H1004 OFF ON S8610H1012 OFF OFF S8610H1020 OFF ON S8610H1038 S8610H1046 S8610H1053 OFF OFF S8610H1061 OFF ON S8610H1079 S8610H1095 S8610H3000 OFF OFF S8610H3018 OFF ON S8610H3026 S8610M1003 OFF OFF S8610M1011 OFF ON S8610M1029 S8610M3009 OFF OFF S8610M3017 OFF ON S8610U1003 S8610U1011 OFF OFF S8620C1003 S8620C1011 OFF ON ...

Страница 3: ...BKG 1 G65BKG 2 G65BKG 3 G65BKM 1 G65BKM 2 G65BKM 3 G65BLG 1 G65BLG 2 G65DBG G65DBM 1 G65DBM 2 G65DBM 3 G65DCM 1 G65DFG G65DFM 1 G65DKG G65DKM G65DKM 1 G65DLM 1 G65FBG G65FFG G65FKG OFF OFF Table 2 S8610U Replaces These Modules Continued Vendor Model SW1 SW2 G66AG 1 G66AG 2 G66BG 1 G66MG 1 G66MG 2 G66NG 1 OFF OFF G67AG 3 G67AG 4 G67AG 7 G67AG 8 G67AG 9 G67AG 10 G67AG 11 G67BG 2 G67BG 3 G67BG 4 G67B...

Страница 4: ...for the ignition control module Corrosive Chemicals Corrosive chemicals can attack the ignition control module and gas control eventually causing a failure If chemicals are used for routine cleaning make sure they do not reach the controls Where chemicals are suspended in air as in some industrial or agricultural applications use a NEMA 4 enclosure for the ignition control module Dust or Grease Ac...

Страница 5: ...rm Pre Installation Safety Check The pre installation checks described below must be done before the replacement ignition control module is installed If a condition that could result in unsafe operation is detected the appliance should be shut off and the owner advised of the unsafe condition Correct any potentially unsafe condition before proceeding with the installation The following safety chec...

Страница 6: ...ield wiring terminals Operating ambient temperatures between 40 F 40 C and 165 F 74 C Relative humidity below 95 non condensing Protection from water steam or corrosive chemicals that are used to clean the appliance Protection from dripping water such as from an overfilled humidifier or from condensation Protection from dust or grease accumulation IMPORTANT Do not mount with terminals facing up Fi...

Страница 7: ...sor stud on the pilot burner igniter sensor Connect Ignition Control Module CAUTION Equipment Damage Hazard Check the wiring diagram provided on the appliance and compare with Table 5 through Table 8 beginning on page 8 Carefully follow any special instructions affecting the general wiring procedures outlined in this section 1 Connect the wires to the module as shown in the wiring tables Table 5 t...

Страница 8: ...t a vent damper was not installed or if it did not have a vent damper connector then connect the 25V 2 or 24V wire from the old module to the TH W terminal on the S8610U Do not use the 24V terminal on the S8610U If the old module had a vent damper connect it to the P1 connector on the module and wire the terminals as indicated in the table 25V 2 or 24V used only in systems where plug in cable conn...

Страница 9: ...79 Y79A module b b Discard wires between Y79A and module as follows Red to 3 Black to 2 White to GR Discard wire between transformer and 6 Y79A module c c Discard wires between Y79B and module as follows White to 3 Black to 1 Brown to GR Discard wire between transformer and 6 Main Valve Operator MV 3 3 Y79B MV MV 3 Main Valve and Pilot Common MV PV GR GR GR GROUND 5 Pilot Valve Operator PV 1 1 Y79...

Страница 10: ...om E1 which is tagged Thermostat Flame Sensor SENSE d d Important If the USI 715U with combination igniter sensor is not used remove black jumper quick connect from Remote Sense terminal of S8610U Cut jumper wire at circuit board and discard e e Labeled OPT SENSOR on USI 715U No external connection if combination igniter sensor is used d d Igniter Sensor SPARK IGN IGN IGN Table 8 Conversion from C...

Страница 11: ...ves as the common grounding area If there is not good metal to metal contact between the pilot burner and ground run a lead from the pilot burner to ground NOTE Earth ground is not required Wiring Connections Use Fig 2 and Table 9 to make the remaining wiring connections Fig 3 Fig 5 beginning on page 12 illustrate typical wiring connections in heating systems with atmospheric burners and with powe...

Страница 12: ... LEG TO TRANSFORMER ONCE POWERED UP WITH VENT DAMPER CONNECTED MODULE WILL OPERATE ONLY WITH DAMPER CONNECTED FOR SINGLE ROD APPLICATIONS CONNECT JUMPER WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE...

Страница 13: ...R WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR M23617 1 2 3 4 5 6 THERMOSTAT L1 HOT L2 LIMIT CONTROLLER 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL P...

Страница 14: ...ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR 1 2 3 4 5 6 REMOTE SENSE JUMPER WIRE CLIPPED CLOSE TO BOARD TWO ROD SENSOR WIRE FROM IGNITER SENSOR 6 THERMOSTAT L1 HOT L2 1 LIMIT CONTROLLER 2 4 3 M23586 AIR PROVING SWITCH COMBUSTION ...

Страница 15: ...out the gas control system At initial installation of the appliance As part of regular maintenance procedures Maintenance intervals are determined by the application For additional information See Planning the Installation on page 4 As the first step in troubleshooting Any time work is done on the system WARNING Fire or Explosion Hazard Failure to heed these warnings may cause fire or explosion wi...

Страница 16: ...r main burner 6 Set thermostat below room temperature and wait one minute before continuing Step 6 Check Normal Operation 1 Turn on the gas supply 2 Set thermostat or controller above room tempera ture to Call for Heat 3 Make sure pilot lights smoothly when gas reaches the pilot burner 4 Make sure main burner lights smoothly without flashback 5 Make sure burner operates smoothly without float ing ...

Страница 17: ...rating Sequence OPERATING SEQUENCE CALL FOR HEAT RECEIVED FROM THERMOSTAT POWER TO MODULE AND SELF CHECK IDLE NOT POWERED RUN YES TRIAL FOR IGNITION TIMER STARTED SPARK ON OPEN PILOT GAS VALVE FLAME PROVED FLAME STABILIZATION 2 SECONDS YES NO RETRY OPEN MAIN GAS VALVE CLOSE MAIN GAS VALVE AND PILOT GAS VALVE FLAME LOST NO CLOSE PILOT GAS VALVE SPARK OFF CALL FOR HEAT ENDS YES NO RETRY DELAY 5 MINU...

Страница 18: ...trol module and to the igniter or igniter sensor are clean and tight 5 Ignition cable provides good electrical continuity STEP 2 Check Ignition System Grounding Nuisance shutdowns are often caused by a poor or erratic ground A common ground is required for the ignition control module and the pilot burner bracket 1 Check for good metal to metal contact between the pilot burner bracket and the main ...

Страница 19: ...ems and their causes i If necessary adjust pilot flame by turning the pilot adjustment screw on the gas control clock wise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation j Set thermostat below room temperature to end Call for Heat 4 Recheck ignition sequence as follow...

Страница 20: ...al for ignition Flash code will remain through the ignition trial until flame is proved If system fails to light on next trial for ignition check gas supply pilot burner flame sense wiring contamination of flame rod burner ground connection 4 Flame sensed out of sequence If situation self corrects within 10 seconds control module returns to normal sequence If flame out of sequence remains longer t...

Страница 21: ... FOR HEAT IS ALWAYS CONNECTED TO THE TH W TERMINAL ON THE MODULE START BEFORE TROUBLESHOOTING FAMILIARIZE YOURSELF WITH THE STARTUP AND CHECKOUT PROCEDURES TURN THERMOSTAT CONTROLLER TO CALL FOR HEAT CHECK LINE VOLTAGE POWER LOW VOLTAGE TRANSFORMER LIMIT CONTROLLER THERMOSTAT CONTROLLER AND WIRING ALSO CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM IF USED AND THAT THE END SWITCH IF USED...

Страница 22: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 69 1955 22 ...

Страница 23: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 23 69 1955 ...

Страница 24: ...d Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2006 Honeywell International Inc 69 1955 M S 11 06 ...

Отзывы: