Honeywell SUITEPRO TB6575 Скачать руководство пользователя страница 15

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS

15

62-0311—05

Fig. 26 illustrates the relationship between setpoints, 
Remote Setback, and deadband for auto changeover with 
heat and cool setpoints.

Fig. 26. Auto Changeover with Heat/Cool Setpoints 

deadband illustration.

For 4 pipe applications with Auto Changeover and a 
single setpoint, when Economy Setback is enabled, the 
setpoint will revert to a dual heat/cool setpoint approach. 
The remote setback heating and remote setback cooling 
setpoints will be used to create an effective unoccupied 
deadband. 

Fig. 27 illustrates the unoccupied deadband when 
Economy Setback is enabled for 4-pipe single setpoint 
auto changeover.

Fig. 27. 4 Pipe Auto Changeover with Single Setpoint 

and Economy Setback Deadband Illustration

Fan Modes

VERSASPEED™ FAN RAMPING

When the fan switch is in auto, the thermostat will cycle 
the fan using the fan ramping algorithm. The appropriate 
fan speed is selected according to Fig. 28.

The fan ramping algorithm is illustrated in Fig. 28

Fig. 28. VersaSpeed™ fan ramping algorithm 

illustration.

AUTO FAN RESET (ISU CODE #24)

If Auto Fan Reset is enabled, and a constant fan speed is 
selected, the thermostat resets the fan to Auto.
• Value = 1: The fan resets back to Auto after 2 hours.
• Value = 2: The fan resets back to Auto after 4 hours.
The start time is calculated after the initial call for Heat/
Cool is satisfied. Then, the two or four hour timing begins. 
The fan is set back to Auto when the 2-hour or 4-hour 
delay expires.

Application Modes

2 PIPE SEASONAL CHANGEOVER APPLICATIONS

These applications require the pipe sensor as a N.O, 
N.C., or Analog Input to detect seasonal changeover:

• 2 pipes with auto changeover
• 2 pipes with auxiliary heat
Changeover occurs when the system has been changed 
over from the boiler to the chiller. This occurs on a 
seasonal basis from winter to summer months. When 
using a pipe sensor as an analog input, the thermostat 
can use the logic below to determine what mode to 
operate in. A changeover will occur when the pipe 
temperature goes above the threshold for heating or 
below the threshold for cooling. If a purge has not 
occurred or a call has not been satisfied in awhile, the 
pipe temperature may start to get close to the ambient 
temperature. In this case, the thermostat will only 
changeover once the temperature falls into the opposite 
threshold. 

2 Pipes with Auto Changeover

For this application the system switch only provides “Off” 
and "Auto". When in "Auto" mode the water temperature 
will indicate if the thermostat should operate in heating or 
cooling. 

Operation: 

After exiting the installer setup, the thermostat will perform 
a 5 minute purge. During this initial 5 minute purge, the 
valve (W/Y) will energize and the fan will be de-energized. 
After the 5 minute purge, the thermostat will go into the 
appropriate mode as described in Table 6

Table 6. Logic for 2 Pipes with Auto Changeover

*If pipe temperature is between the two threshold values 
after the 5 minute purge occurs, the thermostat will 
activate a second 5 minute purge to double check the 
water temperature. If after the second 5 minute purge, the 
water temperature is still between the two thresholds, the 
valve output will be disabled and only manual fan will be 
available. It will stay in this operation until the next purge 
cycle occurs. 

2 Pipes with Auxiliary Heat

For this application, when there is hot water in the pipes, 
the system switch provides "Off" and "Heat". When there 
is cold water in the pipes, the system switch provides 
"Off", "Heat", and "Cool". 

UNOCCUPIED DEADBAND

 DEADBAND  

REMOTE SETBACK COOL SETPOINT

UNOCCUPIED DEADBAND

COOL SETPOINT

HEAT SETPOINT

REMOTE SETBACK HEAT SETPOINT

M27562

M31331

HEAT SWITCHING POINT

REMOTE SETBACK HEAT SETPOINT

REMOTE SETBACK COOL SETPOINT

COOL SWITCHING POINT

SETPOINT

UNOCCUPIED DEADBAND

UNOCCUPIED DEADBAND

-2°F 

+2°F 

+4°F 

-4°F

FAN SPEED IS HIGH

DIFFERENCE

BETWEEN 

RT AND 

SETPOINT

COOL 

HEAT 

SETPOINT

M27563

FAN SPEED IS MEDIUM

FAN SPEED IS LOW

FAN SPEED IS HIGH

FAN SPEED IS LOW

FAN SPEED IS MEDIUM

Pipe Temperature after purge

System Mode

>Threshold for Heating (ISU code #7) Heat
Between Thresholds
 After Purge Occurs

Fan Only*

< Threshold for Cooling (ISU code #6) Cool

Содержание SUITEPRO TB6575

Страница 1: ...re easily made with a press of a key Valves and auxiliary electric heaters can be controlled using a relay or contactor controlled by the system switch FEATURES Simple intuitive user interface Pre installed lead wires for fast installation TB6575A and TB6575B models only Backlight display permits easy viewing in any light Four buttons allow manual control of system operation fan speed and temperat...

Страница 2: ...ble of accepting up to 2 x 18 AWG 0 8 sq mm 1 x 16 AWG 1 3 sq mm or 1 x 14 AWG 2 1 sq mm wires Accepts stranded or unstranded 14 28 gauge wire NOTES 1 The TB6575A1000 model is pre fitted with color coded fly leads 16 AWG attached to seven terminals 2 The TB6575B1000 model is pre fitted with color coded fly leads 16 AWG attached to six terminals 3 The TB8575A1000 model does not have fly leads attac...

Страница 3: ...re or a temperature outside of the thermostat operating range of 18 C to 49 C 0 F to 120 F With displayed the thermostat ceases to operate When the temperature returns to within its operating limits the thermostat returns to operation The optional freeze protect feature should be used if low temperatures can occur The thermostat must be mounted flush to the wall The thermostat can be mounted direc...

Страница 4: ...press the adaptor plate screw cover into place Fig 2 Mounting sub base and thermostat to 2 x 4 in junction box Fig 3 Mounting sub base and thermostat using the adaptor plate 50033847 001 Terminal Wiring Table 3 provides the terminal wiring for each model and application NOTE The TB6575A1000 and TB6575B1000 models have color coded fly leads attached to the termi nals Refer to Table 3 for the color ...

Страница 5: ... Cool with Seasonal Changeover 9 W Y 9 9 9 9 O R O 9 4 pipes Heat and Cool with Manual Changeover 9 W Y 9 9 9 9 O R O 4 pipes Heat and Cool with Auto Changeover 9 W Y 9 9 9 9 O R O 2 pipes Heat or Cool with Auxiliary Heat 9 W Y A 9 9 9 9 O R O 9 4 pipes Heat and Cool with Manual Changeover or Auto Changeover 9 W Y 9 9 9 9 O R O TB6575B1000 120 240 Vac Terminal Identifier L W Y n ai i Terminal 3 is...

Страница 6: ... grounded controller case IMPORTANT All wiring must comply with local electrical codes and ordinances or as specified on installation wiring dia grams Wall module wiring can be sized from 16 to 22 AWG 1 31 to 0 33 sq mm depending on the application The maximum length of wire from the thermostat to a wall module is 1000 ft 305 m Twisted pair wire is recommended for wire runs longer than 100 ft 30 5...

Страница 7: ...uto Changeover wiring diagram 120 240 Vac shown Fig 11 Four pipes Heat and Cool Manual Auto changeover wiring diagram 120 240 Vac shown Fig 12 Two pipes Heat or Cool with Auxiliary Heat and Manual Changeover wiring diagram 120 240 Vac shown L W Y Y A GI Gm Gh N Rs Sc SB Ps N L HOT M27566 REMOTE SENSOR REMOTE SETBACK HEAT VALVE FAN N L HOT M27567 REMOTE SENSOR REMOTE SETBACK COOL VALVE FAN L W Y Y ...

Страница 8: ...S FAN MEDIUM SETTING WILL OPERATE ON HIGH SPEED CONNECT TERMINAL 7 TO THE MID FAN SPEED WIRE FROM THE PREVIOUS SYSTEM REWIRE THE PREVIOUS MID SPEED FAN WIRE TO THE NEUTRAL CIRCUIT IN THE SYSTEM CHANGE INSTALLER SETUP IS CODE 9 TO 2 FOR 2 SPEED FAN CONTROL 3 4 N L W Y Y A GI Gm Gh N Rs Sc SB Ps 24 VAC M27573 HEAT VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT M...

Страница 9: ...s to pull the thermostat straight away from the sub base 24 VAC M27576 VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PIPE SENSOR R W Y Y A GI Gm Gh C Rs Sc SB Ps 24 VAC M27577 HEAT VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED COOL VALVE ...

Страница 10: ...verload will damage the thermostat The thermostat has a safety fuse rated at 15 A 250 Vac If the fuse blows the thermostat must be replaced The fuse is not field replaceable This fuse is provided as a safety feature to prevent fire if the thermostat is overloaded Installer Setup ISU Mode To enter Installer Setup Mode Press and hold both the System button labeled Heat Cool and the Up Arrow button f...

Страница 11: ...n Auxiliary Heat is on 3 Valve Output Type 0 Valve energized on call for heat or cool Default 1 Valve de energized on call for heat or cool 4 Space Sensor Type 0 Onboard Sensor Default 1 Remote Sensor TR21 or other 20K Ohm sensor 5 Pipe Sensor Only displays when value 3 or 6 for the System Type in ISU code 2 is selected 0 Contact Open Cool mode Contact Closed Heat mode Pipe sensor will flash on di...

Страница 12: ...ingle Setpoint 2 to 6 Range is 2 to 6 Default is 3 Heat switching point setpoint switching differential Cool switching point setpoint switching differential Available when Single Setpoint is chosen for the control method for 4 pipe Auto ISU 10 11 CPH Value for Heat 1 to 12 Range is 1 to 12 Default is 4 The number selected indicates the maximum times Heating is cycled on per hour CPH ISU 2 selectio...

Страница 13: ...ing from Occupied to UnOccupied 5 Button Press Default Press and hold Heat Cool Off button for 3 seconds and thermostat will go into Economy Setback 20 Remote Setback for Heating 50 to 70 Range is 50 F to 70 F Default is 64 F Used when the thermostat is in the Unoccupied state 21 Remote Setback for Cooling 72 to 90 Range is 72 F to 90 F Default is 79 F 22 Activity Sensing 0 Disabled Default This w...

Страница 14: ...on the remote setback input from an occupancy sensor time switch or hotel card key The thermostat controls to the user installer defined setback setpoints for increased energy savings The LCD displays Economy Setback just to the right of the main temperature display to indicate the Remote Setback mode is active When Remote Setback is active all buttons on the thermostat are disabled However the bu...

Страница 15: ...er will occur when the pipe temperature goes above the threshold for heating or below the threshold for cooling If a purge has not occurred or a call has not been satisfied in awhile the pipe temperature may start to get close to the ambient temperature In this case the thermostat will only changeover once the temperature falls into the opposite threshold 2 Pipes with Auto Changeover For this appl...

Страница 16: ...te purge will occur when it is switched back into Heat or Cool 4 PIPES AUTO CHANGEOVER Single Set Point Method In 4 pipe auto changeover with a single setpoint the temperature is always controlled to the setpoint Switching points are used to determine when to switch between heating and cooling modes If the current mode is heat and the temperature drifts above the cool switch point Setpoint Switchi...

Страница 17: ...ooling equipment Verify operation of equipment in Installer Test mode Heat does not turn on Heat On is solid in the display Heating equipment failure For TB6575A B 1 Check for 120 240 Vac at the equipment between power and common terminals L and N 2 Check for 120 240 Vac between the heat W and common N terminals If 120 240 Vac is present the thermostat is functional For TB8575A 1 Check for 24 Vac ...

Страница 18: ...ed heating and or cooling equipment Heating equipment does not turn off and heat temperature setting is set below room temperature Heat On is not in the display Incorrect System Type configured Check that the Installer Setup code 2 System Type value matches the installed heating and or cooling equipment Cannot set the system setting to Heat System Type Installer Setup code 2 is set to Cool Only va...

Страница 19: ... Freeze protection is not activated when system type is Cool ISU code 2 value 1 Change System Type System mode is not Off Set the System mode button to Off Auto Fan Reset does not activate Incorrect ISU code Set the Installer Setup code 24 to Enabled value 1 or 2 Calling for Heat Cool setpoint couldn t be satisfied Only after the setpoint is satisfied will the auto fan reset timer activate Table 8...

Страница 20: ... Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 62 0311 05 M S Rev 10 10 Printed in U S A ...

Отзывы: