Honeywell Silent Knight INTELLIKNIGHT 5600 Скачать руководство пользователя страница 64

Model 5600 Installation and Operation Manual

6-4

151450

Table 6-2: shows that any input SLC device with an address set within the range 1-15 will be 
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111 
or 112 will activate for an alarm in zone 1.

6.3.3

Default Mapping for the 2 built-in Notification 
Circuits.

There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to 
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the 
System Sensor synchronization pattern. To change the behavior of the default mapping of 
these circuits refer to Section 6.5.

Table 6-3: Output Points

OUTPUT POINTS

 Group

Output Point Type 

 

Qty

Start SLC 

ID

End SLC ID

Output Activates For

OPG 1

HFS-MR, HFS-MRA, SK-Relay

 

2

111

112

Zone 1 Alarm

OPG 2

HFS-MR, HFS-MRA, SK-Relay

 

2

113

114

Zone 2 Alarm

OPG 3

HFS-MR, HFS-MRA, SK-Relay

 

2

115

116

Zone 3 Alarm

OPG 4

HFS-MR, HFS-MRA, SK-Relay

 

2

117

118

Zone 4 Alarm

OPG 5

HFS-MR, HFS-MRA, SK-Relay

 

2

119

120

Zone 5 Alarm

OPG 6

HFS-MR, HFS-MRA, SK-Relay

 

2

121

122

Zone 1 Supervisory

OPG 7

HFS-MR, HFS-MRA, SK-Relay

 

2

123

124

Zone 2 Supervisory

OPG 8

HFS-MR, HFS-MRA, SK-Relay

 

2

125

126

Zone 3 Supervisory

OPG 9

HFS-MR, HFS-MRA, SK-Relay

 

2

127

128

Zone 4 Supervisory

OPG 10

HFS-MR, HFS-MRA, SK-Relay

 

2

129

130

Zone 5 Supervisory

OPG 11

HFS-MR, HFS-MRA, SK-Relay

 

2

131

132

Zone 1 Trouble

OPG 12

HFS-MR, HFS-MRA, SK-Relay

 

2

133

134

Zone 2 Trouble

OPG 13

HFS-MR, HFS-MRA, SK-Relay

 

2

135

136

Zone 3 Trouble

OPG 14

HFS-MR, HFS-MRA, SK-Relay

 

2

137

138

Zone 4 Trouble

OPG 15

HFS-MR, HFS-MRA, SK-Relay

 

2

139

140

Zone 5 Trouble

OPG 16

HFS-MR, HFS-MRA, SK-Relay

 

2

141

142

General Alarm

OPG 17

HFS-MR, HFS-MRA, SK-Relay

 2

143

144

General 

Supervisory

OPG 18

HFS-MR, HFS-MRA, SK-Relay

 2

145

146

General 

Zone 

Trouble

OPG 19

HFS-MR, HFS-MRA, SK-Relay

 2

147

148

General 

Trouble

OPG 20

HFS-MR, HFS-MRA, SK-Relay

 

2

149

150

Alarm Silenced

OPG 21

HFS-MR, HFS-MRA, SK-Relay

 

2

151

152

Trouble Silenced

OPG 22

HFS-MR, HFS-MRA, SK-Relay

 

2

153

154

AC Loss

OPG 23

HFS-MR, HFS-MRA, SK-Relay

 2

155

156

Resettable 

Aux 

Relay

OPG 24

HFS-MR, HFS-MRA, SK-Relay

 

2

157

158

Aux Door Holder

Содержание Silent Knight INTELLIKNIGHT 5600

Страница 1: ...Installation and Operations Manual INTELLIKNIGHT MODEL 5600 5600C 5600HV ECN 11 0214 Document 151450 06 06 2011 Rev E 151450 E Addressable Fire Control Panel ...

Страница 2: ......

Страница 3: ...and its peripherals be installed in an environment with a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indicating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to lightning induc...

Страница 4: ...ion may be out of service or temporarily disabled The most common cause of fire alarm malfunctions however is inadequate maintenance All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device System inspection and testing should be scheduled monthly or as required by National and or local fire codes Ade...

Страница 5: ...Requirements for Remote Station Protected Fire Alarm Systems 4 2 3 ULC Requirements 4 Section 3 Before You Begin Installing 1 3 1 What s in the Box 1 3 2 Environmental Specifications 1 3 3 Electrical Specifications 2 3 4 Wiring Specifications 3 3 5 Board Assembly Diagram 4 3 6 Calculating Current Draw and Standby Battery 5 3 6 1 Worksheet Requirements 5 3 6 1 1 Current Draw Worksheet for 5600 for ...

Страница 6: ...tion 18 4 9 2 1 Door Holder Power 18 4 9 2 2 Constant Power 19 4 9 2 3 Resettable Power 19 4 10 On Board Relays Conventional Power Limited 20 4 10 1 Common Trouble Relay 20 4 10 2 Programmable Relays 20 4 11 Remote Station Applications 21 4 11 1 City Box Connection Using the 5220 Module 21 4 11 2 NFPA 72 Polarity Reversal 23 4 11 2 1 Alarm Supervisory and Trouble Reverse Polarity Outputs 23 Sectio...

Страница 7: ... Each Zone 9 6 6 2 2 Zone Silenceable 9 6 6 2 3 Zone Type 9 6 6 3 Output Point Programming 9 6 6 4 Notification Appliance Circuit NAC Programming 10 6 6 4 1 Circuit Function 10 6 6 4 2 Conventional Notification Circuit Mapping 10 6 6 5 Relay Programming Options 11 6 6 5 1 General System Relay Silence Option 11 6 6 6 Dialer Phone Line Programming Options 11 6 6 6 1 Line Prefix 11 6 6 6 2 Dial Tone ...

Страница 8: ...es 7 7 22 Operation Mode Behavior 8 Section 8 Reporting 1 8 1 Receivers Compatible with the Control Panel 1 8 2 Reporting Formats Dialer Outputs 1 Section 9 Trouble Shooting and Quick Tips 1 9 1 Troubleshooting 1 9 1 1 JumpStart 1 9 1 2 View Active Points 1 9 1 3 Disable Or Re Enable A Zone 1 9 1 4 Silence the Board PZT 1 9 1 5 Silence the Notification Appliances 1 9 1 6 To Initiate a Fire Drill 2...

Страница 9: ...ntents 151450 Appendix A Compatible Devices 1 Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability Model 5600 5600C 5600HV Basic Operating Instructions ...

Страница 10: ...Model 5600 Installation Manual 6 151450 ...

Страница 11: ...ircuit is power limited per UL 864 and can source up to 2 0A Note Total output power for all three circuits must not exceed 2 0A Built in dual phone line digital alarm communicator transmitter DACT Reports events to central station by zone Two general purpose Form C programmable relays One Form C Trouble Relay 1 1 2 Software Features The 5600 is an addressable panel that operates like a 5 zone con...

Страница 12: ...ation appliances 1 4 How to Contact Silent Knight If you have a question or encounter a problem not covered in this manual contact Silent Knight Technical Support at 800 446 6444 To order parts contact Silent Knight Customer Service at 800 328 0103 or 203 484 7161 Term Description SLC Signaling Line Circuit Input Point An addressable sensing device such as a smoke or heat detector or a contact mon...

Страница 13: ...es developing on another level The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to alarm at various levels of smoke density If such density levels are not created by a developing fire at the location of detectors the detectors will not go into alarm Smoke detectors even when working properly have sensing limitations Detectors that have photo ele...

Страница 14: ...ry or permanent hearing loss Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service For added protection against telephone line failure backup radio transmission systems are recommended System components though designed to last many years can fail at any time As a precautionary measure it is recommended that smoke d...

Страница 15: ...re within the room could prevent the control from reporting a fire All fire alarm systems require notification devices including sirens bells horns and or strobes In residential applications each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels at least 15...

Страница 16: ...Model 5600 Installation and Operation Manual 1 6 151450 ...

Страница 17: ...his device cannot be adjusted or repaired in the field In case of trouble with the device notify the installing company or return to Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 3 If the 5600 causes harm to the telephone network the telephone company will notify the user in advance that temporary discontinuance of service may be required If advance notice is not practica...

Страница 18: ...pany For products approved after July 23 2002 the REN for this product is part of the product identifier that has the format US AC6AL05B 205600 The digits represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label e If this equipment 5600 causes harm to the telephone network the telephone company will notify you in advanc...

Страница 19: ...nstalling an individual device refer to the specific section of the manual for additional requirements The following subsections list specific requirements for each type of installation for example Central Station Fire Alarm systems Local Protected Fire Alarm systems and so on 1 All field wiring must be installed in accordance with NFPA 70 National Electric Code 2 Use ONLY the addressable smoke de...

Страница 20: ...entral station 3 The AC Loss Hours option must be set from 1 3 hours 2 2 3 Requirements for Local Protected Fire Alarm Systems At least one UL listed supervised notification appliance must be used 2 2 4 Requirements for Remote Station Protected Fire Alarm Systems 1 Do not exceed the current load restrictions shown in Section 3 6 2 The AC Loss Hours option must be set from 1 3 hours 2 3 ULC Require...

Страница 21: ...rtant to protect the 5600 control panel from water To prevent water damage the following conditions should be AVOIDED when installing the units Intended for indoor use in dry locations only Do not mount directly on exterior walls especially masonry walls condensation Do not mount directly on exterior walls below grade condensation Protect from plumbing leaks Protect from splash caused by sprinkler...

Страница 22: ...A 0Ω B SLC Out SLC Terminals 24 VDC 100 mA 0Ω NAC1 Notification Appliance Circuit 24 VDC 2 0 Amp 0Ω Auxiliary power 1 0 Amp NAC2 Notification Appliance Circuit 24 VDC 2 0 Amp 0Ω Auxiliary power 1 0 Amp TROUBLE NO Normally open relay contact 24 VDC 2 5 A resistive N A COM Common terminal NC Normally closed relay contact RELAY 1 NO Normally open relay contact 24 VDC 2 5 A resistive N A COM Common te...

Страница 23: ... shield to earth ground at the panel You must route high and low voltages separately Route the wiring around the inside perimeter of the cabinet It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits See Figure 3 1 for an example High frequency noise such as that produced by the inductive react...

Страница 24: ...which hold the control board in the cabinet slide out of slot from slide in standoff Then lift the control board off the location mounting pin and out of the cabinet Form C Trouble Relay On board Annunciator Battery Connector AC Power Input Form C Programmable Relays AC Power Input Battery Connector 24VDC Ethernet Programming Port Mounting screw Location Mounting Pin Mounting screws Slide In Stand...

Страница 25: ... 2 Add up the current draw for all auxiliary devices and record in the table at Line B 3 Add up all notification appliance loads and record in the table at Line C 4 For notification appliance circuits and auxiliary devices not mentioned in the manual refer to the device manual for the current ratings 5 Make sure that the total alarm current you calculated including current for the panel itself doe...

Страница 26: ...A mA mA HFS PT mA mA HFS D mA mA HFS T mA mA SK Photo mA mA SK Photo T mA mA SK DUCT mA mA SK Heat mA mA Addressable SLC Modules HFS MM 25 max detectors or modules in any combination Standby Alarm 0 375 mA mA mA SK Pull SA Standby Alarm 0 375 mA mA mA SK PULL DA Standby Alarm 0 375 mA mA mA HFS MR Standby Alarm 0 255mA mA mA SK Minimon Standby Alarm 0 375 mA mA mA SK Relay Standby Alarm 0 375 mA m...

Страница 27: ...s E and F Total standby AH AH H Alarm sounding period in hours For example 5 minutes 0833 hours H I Multiply lines E and H Total alarm AH AH J Add lines G and I 1 Total ampere hours required AH Table 3 2 Current Calculation Worksheet for SLC Devices Device of Devices Current per Device Standby Current Alarm Current ...

Страница 28: ...m 6 5 mA mA mA HFS PTA mA mA HFS DA mA mA HFS TA mA mA SK Photo mA mA SK Photo T mA mA SK DUCT mA mA SK Heat mA mA Addressable SLC Modules HFS MMA 25 max Standby Alarm 0 375 mA mA mA SK Pull SA Standby Alarm 0 375 mA mA mA SK PULL DA Standby Alarm 0 375 mA mA mA HFS MRA Standby Alarm 0 255mA mA mA SK Minimon Standby Alarm 0 375 mA mA mA SK Relay Standby Alarm 0 375 mA mA mA SK ISO 10 max Standby A...

Страница 29: ...ed H Alarm sounding period in hours For example 5 minutes 0833 hours H I Multiply lines E and H Total alarm AH AH J Add lines G and I 1 Total ampere hours required AH Table 3 3 Current Calculation Worksheet for SLC Devices for ULC Device of Devices Current per Device Standby Current Alarm Current ...

Страница 30: ...erating factor for the battery amp hour capacity Table 3 5 Maximum Battery Standby loads for ULC 24 Hour Standby Table 3 4 Maximum Battery Standby loads for 24 Hour Standby Rechargeable Battery Size 24 hr Standby 5 mins Alarm 24 hr Standby 15 min alarm 24 hr Standby 20 min alarm 7 AH 226 mA 213 mA 206 mA 12 AH 393 mA 379 mA 372 mA 18 AH 593 mA 579 mA 572 mA 24 AH 793 mA 779 mA 772 mA 33 AH 1 09 A ...

Страница 31: ...pected attach a piece of 3 4 inch plywood to the concrete surface and then attach the 5600 to the plywood Also mount any other desired components to the plywood DO NOT flush mount the 5600 cabinet 4 1 1 Preventing Water Damage Water damage to the fire system can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most like...

Страница 32: ...ng the Dead Front Follow these steps to properly install the dead front panel into the control panel cabinet 1 Remove the top two annunciator screws do not discard them they will be reused See Figure 4 1 for annunciator screw location 2 Set the dead front into the cabinet as shown in Figure 4 1 3 Reinsert the two annunciator screws as shown in Figure 4 1 Figure 4 1 Dead Front Installation and Remo...

Страница 33: ...move the dead front panel from the control panel cabinet 1 Remove the two annunciator screws do not discard them See Figure 4 1 2 Tilt the dead front forward to clear the top of the cabinet and left the dead front out of the cabinet See Figure 4 1 3 Reinsert the two annunciator screws See Figure 4 1 ...

Страница 34: ...in Figure 4 2 It may be necessary for a professional electrician to make this connection Connect black and white wires from transformer to 120V power Connect ground wire from 120V power to screw labeled G on the 5600 circuit board The AC power input is rated at 120 VAC 60 Hz 1 5A for 5600 and 230 VAC 50 60Hz 75A for 5600HV Figure 4 2 120 230 VAC Power Connection Ground To AC Supervised AC Connecti...

Страница 35: ...tion for Canadian Applications For Canadian applications an AC terminal block is supplied standard with the 5600C The AC terminal block is factory installed on the left of the circuit board chassis as shown in Figure 4 3 Figure 4 3 AC terminal Block Connections ...

Страница 36: ...eries is 3 1A 27 VDC Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating The following steps and diagram explain how to connect the batteries 1 Connect the black wire from the control panel negative battery terminal to the negative side of Battery 2 2 Connect the jumper wire provided P N 140694 from the positive side of Battery 2 to the nega...

Страница 37: ...net must be mounted onto 3 4 inch ply wood This is necessary because the weight of the batteries inside the accessory cabi net could cause the cabinet to pull away from the drywall When mounting on concrete especially when moisture is expected attach a piece of 3 4 inch plywood to the concrete surface and then attach the RBB cabinet to the ply wood If using the battery cable extenders provided P N...

Страница 38: ...o cabinets 4 Connect battery leads to the backup battery terminals See Figure 4 7 Observe the proper polarity to prevent damage to the batteries or the control panel 5 Insert the RBB cover screws into the cover mounting holes see Figure 4 7 Screw the cover screw 3 4 of the way into the cover mounting hole 6 Align the cover plate mounting keyhole over the cover mounting screws See Figure 4 8 Figure...

Страница 39: ...t draw Table 4 1 specifies the maximum distance the modules can be located from the panel on a single wire run The table insures 6 0 volts of line drop maximum In general the wire length is limited by resistance but for heavier wire gauges capacitance is the limiting factor These cases are marked in the chart with an asterisk Maximum length can never be more than 6 000 feet regardless of gauge use...

Страница 40: ...available options are 1852 feet maximum using 22 Gauge wire 4688 feet maximum using 18 Gauge wire 6000 feet maximum using 16 Gauge wire 6000 feet maximum using 14 Gauge wire Maximum Resistance Ohms 6 0 Volts Total Worst Case Current Draw amps Maximum Wire Length Feet 6000 feet maximum Maximum Resistance Ohms 500 Rpu where Rpu Ohms per 1000 feet for various wire gauges see table below Table 4 2 Typ...

Страница 41: ...Control Panel Installation 151450 4 11 4 4 2 Wiring Configurations Figure 4 9 illustrates Class B configuration Figure 4 9 SBUS Class B Wiring Supervised Power Limited 5635 ...

Страница 42: ...llowing steps 1 Make sure power is off at the panel 2 Mount the 5635 in the desired location see Section 4 5 1 3 Connect the 5635 to the panel see Section 4 6 4 Use the DIP switches on the back of the 5635 to assign an ID to the 5635 see Section 4 7 1 5 The new 5635 module must be added to the system through programming JumpStart will add the module automatically see Section 6 1 You can also add i...

Страница 43: ...osition 2 Push in the snap latch tab located on the right side while pulling the cover open 3 Pull wire through 7 8 hole in backplate and feed through wire channel to lower left cor ner of backplate before routing to terminal block 4 The cover must remain attached to the backplate while mounting the annunciator to the electrical box wall The cover cannot be reattached or removed after the annuncia...

Страница 44: ... Installation and Operation Manual 4 14 151450 4 6 Model 5635 Connection to the Panel Connect the 5635 to the panel as shown in Figure 4 12 Figure 4 12 Model 5635 Connection to the Panel Supervised Power Limited ...

Страница 45: ...CD display as the Station ID number 4 7 1 Assigning Module IDs When installing the 5635 you must use the DIP switches on the module to assign an ID to the module A maximum of 2 devices can be connected to the FACP SBUS communication circuit The SBUS device address needs to be set to 01or 02 Note Note that 00 is not a valid address Figure 4 13 shows the DIP switch positions and their correlation to...

Страница 46: ...4 16 151450 4 8 Telephone Connection Connect the telephone lines as shown in Figure 4 14 The Model 7860 phone cord is available from Silent Knight for this purpose Figure 4 14 Connection of Telephone Lines Use Minimum of 26 AWG Telephone Line cord ...

Страница 47: ...onal Notification Appliance Circuit The 5600 supports Class B Style Y configurations for notification appliance applications You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual Each circuit can source up to 2 0A total current for the system must not exceed 2 0A To install a Class B notification appliance circuit 1 Wire Class B Notification ...

Страница 48: ...rcuits 2 Configure the auxiliary power output through programming 4 9 2 1 Door Holder Power Door holder power is intended for fire door applications When there are no alarms in the system and the panel has AC power door holder circuits have 24 volt power present at their terminals Any alarm will cause power to disconnect Power will be re applied when the system is reset If AC power is off for more...

Страница 49: ...at Constant circuits 4 9 2 3 Resettable Power Resettable power is typically used to power beam detectors flame detectors and conventional 4 wire smoke detectors For circuits selected as Resettable 24 volt power is always present at the terminals unless a system reset occurs If a system reset occurs power is disconnected from the terminals for 30 seconds then re applied ...

Страница 50: ...ated at 2 5 A 24 VDC Resistive Note The N C contact is the relay contact that is closed when the panel has power and there are no alarm or trouble conditions 4 10 2 Programmable Relays The control panel has two Form C programmable relays built into terminals labeled RELAY 1 or RELAY 2 Each relay provides a normally open and a normally closed contact To configure one or two programmable relays foll...

Страница 51: ...unted for in control panel draw Alarm Current 1 Amp for 1 second Max Voltage 24 VDC The maximum coil and wire resistance combined must not exceed 30 ohms To install the 5220 for city box connection 1 Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of conduit must not exceed 20 feet in length 2 Wire the 5220 to the control panel as shown in Fi...

Страница 52: ...not possible to reset the remote indication until you clear the condition and reset the control panel Figure 4 17 City Box Connection Note NAC Circuit 2 Used as an Example Either NAC Circuit Can Be Used Supervised for Opens and Ground faults only Non Power Limited ...

Страница 53: ...4 11 2 1 Alarm Supervisory and Trouble Reverse Polarity Outputs Three HFS MR or SK Relay modules are required to independently report alarm supervisory and trouble SLC addresses 141 143 and 147 must be used as shown in Figure 4 18 Figure 4 18 Reverse Polarity output wiring ...

Страница 54: ...Model 5600 Installation and Operation Manual 4 24 151450 ...

Страница 55: ...me Description Install Sheet PN HFS P HFS PA SK Photo Photoelectric smoke detector I56 3483 00 I56 3426 00 HFS PT HFS PTA SK Photo T Photoelectric smoke detector with thermal 135 F HFS D HFS DA SK Duct Photoelectric duct smoke detector with extended air speed range I56 3488 00 I56 3432 00 HFS T HFS TA SK Heat Fixed temperature thermal detector 135 F I56 3485 00 I56 3429 00 SK Pull SA Addressable s...

Страница 56: ... can be untwisted unshielded solid or stranded as long as it meets the National Electric Code 760 121 requirements for power limited fire protective signaling cables Wire distances are computed using copper wire Maximum wiring resistance is 40 ohms to the farthest SLC device Maximum loop length depends on the wire gauge All SLC wiring is Supervised and Power limited Table 5 1 Maximum wiring distan...

Страница 57: ...SLC Device Installation 151450 5 3 The following figures show how length is determined for out and back tap and T Tap style wiring Figure 5 1 Calculating wire run length for a simple out and back ...

Страница 58: ...1450 When using T taps the total length of all taps and the main bus must not exceed 40 000 feet This requirement must be met in addition to the maximum distance requirements for the various wire gauges Figure 5 2 Calculating Wire Run Length for a T tap ...

Страница 59: ...pplies to the following HFS or SK models HFS P HFS PA SK Photo Photoelectric Smoke Detector HFS PT HFS PTA SK Photo T Photoelectric Smoke Detector with Thermal HFS D HFS DA SK Duct Photoelectric Duct Detector HFS T HFS TA SK Heat Fixed Temperature Detector To wire HFS or SK detectors 1 Wire device bases as shown in Figure 5 3 2 Set the address for each device as described in Section 5 5 Figure 5 3...

Страница 60: ... TENS rotary dial to set the tens place in a two digit number Example 1 To select device address 35 turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 5 4 Example 2 To select device address 105 turn the ONES rotary dial to 5 and the TENS rotary dial to 10 as show in Figure 5 4 Figure 5 4 HFS SK SLC Device Addressing Using Rotary Dials All dials labeled for ONES or TENS...

Страница 61: ...After determining that the hardware is properly installed custom programming can be performed Refer to Section 6 Table 6 1 Standards in Requirements for Control Units and Accessories NOTICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in the Standard for ...

Страница 62: ...at may allow the installer to use the panel without doing any custom programming 6 3 1 Default Mapping of SLC Inputs to Outputs The panel mapping configuration for the 5600 is fixed with regards to SLC addresses zone assignments and output points The relationship between input points and output points follows the rules defined in 6 3 2 below For input points the SLC address determines the zone ass...

Страница 63: ...A SK Pull DA HFS MM SK Minimon Alarm 15 21 35 Alarm Zone 2 Supervisory 5 36 40 Supervisory Zone 2 Zone 3 HFS P HFS PT HFS D HFS T SK Photo SK Photo T SK Duct SK Heat SK Pull SA SK Pull DA HFS MM SK Minimon Alarm 15 41 55 Alarm Zone 3 Supervisory 5 56 60 Supervisory Zone 3 Zone 4 HFS P HFS PT HFS D HFS T SK Photo SK Photo T SK Duct SK Heat SK Pull SA SK Pull DA HFS MM SK Minimon Alarm 15 61 75 Alar...

Страница 64: ...one 4 Alarm OPG 5 HFS MR HFS MRA SK Relay 2 119 120 Zone 5 Alarm OPG 6 HFS MR HFS MRA SK Relay 2 121 122 Zone 1 Supervisory OPG 7 HFS MR HFS MRA SK Relay 2 123 124 Zone 2 Supervisory OPG 8 HFS MR HFS MRA SK Relay 2 125 126 Zone 3 Supervisory OPG 9 HFS MR HFS MRA SK Relay 2 127 128 Zone 4 Supervisory OPG 10 HFS MR HFS MRA SK Relay 2 129 130 Zone 5 Supervisory OPG 11 HFS MR HFS MRA SK Relay 2 131 13...

Страница 65: ...6 4 JumpStart Autoprogramming Once the physical installation of SLC devices is finished the panel will need to learn which SLC devices and SBUS annunciators are present To run JumpStart 1 Press and hold the JumpStart key 2 Press the installer code after PIN is displayed 3 During JumpStart the panel will briefly light up all LEDs and then display SLC Prg on the 7 segment display 4 When complete the...

Страница 66: ... panel is connected to a PC without a router it assigns itself a default class B IP address of the format 169 254 X X Each panel will have a unique IP address and it will also be displayed on the 7 segment display When direct connected it will normally take about 40 seconds to display the IP address The panel displays IP while the IP address is being determined during this 40 second search period ...

Страница 67: ...er riser The default setting is 1 second which is the minimum debounce time You can set the water flow delay within the range 1 90 seconds 6 6 1 4 Installer Code User ID This is the password used to lock the list of SLC devices found during the JumpStart auto learn process It is defaulted to 123456 and can be changed to any 4 to 8 digit number 6 6 1 5 Alarm Verification Time Alarm verification is ...

Страница 68: ... alarm activation the NACs will automatically deactivate after the programmed amount of time expires 6 6 1 11 Clock Source The panel s AC line frequency is selectable for 60 Hz 50 Hz or Internal Clock Source AC frequency feature dictates how the control panel will calculate time based on the AC line frequency used in the installation site The Internal Clock option can be used in areas where the AC...

Страница 69: ...he zone select YES for this option The default setting is Yes 6 6 2 3 Zone Type A zone can be either a one count zone or an alarm verification zone The default setting is one count A one count zone has an immediate alarm when a single detector goes into alarm Alarm verification is an optional false alarm prevention feature for smoke detectors that verifies an alarm condition by resetting the smoke...

Страница 70: ...es you wish to have the circuit activate under Conventional Notification Circuit Cadence Pattern When a conventional notification circuit activates it can be configured to produce one of six output patterns 1 Constant On 24V DC power 2 ANSI ANSI temporal pattern 3 AMSECO Sync Strobe synchronization for AMSECO appliances 4 Gentex Sync Strobe synchronization for Gentex appliances 5 System Sensor Syn...

Страница 71: ... tone characters to be dialed before the phone number stored in the account option is dialed The default setting is to not have any prefix 6 6 6 2 Dial Tone Detection The default configuration for this option is Enabled If set to Disabled the dialer will not check for the presence of dial tone on the associated phone line prior to making a call 6 6 6 3 Line Monitoring Enabled Y N This option is us...

Страница 72: ... station Default setting is blank The following special characters are available Table 6 4 Special Dialing Characters 6 6 7 3 Reporting Format Choose SIA8 up to 8 events per call SIA20 up to 20 events per call or contact ID reporting format Default setting is contact ID 6 6 7 4 Reporting Filters Selecting the Must option forces the event type to be reported to the account even if it was already re...

Страница 73: ...ce with ULC 527 99 see 5600C Basic Operating Instructions 7 3 System Silence To Silence the PZT and all silenceable outputs that are active press the SILENCE key once Any silenceable trouble supervisory or alarm that is silenced will automatically unsilence if left silenced for 24 hours or if a new trouble supervisory or alarm event occurs 7 4 Acknowledge Use the ACK key to acknowledge alarm super...

Страница 74: ...sable points that are in trouble throughout the control panel will be displayed when using the scroll keys Note If there are any system level troubles active the LED corresponding to the system level trouble will blink also However system level troubles are not displayed on the 7 segment display after using the TROUBLE ID key and the PREV or NEXT to scroll addressable troubles Only point troubles ...

Страница 75: ...ill cause a trouble on the circuit The PZT will sound the trouble cadence The trouble LED for the circuit along with the general trouble LED will blink indicating trouble If the silence key is pressed the trouble LEDs will be continuously on and the PZT will silence Pressing the NAC disable key when the circuit is already disabled will enable the circuit Each pressing of a NAC disable key will tog...

Страница 76: ... and TELCO2 when line monitoring is enabled see programming section 6 5 6 3 When line monitoring is enabled and there is not sufficient voltage at TELCO1 or TELCO2 the 7 segment display will indicate Ln1 and or Ln2 for phone line 1 and phone line 2 troubles 7 17 Reporting Account Monitoring When the control panel is configured to use the dialer the reporting accounts will indicate trouble if the p...

Страница 77: ...fully before operating the Remote Annunciator Figure 7 1 shows the Remote Annunciator Figure 7 1 5635 Remote Annunciator 7 20 1 LCD Displays The Remote Annunciator s LCD displays system messages annunciates alarms supervisories and troubles provides status information and prompts for input These messages can be up to 80 characters displaying over four lines of 20 characters each Annunciator keys b...

Страница 78: ...unciator when the system is in normal mode no alarm trouble or supervisory condition exists You can create a customized message that will display instead of the internal default message See 6 6 1 13 for information on customizing the banner Figure 7 2 Banner Display Examples Text of Internal Banner Custom Banner example ...

Страница 79: ... on all LEDs for several seconds beeps the PZT and displays a message on the LCD display A problem is indi cated if any of the following occurs An LED does not turn on You do not hear the beep The LCD is unable to annunciate the message correctly 7 21 3 Silence alarms or troubles 1 Activate the key by turning it to the ON position 2 Press the Silence Key Note Alarm and trouble signals that have be...

Страница 80: ...ill also sound ALARM LED flashes The LCD displays a screen similar to this one Press the down arrow to view the alarm A screen similar to this one displays Activate the key by turning it to the ON position then press the Silence key to silence the Remote Annunciator and any notification devices attached to the system When the alarm condition clears activate the key and press Reset to restore the p...

Страница 81: ...n is pressed while the key is activated All LEDs are on briefly then the LCD displays RESET IN PROGRESS If the reset process completes normally the date and time normal mode screen displays Silenced An alarm or trouble condition has been silenced but still exists To silence alarms and troubles press while the key is activated SILENCE LED is on TROUBLE SUPERVISORY or GENERAL ALARM LED depending on ...

Страница 82: ...Model 5600 Installation and Operation Manual 7 10 151450 ...

Страница 83: ...t Contact ID Reporting Format Event Description Event Family Event Class System Zone or Point Module ID if any SIA Event Code Parameter if any Qualifier Event Code Group Contact System Events System events are reported when either Report by Zone is selected AC power restore Trouble System Event AR 3 301 00 000 AC power lost Trouble System Event AT 1 301 00 000 Short circuit removed from SLC commun...

Страница 84: ...uccessful Trouble System Event YK Acct 3 354 Acct Acct Auto dialer test communication trouble restore Trouble System Event YK Line 3 350 00 Line Ground fault condition detected Trouble System Event YP 34 1 310 00 Exp ID Ground fault condition restore Trouble System Event YQ 34 3 310 00 Exp ID Battery voltage restore Trouble System Event YR 34 3 302 00 Exp ID Battery voltage low Trouble System Even...

Страница 85: ...witch alarm Alarm Zone Event SA Zone 1 113 00 Zone Water flow switch alarm restore Restore Zone Event SH Zone 3 113 00 Zone Water flow switch trouble restore Trouble Zone Event SJ Zone 3 373 00 Zone Supervisory Tamper switch trouble restore Trouble Zone Event SJ Zone 3 373 00 Zone Supervisory condition restore Trouble Zone Event SR Zone 3 203 00 Zone Supervisory condition Trouble Zone Event SS Zon...

Страница 86: ...Model 5600 Installation and Operation Manual 8 4 151450 ...

Страница 87: ...N is displayed 2 Enter the installers code on the 10 digit keypad 3 SLC Prg will be displayed until the JumpStart is complete 9 1 2 View Active Points View Active Points alarm non system trouble and supervisory conditions Press the corresponding ID key e g Alarm ID Use Prev and Next to view more active points of that type 9 1 3 Disable Or Re Enable A Zone 1 Press the Zone x Disable button on the k...

Страница 88: ... test 2 Press SYSTEM RESET to end the test 9 1 11 Seven Segment Display On the 7 segment display AC1 indicates dialer account 1 failed to report AC2 indicates dialer account 2 failed to report dlr indicates a problem with the dialer The panel must be returned to the factory for repair drL indicates a fire drill is taking place Ln1 indicates low no voltage on phone line 1 Ln2 indicates low no volta...

Страница 89: ...arm Points 3 Find an Unused SLC Address and click on the detector type e g address 24 Photo 4 Click Accept Note Remember to choose to Download to Panel after all of your changes are done AND set the rotary switches on the back of the smoke detector e g tens 2 and ones 4 9 2 2 To add a notification appliance fire bell 1 Click on NAC Programming 2 Click on the NAC circuit you want to activate e g NA...

Страница 90: ...at you want to trip the appliance Note Be sure to set your SLC notification device address to match 9 2 6 To trip a Door Holder 1 Click on Output Point Programming 2 Click on the System tab 3 Click on the circle for Present across from the SLC Address of the door holder e g 158 4 Set the Door Holder device address accordingly e g 158 The Door Holder will provide 24VDC when in standby 0V during ala...

Страница 91: ...Table A 1 below lists notification appliances compatible with the fire alarm control panel Appliances which can be synchronized indicate the type of SYNC available in the columns marked Audio and or Visual Table A 1 Compatible Notification Appliances Manufacturer Model Audio Visual Type AMSECO SH24W 153075 Horn Strobe SAD24 153075 Strobe SAD24 75110 Strobe SL24W 75110 Strobe SL24C 3075110 Strobe S...

Страница 92: ...GCC24 Multi Candella Horn Strobe Ceiling Mount GCCR24 Multi Candella Horn Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR 24 Multi Candella Horn Strobe GES24 15 Strobes GES24 30 Strobes GES24 60 Strobes GES24 75 Strobes GES24 110 Strobes GES24 15 75 Strobes GES24 177 Strobes GES3 24 Multi Candella Strobe GESR 24 Multi Candella Strobe G...

Страница 93: ...Horn Strobe High Candela P2W 2 Wire Horn Strobe P2W P 2 Wire Horn Strobe PC2W 2 Wire Horn Strobe PC2W P 2 Wire Horn Strobe P2WH 2 Wire Horn Strobe High Candela P2WH P 2 Wire Horn Strobe High Candela PC2WH 2 Wire Horn Strobe High Candela PC2WH P 2 Wire Horn Strobe High Candela P2RK 2 Wire Horn Strobe PC2RK 2 Wire Horn Strobe P2RHK 2 Wire Horn Strobe High Candela PC2RHK 2 Wire Horn Strobe High Cande...

Страница 94: ...Horn Strobe High Candela PC4RH 4 Wire Horn Strobe High Candela SR Strobe SR P Strobe SCR Strobe SCR P Strobe SRH Strobe High Candela SRH P Strobe High Candela SCRH Strobe High Candela SCRH P Strobe High Candela SW Strobe SW P Strobe SCW Strobe SCW P Strobe SWH Strobe High Candela SWH P Strobe High Candela SCWH Strobe High Candela SCWH P Strobe High Candela SRK Strobe SCRK Strobe SRHK Strobe High C...

Страница 95: ...Multi tone Horn AS 121575W Horn Strobe NH 12 24 Horn AS 241575W Horn Strobe AS 24MCC Horn Strobe AS 24MCCH Horn Strobe AS 24MCW Horn Strobe AS 24MCWH Horn Strobe ASWP 2475W Horn Strobe Weatherproof ASWP 2475C Horn Strobe Weatherproof ASWP 24MCWH Horn Strobe ASWP 24MCCH Horn Strobe CH 70 Chime CH 90 Chime CH70 241575W Chime Strobe CH70 24MCW Chime Strobe CH70 24MCWH Chime Strobe CH90 24MCC Chime St...

Страница 96: ...rn Strobe MTWPA 2475W Multitone Horn Strobe MTWPB 2475W Multitone Horn Strobe MTWPG 2475W Multitone Horn Strobe MTWPR 2475W Multitone Horn Strobe MTWPA 24MCCH Multitone Horn Strobe ZNH Horn NS 121575W Horn Strobe NS 241575W Horn Strobe NS 24MCW Horn Strobe NS 24MCC Horn Strobe NS 24MCCH Horn Strobe ZNS MCW Horn Strobe ZNS MCWH Horn Strobe ZNS 24MCC Horn Strobe ZNS 24MCCH Horn Strobe RSS 121575W St...

Страница 97: ...G 24MCCH Strobe Weatherproof RSSWPR 24MCCH Strobe Weatherproof RSSWP 2475W Strobe Weatherproof RSSWP 2475C Strobe Weatherproof RSSWP 24MCWH Strobe Weatherproof ZRS MCWH Strobe ZRS 24MCC Strobe ZRS 24MCCH Strobe MB G6 24 Motor Bell MB G10 24 Motor Bell MB G6 12 Motor Bell MB G10 12 Motor Bell MIZ 24 R Mini Horn MT 12 24 R Multitone Horn MT4 12 24 Multitone Horn ZRS MCW Strobe MTWPR 24MCCH Multitone...

Страница 98: ...sor 1112 24 D Ionization 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base Ionization 0 10 39 System Sensor 2112 24ATR Photoelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelec...

Страница 99: ...System Sensor 4WITAR B 12 24 Volt I3 Photo w Isolated Therm Sounder Relay 05 50 System Sensor 2W MOD2 I3 Loop Test Maintenance Mod 05 System Sensor RRS MOD I3 Reversing Relay Sync Module 05 System Sensor 6424 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 38 5 Notes Contact manufacturer for current draws Smoke Detector Base Detector Type Max Standby Current mA Alarm Current mA ...

Страница 100: ...elays MANUFACTURER MODEL TYPE Current mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 MANUFACTURER MODEL Current mA Air Products Controls LTD MR 101 C MR 201 C PAM 1 PAM 2 PAM SD 15 35 15 15 15 System Sensor A77 716B PR 1 PR 2 ...

Страница 101: ...1450 11 A 5 Accessory Modules UL Listed Table A 5 lists accessory modules compatible with the fire control panel Table A 5 Compatible Accessory Modules Manufacturer Model Current mA Silent Knight 5635 40 ...

Страница 102: ...Model 5600 Installation and Operation Manual 12 151450 ...

Страница 103: ...urn address example under Advanced Replacement Policy Include a packing slip that has the RMA number a content list and a detailed description of the problem should be included with each return All products returned to Silent Knight must be sent freight pre paid After product is processed Silent Knight will pay for shipping product back to customer via UPS ground Return the Silent Knight product c...

Страница 104: ...oard is received at Silent Knight All returned products must comply with the guidelines described under General Terms and Conditions The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit No credit will be issued if the returned board was damaged due to misuse or abuse Repairs and returns should be sent to Silent Knight Honeywell Attn Re...

Страница 105: ...ES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED By MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This doc...

Страница 106: ......

Страница 107: ...ervisory press Supervs ID followed by or button to view the SLC ID for each point View Troubles Zones that are in trouble will have their trouble LED on To view all points in trouble press Trouble ID followed by or button to view the SLC ID for each point Conduct a Fire Drill 1 Press to start Fire Drill 2 Press to end Fire Drill Dialer Test Press and key at same time Lamp Test Press and key at sam...

Страница 108: ......

Страница 109: ......

Страница 110: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...

Отзывы: