SK-460-006 

I56-3437-002

TABLE 1: ShORT CIRCUIT PROTECTION - UL 864 9Th EDITION REqUIREMENTS

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with requirements in the Standard for Control 

Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used 

at all as indicated below.

Program Feature or Option

Permitted in  

UL 864 (Y/N)

Possible Settings

Settings Permitted in UL 864

Disabling short circuit protection 

when a single power supply is 

shared by multiple NACs

No

Enable or Disable short 

circuit protection

Enable short circuit protection when a single power sup-

ply is shared by multiple NACs.  Short circuit protection 

can be disabled only when a power supply is not shared by 

multiple NACs.

COMPATIBILITY REqUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Silent Knight system control panel.

COMPONENTS

The following is a description of the SK-Control-6 mounting framework:

One or two SK-Control-6 modules can be installed in a IDP-ACB cabinet.

• 

The IDP-ACB cabinet has a built-in chassis that will accommodate one or two 
SK-Control-6 modules.

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABLE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

BASE 

ADDRESS

ADDRESS

DISABLE

10

11

12

13

14

15

The front SK-Control-6 module positions of each chassis are offset below the 
rear SK-Control-6 module positions so that all of the status indicators are vis-
ible. For cabinet dimensions refer to the IDP-ACB instruction manual.

INSTALLATION STEPS

1.  Cabinet Mounting

 

 In a clean, dry area, mount the backbox using the four holes provided in the 
back surface of the cabinet (Figure 3).

FIGURE 1: IDP-ACB CABINET

FIGURE 2: TYPICAL MOUNTING hOLE LOCATIONS

BACKBOX
MOUNTING
HOLES

C0235-00

C0234-03

2.  Module Installation
 

 There are two methods for installing a module in the rear position of a 
chassis. Method one is for installation of a rear module only, when no 
module will be installed in front of it. Refer to Figure 3 for instructions. 
Method two is for installation of a rear module when another module 
will be installed in the chassis position in front of it. Refer to Figures 4a 
and 4b for method two. All necessary screws and standoffs are supplied 
with the modules.

2

3

1

Step 1: 

 Insert the bottom of the SK-Control-6 module down into a rear slot 
on the chassis. 

Step 2: 

 Carefully swing the upper edge of the board back towards the back 
of the chassis until it  touches the two standoffs.

Step 3: 

Align two 4-40 screws with the two standoffs and tighten.

Step 4: 

 Address and wire the modules according to the instructions in this 
manual.

The  steps  in  Figures  4a  and  4b  describe  and  illustrate  module  installation 
when the rear chassis position and the position in front of it will be filled. 
Front position installation is possible only if the rear position is filled with a 
module.

C0237-00

FIGURE 3: INSTALLATION OF REAR MODULE ONLY, METhOD ONE

1

C0225-00

FIGURE 4A: INSTALLATION OF SK-CONTROL-6 MODULE IN A REAR 
ChASSIS POSITION, METhOD TwO

firealarmresources.com

Содержание SILENT KNIGHT SK-Control-6

Страница 1: ... common SLC input is used for all modules Each module has its own address A pair of rotary code switches is used to set the address of the first module from 01 to 154 The remaining modules are automatically assigned to the next five higher addresses Provisions are included for disabling a maximum of three unused modules to release the addresses to be used elsewhere Each module also has panel contr...

Страница 2: ... each chassis are offset below the rear SK Control 6 module positions so that all of the status indicators are vis ible For cabinet dimensions refer to the IDP ACB instruction manual INSTALLATION STEPS 1 Cabinet Mounting In a clean dry area mount the backbox using the four holes provided in the back surface of the cabinet Figure 3 Figure 1 IDP ACB Cabinet Figure 2 Typical mounting hole locations B...

Страница 3: ...l be enabled The SK Control 6 must have power cycled for shunt changes to take effect 5 There is an active short circuit protection option for each address The board is shipped with this option disabled for each address represented by six large shunts on the Disable Short Circuit Protection area To C0226 00 Figure 4b Installation of SK Control 6 module in front chassis position enable short circui...

Страница 4: ...AL POWER SUPPLY TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 EOLR 1 RED VIO VIO RED BLK BLK 47K TABLE 4 JUMPER LOCATION NAC PAIR SHARING SUPPLY T11 0 and 1 T12 1 and 2 T13 2 and 3 T14 3 and 4 T15 4 and 5 NOTE Jumpers must be placed on T11 T13 and T15 for all Class A Style Z ...

Страница 5: ...12 13 14 15 C0177 04 Figure 8 Example of Class A Style Z NAC configuration with a single supply dedicated to a single NAC BASE ADDRESS STATUS INDICATORS NAC PS NAC PS NAC PS NAC PS NAC TOP BOT NAC PS SLC PS 1 2 3 4 5 T11 T10 T0 0 T12 T1 T2 T3 T4 T5 T13 T14 T15 T16 ENABLE POWER SUPPLY MONITOR DISABLE SHORT CIRCUIT PROTECTION A B SELECT DISABLE 1 DISABLE 2 DISABLE 3 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3...

Страница 6: ...ese limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installa tion I...

Отзывы: