OPERATOR MANUAL // SECTION 3: MAINTENANCE AND
TROUBLESHOOTING
HONEYWELL
16
1.
With electrical power off, loosen the Allen-head screw at the base
of the metal enclosure top windowed cover. (Double-check and see
that the Detector's LED's do
NOT
blink for at least 10 seconds.)
2.
Unscrew the top windowed cover and set aside with its "O" ring.
Keep both clean.
3.
Loosen, then remove the three slot headed screws located on the
top circuit board. (Some models use captive screws that should not
be removed from the circuit board).
4.
Gently lift out the module, sliding it along the three metal standoffs.
5.
Disconnect all of the wires from the female jacks located on the
bottom of the module. Be sure to note the connection location of
each wire.
6.
Install another module. Reconnect the wires to the new module.
Make sure the module is correctly aligned. Gently re-install back
over the three metal standoffs. Next, re-install the three chrome-
plated screws.
Be careful not to touch the Detector elements
. If
they are accidentally touched, clean as instructed in Section 3.2,
Cleaning Windowed Enclosures and Detectors.
7.
Screw down the metal enclosure top windowed cover until it is
secure and tighten the Allen-head "tamper-proof" screw.
3.5
Detector Repair
Return the defective module to the factory for repair service.
There are NO user serviceable parts in a Detector Module.
If the Model SS4-AI Module must be shipped back to the factory for repair,
it
M UST
be packed in static protected material. If this material is not
available, carefully wrap the Module in aluminum foil. An RMA (Return
Material Authorization) is required for all returns to the factory. Contact
Customer Service or your Distributor for an RMA number before shipping a
unit back to the factory.