e) Supervisory Main: 

192.168.0.1 

(note this is the primary receiver’s IP address 

assigned by central station) 
 
f) Supervisory Backup: 

192.168.0.2 

(note this is the secondary receiver’s IP 

address assigned by central station.) 
 
g) Maintenance:  This is a third IP receiver setting that is not normally used.  A 
third maintenance receiver can be installed at a remote site and used to obtain 
trouble signals such as at a maintenance facility or dealer location. 
h) Port: (80 is the default but the central station may assign a different one) 
 

DO NOT REGISTER the IPDACT at this point. PROCEED to the next 
step - RESET. 

 

 

 

 

j)  (Select item “j” Reset).   At this point the IPDACT will reset and prompt for the 

default password.  This step fixes the programming you entered into the flash 
memory of the IPDACT. 

  Enter password 24680 and press the enter key. 

  Enter password 24680 when prompted again. You should see 

“PASSWORD ACCEPTED” 

 

  At the menu options screen, once again select "

c: Quick Install

 

 

 

i) 

(Select i) Register MIP 

  When prompted for password Use the different installation password 

assigned by Central such as:

 1111

 you should see “OK” in the display if 

successful

.  

Check that LED "LD6" is illuminated - this indicates proper 

communication/registration with the CS receiver. 

 

Note:

 If you do not see 

OK

, it could be that the Account Number has already 

been registered with the receiver by another IPDACT.  If you see the 
message 

VA unreachable

, recheck all the given parameters and be sure 

to use the different installation password assigned by the Central Station, 
NOT the default of 24680!

 

 

z) Select z) to exit submenu 
 
Select z again to exit to main menu 
 
Close HyperTerminal 
 
Disconnect your serial cable from the PC and the IPDACT. 
Ensure the FACP is programmed for DACT communications as if you were using 
standard phone line connections with the following information.  Remember the 

Содержание Smoke Alarm

Страница 1: ...l equipped with on board or optional DACT Requires 300mA aux non reset able power from FACP Includes cable from panel primary telco port to IPDACT IPBRKT Bracket for mounting IPDACT inside MS 9200UDLS common enclosure or in optional HPP 300ULX power supply IPSPLT Splitter for dual phone lines to IPDACT input cable ALMSC119 RJ45 DB9F PC serial port programming cable for IPDACT IPENC Optional cabine...

Страница 2: ...d required to execute the register command 3 If STATIC IP is to be used such as in an enterprise or corporation Obtain IP address subnet mask and gateway for IPDACT from enterprise IT manager Default IP is 192 168 0 100 with subnet of 255 255 255 0 4 IPDACT account number or client number 5 IP addresses and of the Primary and Secondary VisorALARM central station receivers 6 UDP Port number to use ...

Страница 3: ... the IPBRKT Note discard any double sided tape plastic standoffs that may be included with the IPDACT and use the supplied machine screw versions 3 Connect 24 VDC from the non resettable power output of the control panel to the IPDACT terminals marked GND and 12 24VDC Be careful to observe correct polarity Run the two conductor power supply wire through the small ferrite ring supplied with the IPD...

Страница 4: ...n the FACP is not used for a backup via POTS line the IPSPLT can be obtained and used to combine both phone lines In this case the cable supplied with the IPDACT connects to the single connector on the IPSPLT See Panel Manual Connect serial cable here CN1 6 Plug one end of the IPDACT Programming Cable PN ALSMSC120 shown above or equivalent into the black RJ45 receptacle on the IPDACT labeled CN1 P...

Страница 5: ...ory mounted IPBRKT inside the IPENC using the 4 supplied X 6 32 machine screws as shown below The four black screws will be used to secure the enclosure door following IPDACT wiring connections For complete information of all installation options follow the wiring instructions found in the included Product Installation Document Mount the IPENC next to the FACP as shown in the drawing below Mountin...

Страница 6: ...ing holes in the HP300ULXbackbox Use the landmarks illustrated in the figure below to locate the correct mounting location 2 Secure the IPBRKT bracket to the back box by installing the supplied screws into the top left hole and bottom right slot of the IPBRKT as illustrated and tighten 3 Secure IPDACT Module to IPBRKT bracket using the four supplied standoffs as illustrated in the figure below 4 W...

Страница 7: ...lack serial cable PN ALMSC119 described above is needed between a PC COM port and CN1 on the IPDACT Returning the IPDACT to factory default settings Note While not a required step it is always good practice to insure any programmable device be set to its default factory settings To return the IPDACT to factory default settings follow the procedure below 1 Remove power to IPDACT 2 Short jumper P2 o...

Страница 8: ...5 19 2008 8 of 15 Set Connect using to COM1 then OK Note if using a USB Serial converter select the COM port assigned to the converter ...

Страница 9: ...s to Bits per second 9600 Data bits 8 Parity none Stop bits 1 Flow control none very important Click OK Press Enter and the word password should appear as shown below Key in default IPDACT password 24680 as shown above then press Enter ...

Страница 10: ...5 19 2008 10 of 15 At the menu options screen shown below select C Quick Install ...

Страница 11: ...static IP is to be assigned select b and key in the assigned number similar to the following example 192 168 0 x where x is unique for each IPDACT Press enter and the unit will present msk Enter the subnet mask such as 255 255 255 0 Note that this IP address and subnet will be obtained from the IT manager for the site c Gateway IP 192 168 0 1 When static IP s are provided this is the router addres...

Страница 12: ... enter key Enter password 24680 when prompted again You should see PASSWORD ACCEPTED At the menu options screen once again select c Quick Install i Select i Register MIP When prompted for password Use the different installation password assigned by Central such as 1111 you should see OK in the display if successful Check that LED LD6 is illuminated this indicates proper communication registration ...

Страница 13: ... panel dials out the backup phone line Confirm that the central station received the communication lost signals DHCP Theory of Operation The following information is not required for configuration but is included for further understanding of DHCP DHCP is used in private networks to auto configure not only the IP addresses and masks of the network hosts PC s IPDACT s etc but also their default gate...

Страница 14: ...onse o If there is no DHCP server the IPDACT uses the IP address mask and gateway that are manually fixed by the IPDACT user or in their absence the default ones IP address 192 168 0 100 mask 255 255 255 0 Def GW 192 168 0 200 If you set the DHCP to OFF the IPDACT will never request the IP settings no matter if there is a DHCP server in the network or not so it will use the manually fixed ones or ...

Страница 15: ...rough DHCP the fixed ones entered in c Quick Install are displayed and actually used If on the other hand the IP Settings were dynamically obtained from a DHCP server these parameters will be displayed together with other DHCP parameters remaining lease time remaining time until the next DHCP request is sent and the DHCP server IP address ...

Отзывы: