R8001C6001
Configuration
Min
Optimum Range for Performance Max
Thermocouple J -50°C
1025°C ± 4 °C
K -50°C
1000°C ± 4 °C
RTD
-135°C
250°C
± 2 °C
NTC
25°C
125°C
± 1°C
Current Out
4 mA
20 mA
± .05 mA
Voltage: In / Out
2 V
10 V
0.3 %,
typical
Table 7. Suggested Sensor Selection Based on Application.
Application
Recommended Wire
Size
Recommended
Part Numbers
Communication
Lines
22 AWG two-wire
twisted pair with ground,
or five-wire.
Belden 8723
shielded cable or
equivalent.
Other terminals
18 AWG wire insulated
for voltages and
temperatures for given
application.
TTW60C,
THW75C,
THHN90C
Table 8. Recommended Wire Sizes and Part Numbers.
Resistance to Temperature Conversion Tables
Below are the lookup tables for various types of SLATE sensors.
Linear interpolation is used for values that are between the points
that are shown.
10K NTC
Ohms
Degrees C
100.000
228.199
120.000
214.979
144.000
202.439
172.800
190.526
207.360
179.195
248.832
168.404