INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3437-00
2
SK-Control-6
Six Circuit Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2.25 mA
Alarm Current:
35 mA (assumes all six relays have been switched and all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)–10°C to 55°C
Humidity:
10 to 85% Non-condensing
Dimensions:
6.8˝ H x 5.8˝ W x 1.25˝ D
Accessories:
IDP-ACB Cabinet and chassis
Wire Gauge:
12-18 AWG
Max. NAC Circuit
Line Loss:
4 VDC
Power Rating Per Circuit:
63 W @ 70.7 VAC; 50 W @ 25 VAC
Max. NAC Current Ratings:
For class B wiring systems, 3A
For class A wiring systems, 2A
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE:
This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Control-6 Six Circuit Supervised Control Module is intended for use
in an intelligent alarm system. Each module is intended for switching ap-
plications involving AC, or DC which require wiring supervision. A common
SLC input is used for all modules. Each module has its own address. A pair
of rotary code switches is used to set the address of the first module from 01
to 154. The remaining modules are automatically assigned to the next five
higher addresses. Provisions are included for disabling a maximum of three
unused modules to release the addresses to be used elsewhere. Each module
also has panel controlled green LED indicators. The panel can cause the LEDs
to blink, latch on, or latch off. In order to synchronize strobes, horn/strobes,
and speaker/strobes, a SYNC-1 accessory card (sold separately) must be used
with the SK-Control-6. See the SYNC-1 installation manual for details on how
to install.
Each module has terminals for connection to an external supply circuit for
powering devices on its NAC. Each supply must be power limited and its volt-
age/current limits must be at or below those specified. There is a short circuit
protection monitor for each module. This is provided to protect the external
power supply against short circuit conditions on the NAC.
ShIPPED ON BOARD:
(1) Small shunt in A/B select position (Shipped in Class B position, remove
shunt for Class A)
(6) Large shunts on Enable Power Supply Monitors
(6) Large shunts on Disable Short Circuit Protection
(3) Large shunts on Sync Generator
INCLUDED:
(7) 1 x 4 Terminal Blocks (2) 1
1
/
4
˝ (32mm) (15) Large Shunts
Stand offs
(4) Machine Screws (5) Short Power
(2) Small Shunts
Suppy Jumpers
(2) Nuts
(6) 47k Ohm End
of Line Resistors
(2) EOL Relay Connector
Assmeblies
(1) Long Power Supply Jumper