background image

Silver Series LightSpot with photocell 

The Silver Series LightSpot is a high performance presence detector with photocell.  In all operating modes, the 
photocell can hold lights off as a vacant area becomes occupied, and if the light level falls too low during the 
period of occupancy, the lights switch on.  In ‘Passive Mode’ the lights do not switch off whilst the area is occupied 
no matter how much light is measured.  In ‘Active Mode’ the photocell is able to switch the lights off whilst the area 
is occupied.

Fixing

MS1201PSM / MS1221PSM  - The housing may be secured to a hard surface or a BESA box.  The unit fits into 
the housing with a simple bayonet action.
MS1201PF / MS1221PF  - Supplied with a sinking (dry lining) box for flush fitting.  Sinking box fits into an 89mm 
diameter hole in ceiling tile or plasterboard ceiling.   To avoid damage to ceiling tile, do not overtighten.   Depth 
required behind ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable.  No 
access above the ceiling is necessary.

Note: 

 Do not mount within 25cm of a luminaire.

Connection Examples

Important Additional Notes

1.

Only suitably qualified personnel should install this equipment.

2.

All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box 
for looping cables. 

3.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

4.

This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 
some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in 
order to achieve a predicted lamp life.   Please check with the manufacturer of the luminaires to ensure that they are 
compatible with automatic controls in this respect. 

Multiple Units 

Larger areas can be covered by connecting extra units in parallel.  The total load current must not exceed 6 Amps 
in case only one unit is activated.  

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

VOLT-
FREE 
OUTPUT

LIVE IN

LIVE IN

LIVE IN

NEUTRAL

NEUTRAL

EARTH

EARTH

LOAD

(Max 6 Amps)

LIVE IN

*
*

*
*

*

 The Live terminals are internally linked

External Link

External Link

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE IN

LIVE IN

NEUTRAL

EARTH

MS1201PF or MS1201PSM 

LOAD

(Max 6 Amps)

The MS1221 has two outputs, one influenced by the 
photocell (R1), the other not (R2). This is useful in 
applications where a fan or water is being controlled in 
addition to any lighting. 

*
*

External Link

*

 The Live terminals are internally linked

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE OUT

LIVE IN

NEUTRAL

EARTH

LOAD 2

(Max  6 Amps)

NOT INFLUENCED 

BY PHOTOCELL

LOAD 1

(Max  6 Amps)
INFLUENCED 

BY PHOTOCELL

R2

R2

R1

TOTAL LOAD 

NOT

TO EXCEED 10A

R1

R1

EXAMPLE SHOWS

2 x MS1201P

R1

R1

R1

R1

MS1221PF or MS1221PSM 

Содержание Silver Series

Страница 1: ...nicalsales ex or honeywell com www ex or com At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with normal household waste Do not burn by Honeywell Note Infrared Programmer required for commissioning HP2000 HP10 or HP18 for MS1201PF SM HP2000 or HP10 for MS1221PF SM Please note that only the HP2000 offers the full rang...

Страница 2: ... 3 Ameans for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations 4 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of some lighting types e g 2D luminaires may specify a maximum number of switching cycles and or a minimum on time in order to achieve a predicted lamp life Please che...

Страница 3: ...ed load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the light level falls below the lower set point however the load switches off only if the light level exceeds the upper threshold continuousl...

Страница 4: ...own momentarily on the HP2000 screen following the Download this is a useful mechanism for troubleshooting Washroom Mode The unit may be used in conjunction with a 230V solenoid valve and a trickle valve or petcock to effect a urinal flush system Set the water flow rate by adjusting the petcock so that the cistern just fills within the chosen Off Delay period of the detector Note that in this mode...

Отзывы: