TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS

62-0311—05

14

NOTE: Exiting Installer Test Mode is the same as the 

method for entering test mode, 

 

Fig. 25. Installer Test (IT) mode screen.

OPERATION

PROPOR INTEGRAL 
(P+I) CONTROL

Like a mechanical thermostat, the fan coil thermostats 
have On/Off control output. However, this output is 
regulated by a P+I algorithm, enabling the thermostat to 
control closer to setpoint than conventional thermostats. 
This results in performance where the space temperature 
is maintained within 0.75°C (1.5°F) of the setpoint 
regardless of fan speed.

NOTE: Integral action corrects the temperature control 

errors of proportional-only control, but it is slower 
to react to large temperature or setpoint 
changes. 

Economy Setback Modes

ACTIVITY SENSING (ISU CODE #22)

If Activity Sensing is enabled, any time the thermostat is 
not touched (no single key is pressed) for the duration 
selected, the thermostat automatically falls back into the 
Economy Setback. The LCD displays ECONOMY 
SETBACK just to the right of the main temperature 
display to indicate Activity Sensing mode is active. When 
any key is pressed, the thermostat controls to Occupied 
mode.

BUTTON PRESS SETBACK (ISU CODE #19-5)

The default remote setback option is for economy setback 
via a button press on the thermostat. In this mode, the 
thermostat can quickly be setback by pressing and 
holding down the System Mode button for more than 3 
seconds. The LCD displays ECONOMY SETBACK just to 
the right of the main temperature display to indicate the 
Setback is active. When any key is pressed, the 
thermostat controls to Occupied mode. 

REMOTE SETBACK (ISU CODE #19)

Remote Setback is activated by a dry contact closure on 
the remote setback input from an occupancy sensor, time 
switch, or hotel card key. The thermostat controls to the 
user/installer defined setback setpoints for increased 
energy savings. The LCD displays Economy Setback just 
to the right of the main temperature display to indicate the 
Remote Setback mode is active.

When Remote Setback is active, all buttons on the 
thermostat are disabled. However, the button 
combinations to access Installer Setup (ISU) and Installer 
Test (IT) remain enabled.

ECONOMY SETBACK OPERATION

For Heat Mode, when Economy Setback is enabled, the 
set point changes to the remote setback heating setpoint
(ISU CODE #20).

For Cool Mode, when Economy Setback is enabled, the 
set point changes to the remote setback cooling setpoint
(ISU CODE #21).

For 4 pipe applications with Auto Changeover and Heat/
Cool Setpoints, when Economy Setback is enabled, the 
cool setpoint changes to the remote setback cooling 
setpoint and the heat setpoint changes to the remote 
setback heating setpoint. The new effective deadband is 
the difference between the remote setback heating 
setpoint and the remote setback cooling setpoint.

Table 5. Installer Test (IT) Codes and Options.

IT

Code

Code

 Description

Option

Value

Option Description

10

Heat Control

0

Close

1

Open

20

Auxiliary Heat 
Control

0

Close

1

Open

30

Cool Control

0

Close

1

Open

40

Fan Control

0

Close

1

Low  Speed

2

Medium Speed

3

High Speed

50

Pipe Sensor

32-199 Displays the pipe 

sensor temperature.
Only used for System 
Type 3 or 6 (ISU code 
#2, value 3 or 6). Only 
the Analog pipe sensor 
is tested.

71

Software Main 
version

01-99 A 2-digit number, 01-99

72

Software Vice 
version

01-99 A 2-digit number, 01-99

73

Configuration 
Data Main version

01-99 A 2-digit number, 01-99

74

Configuration 
Data Vice version

01-99 A 2-digit number, 01-99

75

Week Produced

01-52 A 2-digit number, 01-52

76

Year Produced

08-99 A 2-digit number, 08-99

M27587

Test

Содержание SUITEPRO TB6575

Страница 1: ...re easily made with a press of a key Valves and auxiliary electric heaters can be controlled using a relay or contactor controlled by the system switch FEATURES Simple intuitive user interface Pre installed lead wires for fast installation TB6575A and TB6575B models only Backlight display permits easy viewing in any light Four buttons allow manual control of system operation fan speed and temperat...

Страница 2: ...ble of accepting up to 2 x 18 AWG 0 8 sq mm 1 x 16 AWG 1 3 sq mm or 1 x 14 AWG 2 1 sq mm wires Accepts stranded or unstranded 14 28 gauge wire NOTES 1 The TB6575A1000 model is pre fitted with color coded fly leads 16 AWG attached to seven terminals 2 The TB6575B1000 model is pre fitted with color coded fly leads 16 AWG attached to six terminals 3 The TB8575A1000 model does not have fly leads attac...

Страница 3: ...re or a temperature outside of the thermostat operating range of 18 C to 49 C 0 F to 120 F With displayed the thermostat ceases to operate When the temperature returns to within its operating limits the thermostat returns to operation The optional freeze protect feature should be used if low temperatures can occur The thermostat must be mounted flush to the wall The thermostat can be mounted direc...

Страница 4: ...press the adaptor plate screw cover into place Fig 2 Mounting sub base and thermostat to 2 x 4 in junction box Fig 3 Mounting sub base and thermostat using the adaptor plate 50033847 001 Terminal Wiring Table 3 provides the terminal wiring for each model and application NOTE The TB6575A1000 and TB6575B1000 models have color coded fly leads attached to the termi nals Refer to Table 3 for the color ...

Страница 5: ... Cool with Seasonal Changeover 9 W Y 9 9 9 9 O R O 9 4 pipes Heat and Cool with Manual Changeover 9 W Y 9 9 9 9 O R O 4 pipes Heat and Cool with Auto Changeover 9 W Y 9 9 9 9 O R O 2 pipes Heat or Cool with Auxiliary Heat 9 W Y A 9 9 9 9 O R O 9 4 pipes Heat and Cool with Manual Changeover or Auto Changeover 9 W Y 9 9 9 9 O R O TB6575B1000 120 240 Vac Terminal Identifier L W Y n ai i Terminal 3 is...

Страница 6: ... grounded controller case IMPORTANT All wiring must comply with local electrical codes and ordinances or as specified on installation wiring dia grams Wall module wiring can be sized from 16 to 22 AWG 1 31 to 0 33 sq mm depending on the application The maximum length of wire from the thermostat to a wall module is 1000 ft 305 m Twisted pair wire is recommended for wire runs longer than 100 ft 30 5...

Страница 7: ...uto Changeover wiring diagram 120 240 Vac shown Fig 11 Four pipes Heat and Cool Manual Auto changeover wiring diagram 120 240 Vac shown Fig 12 Two pipes Heat or Cool with Auxiliary Heat and Manual Changeover wiring diagram 120 240 Vac shown L W Y Y A GI Gm Gh N Rs Sc SB Ps N L HOT M27566 REMOTE SENSOR REMOTE SETBACK HEAT VALVE FAN N L HOT M27567 REMOTE SENSOR REMOTE SETBACK COOL VALVE FAN L W Y Y ...

Страница 8: ...S FAN MEDIUM SETTING WILL OPERATE ON HIGH SPEED CONNECT TERMINAL 7 TO THE MID FAN SPEED WIRE FROM THE PREVIOUS SYSTEM REWIRE THE PREVIOUS MID SPEED FAN WIRE TO THE NEUTRAL CIRCUIT IN THE SYSTEM CHANGE INSTALLER SETUP IS CODE 9 TO 2 FOR 2 SPEED FAN CONTROL 3 4 N L W Y Y A GI Gm Gh N Rs Sc SB Ps 24 VAC M27573 HEAT VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT M...

Страница 9: ...s to pull the thermostat straight away from the sub base 24 VAC M27576 VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PIPE SENSOR R W Y Y A GI Gm Gh C Rs Sc SB Ps 24 VAC M27577 HEAT VALVE FAN L1 HOT L2 1 REMOTE SENSOR REMOTE SETBACK 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED COOL VALVE ...

Страница 10: ...verload will damage the thermostat The thermostat has a safety fuse rated at 15 A 250 Vac If the fuse blows the thermostat must be replaced The fuse is not field replaceable This fuse is provided as a safety feature to prevent fire if the thermostat is overloaded Installer Setup ISU Mode To enter Installer Setup Mode Press and hold both the System button labeled Heat Cool and the Up Arrow button f...

Страница 11: ...n Auxiliary Heat is on 3 Valve Output Type 0 Valve energized on call for heat or cool Default 1 Valve de energized on call for heat or cool 4 Space Sensor Type 0 Onboard Sensor Default 1 Remote Sensor TR21 or other 20K Ohm sensor 5 Pipe Sensor Only displays when value 3 or 6 for the System Type in ISU code 2 is selected 0 Contact Open Cool mode Contact Closed Heat mode Pipe sensor will flash on di...

Страница 12: ...ingle Setpoint 2 to 6 Range is 2 to 6 Default is 3 Heat switching point setpoint switching differential Cool switching point setpoint switching differential Available when Single Setpoint is chosen for the control method for 4 pipe Auto ISU 10 11 CPH Value for Heat 1 to 12 Range is 1 to 12 Default is 4 The number selected indicates the maximum times Heating is cycled on per hour CPH ISU 2 selectio...

Страница 13: ...ing from Occupied to UnOccupied 5 Button Press Default Press and hold Heat Cool Off button for 3 seconds and thermostat will go into Economy Setback 20 Remote Setback for Heating 50 to 70 Range is 50 F to 70 F Default is 64 F Used when the thermostat is in the Unoccupied state 21 Remote Setback for Cooling 72 to 90 Range is 72 F to 90 F Default is 79 F 22 Activity Sensing 0 Disabled Default This w...

Страница 14: ...on the remote setback input from an occupancy sensor time switch or hotel card key The thermostat controls to the user installer defined setback setpoints for increased energy savings The LCD displays Economy Setback just to the right of the main temperature display to indicate the Remote Setback mode is active When Remote Setback is active all buttons on the thermostat are disabled However the bu...

Страница 15: ...er will occur when the pipe temperature goes above the threshold for heating or below the threshold for cooling If a purge has not occurred or a call has not been satisfied in awhile the pipe temperature may start to get close to the ambient temperature In this case the thermostat will only changeover once the temperature falls into the opposite threshold 2 Pipes with Auto Changeover For this appl...

Страница 16: ...te purge will occur when it is switched back into Heat or Cool 4 PIPES AUTO CHANGEOVER Single Set Point Method In 4 pipe auto changeover with a single setpoint the temperature is always controlled to the setpoint Switching points are used to determine when to switch between heating and cooling modes If the current mode is heat and the temperature drifts above the cool switch point Setpoint Switchi...

Страница 17: ...ooling equipment Verify operation of equipment in Installer Test mode Heat does not turn on Heat On is solid in the display Heating equipment failure For TB6575A B 1 Check for 120 240 Vac at the equipment between power and common terminals L and N 2 Check for 120 240 Vac between the heat W and common N terminals If 120 240 Vac is present the thermostat is functional For TB8575A 1 Check for 24 Vac ...

Страница 18: ...ed heating and or cooling equipment Heating equipment does not turn off and heat temperature setting is set below room temperature Heat On is not in the display Incorrect System Type configured Check that the Installer Setup code 2 System Type value matches the installed heating and or cooling equipment Cannot set the system setting to Heat System Type Installer Setup code 2 is set to Cool Only va...

Страница 19: ... Freeze protection is not activated when system type is Cool ISU code 2 value 1 Change System Type System mode is not Off Set the System mode button to Off Auto Fan Reset does not activate Incorrect ISU code Set the Installer Setup code 24 to Enabled value 1 or 2 Calling for Heat Cool setpoint couldn t be satisfied Only after the setpoint is satisfied will the auto fan reset timer activate Table 8...

Страница 20: ... Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 62 0311 05 M S Rev 10 10 Printed in U S A ...

Отзывы: