Honeywell SS4-AI Скачать руководство пользователя страница 5

 

OPERATOR MANUAL //  

SECTION 1: FAMILIARIZAT ION 

 

HONEYWELL 

 
SECTION 1: FAMILIARIZATION  

1.1 

Introduction 

The 

M odel SS4-AI Infrared Flame Detectors 

can be used in the FS2000 

Fire Early Warning System or in the Stand-Alone mode.  This model is 
housed in an Explosion-Proof enclosure and incorporates built in optical 
testing of both the Detectors and lens. 

The Detector maximum alarm range is 45 feet for a one square foot 
gasoline with a 120 degree circular field of view.  This Detector design 
features dynamic signal processing that utilizes infrared band and visible 
band sensor elements.  

For Special Applications Only – Consult 

Factory.

 

The only difference between a FS2000 System Model SS4-AI 
Detector and a Stand-Alone SS4-AI Detector is how each is wired 
and the use of the fault relay.  However, there are operational 
advantages when the Model SS4-AI Detector is connected to a 
FS2000 Controller and FireBus. 

The Model SS4-AI Detector also has the flexibility to be re-configured in 
the field.  It is simple to install and operate because its built in self-testing 
does most of the work.  The only real maintenance is to wipe the Detector 
window lens clean and perform any periodic testing required by the 
manufacturer of the Fire Control and Suppression System. 

1.2 

Stand-Alone Operation 

For Stand-Alone operation, the Model SS4-AI Detector may be connected 
to a FM/UL Approved Fire/Security Panel.  The Model SS4-AI Detector 
operates on 24 volts DC.  The Model SS4-AI Detector, when operated in 
the Stand-Alone mode, uses its Fire, Fault, and Verify (optional) relays to 
interface to FM/UL Approved Fire /Security Panels.  For Stand-Alone 
operation, the Model SS4-AI's Fault relay is 

automatically

 configured by 

its on-board microcomputer.  The input current of the Model SS4-AI 
Detector increases about 15 milliamps in the Stand-Alone mode compared 
to with connected to theFS2000 System.  The Fault relay is not available 
for use when the Model SS4-AI Detector is wired to the FS2000 System. 

1.3 

FS2000 System Operation 

For FS2000 System operation, the Model SS4-AI Fire and Fault signals are 
sent digitally to the FS2000 System Controller using the four wire FS2000 
FireBus.  The FireBus provides the 24 volts DC power for the Model SS4-
AI Detector and RS-485 digital communication (Refer to Honeywell 
Analytics document MN0003 entitled "FS2000 FIRE EARLY WARNING 
SYSTEM - INSTALLATION and OPERATIONS GUIDE").  For special 
remote alarm applications, users may connect directly to the Model SS4-
AI's Fire four pin relay connector.  (Note:  When the Model SS4-AI Detector 
is connected to the FS2000 System using FireBus communication, the 
Controller 

automatically

 disables the Model SS4-AI's Fault relay.) 

Содержание SS4-AI

Страница 1: ...Installation Guide and Operating Manual Infrared IR Digital Electro Optical Fire Detector Model SS4 AI For Special Applications Only Consult Factory Stand Alone Mode ...

Страница 2: ...ptical Path Integrity CM1 CM1 A DartLogic FireLogic Fire Signature Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Fire Sentry Corporation Fire Sentry Corp FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5X FS6 FS6X FS7 FS7X FS8 FS8X FS9 FS9X FS10X FS10X FS11 FS11X FS12 FS12X FS14 FS14X FS15 FS15X FS16 FS16X FS17 FS17X FS18 FS18X FS19 F...

Страница 3: ...this bookset REFERENCE INTERNAL Identifies an additional source of information within this bookset Indicates a situation which if not avoided may result in equipment or work data on the system being damaged or lost or may result in the inability to properly operate the process CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may als...

Страница 4: ... 1 1 Installation Precautions 8 2 1 2 Conduit Installation 8 2 1 3 Wiring Recommendations 9 2 1 4 Power Supply Considerations 9 2 2 Enclosure Installation 10 2 4 Configuring and Wiring Detectors 11 SECTION 3 MAINTENANCE AND TROUBLESHOOTING 14 3 1 Personnel 14 3 2 Cleaning Windowed Enclosures and Detectors 14 3 3 Model SS4 AI Detector Faults 15 3 3 1 Detector Faults 15 3 4 Model SS4 AI Detector Mod...

Страница 5: ...d Suppression System 1 2 Stand Alone Operation For Stand Alone operation the Model SS4 AI Detector may be connected to a FM UL Approved Fire Security Panel The Model SS4 AI Detector operates on 24 volts DC The Model SS4 AI Detector when operated in the Stand Alone mode uses its Fire Fault and Verify optional relays to interface to FM UL Approved Fire Security Panels For Stand Alone operation the M...

Страница 6: ...immediately and the second LED will rapidly blink for several seconds indicating that the Detector s FirePic is being permanently stored in the Detector s solid state memory FirePic is the several seconds of Detector data that preceded an alarm event Once the FirePic data is stored the second LED will remain on 1 4 2 Detection Range The detection range of the detector is field adjustable between 1...

Страница 7: ...elay may be set in a Latching or Non Latching mode If Latching mode is set the Fire or Verify Relay will remain energized until the Detector is reset Powered down and up When Non latching mode is set the Fire Relay will reset after 10 seconds Unless the Verify Relay is enabled with a Verify Time then the Fire Relay will remain energized until the Verify Relay is energized or until the end of the v...

Страница 8: ...ally all internal electronic systems The Model SS4 AI Detectors and the system they are connected to should be periodically manually tested to insure proper function of the entire Fire Protection System To test the Model SS4 AI Detectors manually where open fires are might be a safety hazard for both optical path and window cleanliness use a Honeywell Analytics Model FT 2145 Test Lamp ...

Страница 9: ...nual for your Fire Control Panel 2 1 1 Installation Precautions The following precautions should be observed during installation of Model SS4 AI Detectors 1 Double check to make sure that the external electrical power is turned OFF before connecting to the Model SS4 AI Detector 2 Do not handle the Model SS4 AI Detector s module with its printed circuit boards without being adequately grounded Prin...

Страница 10: ...s are necessary solder all splices The use of good wiring practices will greatly improve the ease of installation improve reliability and allow easier servicing 2 1 4 Power Supply Considerations The Model SS4 AI Detector uses 24 volts DC at a maximum current of 75 milliamps Make sure that the Panel s power supply can handle the current load of the total number of Model SS4 AI Detectors connected t...

Страница 11: ... bracket is mounted with the correct orientation The outside contours of the mounting ears on the Detector enclosure and the ends of the bracket will match The large diameter of the threaded insert must be facing the enclosure d Screw the enclosure bracket assembly on to the ball stud Turn the Detector until the stud bottoms against the enclosure Do not tighten While holding the enclosure tighten ...

Страница 12: ...Windowed Enclosures and Detectors Observe static protection safeguards while handling Model SS4 AI Detector modules Properly wear a wrist strap connected to earth ground 1 REMOVE THE DETECTOR MODULE FROM ITS ENCLOSURE a With electrical power off loosen the Allen head screw at the base of the metal enclosure top windowed cover Double check that electrical power is off by seeing that the Detector s ...

Страница 13: ...Insert the cables into the metal enclosure base through one of the conduit openings Figure 5 Model SS4 AI Detector Wiring Bottom View of SS4 AI Detector Module b Then connect the 24 volt DC Power Supply wires into the J1 or J2 connector and firmly tighten down the two slotted screws with a small screwdriver DO NOT CONNECT ANY WIRES TO Pin 2 or Pin 3 Do NOT over tighten or the screws may strip or b...

Страница 14: ...d If the Fire Verify option is used connect the Verify Fire Alarm wires to the four pin WECO terminal J6 Install the wires into J6 Pins 1 and 2 for Normally Open relays and firmly tighten down the slotted screws with a small screwdriver Refer to Figure 4 Model SS4 AI Detector Wiring for more details on relay connections 5 REPLACE THE DETECTOR MODULE INTO THE ENCLOSURE a Gently install the module b...

Страница 15: ...closures and Detectors The optical windows on the Model SS4 AI Detector should be cleaned periodically on a regular maintenance schedule For clean applications this may be every month However for extremely dirty applications such as a truck filling station where black carboneous smoke can cover a nearby Detector a cleaning schedule of every day may be necessary Clean the windows on the Model SS4 A...

Страница 16: ...heck voltage at the power connector J1 or J2 Pins 1 and 4 If no or very low voltage is measured check wiring and power supply e Detector Fault The Detector will Fault if any one of its Detectors fails the automatic built in test One LED is on until the fault is corrected Begin by thoroughly cleaning the Lens both inside and outside also clean the exposed surface of the Detector elements and the pr...

Страница 17: ...ires to the new module Make sure the module is correctly aligned Gently re install back over the three metal standoffs Next re install the three chrome plated screws Be careful not to touch the Detector elements If they are accidentally touched clean as instructed in Section 3 2 Cleaning Windowed Enclosures and Detectors 7 Screw down the metal enclosure top windowed cover until it is secure and ti...

Страница 18: ...ETECTOR POWER OUT PIN 1 DC Return or Ground 2 NOT USED Do not connect this Pin 3 NOT USED Do not connect this Pin 4 Power 24 Volts DC J4 FIRE RELAY PIN 1 Fire Relay Common 2 Fire Relay Normally Closed 3 Fire Relay Common 4 Fire Relay Normally Open J5 FAULT RELAY Energized PIN 1 Fault Relay Normally Open 2 Fault Relay Common 3 Fault Relay Normally Closed 4 Fault Relay Common J6 FIRE VERIFY RELAY PI...

Страница 19: ...CH 4 DESCRIPTION open Non Latching mode If Verify is enabled then the Verify Relay will de energize approximately 10 seconds after it energizes If Verify is disabled then the Fire Relay s will de energize approximately 10 seconds after it energizes closed Latching mode If Verify is enabled then when the Verify Relay energizes it will remain energized until the detector is reset If Verify is disabl...

Страница 20: ...Self Checking 15 E ESD 8 F FireBus 4 FireBus Wiring 9 Flame Detector See Detector 5 G Grounding 8 I Infrared IR Band 5 Installation 8 Conduit 8 Detector 11 Enclosure 10 Precautions 8 Static Damage 8 J Junction Box 8 9 L Layout Planning 8 M Maintenance 14 P Personnel Qualified 14 Power 9 R Relay Fault 17 Fire 17 Removing Modules 11 S Spectral Bands 5 Stand Alone 4 Static Damage 8 Swivel Mount 10 T ...

Страница 21: ...enience commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such product to the full extent such may be disclaimed by law THIS WARRANTY DOES NOT COVER 1 Defects or damage resulting from use of the Product s in other than its normal and customary manner 2 Defects or damage from misuse accident ...

Страница 22: ...lon Science Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Email analytics ap honeywell com Internet These Honeywell websites may be of interest to Industry Solution customers Honeywell Organization URL Corporate www honeywell com Honeywell Analytics www honeywellanalytics com Telephone Contact us by telephone at these numbers Organization Phone Number Americas Honeywell Analytics Inc 1...

Страница 23: ...1998M0915 Rev A 072014 2014 Honeywell International Inc ...

Отзывы: