151450
6-1
Section 6
Programming
This section of the manual describes how to change the control panel programming options
from the built-in web page of the control panel. All options described in this section are edited
via the panel’s built in web page
6.1
UL 864 Programming Requirements
*Only needs to be enabled if using the DACT.
Important!
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested
after JumpStart is because JumpStart automatically programs the system, searching for
and configuring all SLC devices and SBUS annunciators it finds. JumpStart allows you
to confirm the integrity of the installation prior to performing any custom
programming. After determining that the hardware is properly installed, custom
programming can be performed. Refer to Section 6.
Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings Permitted in
UL 864
System Options
Low AC Report Delay
Yes
0–30 hours
1–3
Zone Options
Supervisory
Yes
Latching/Non
Latching
Zone Options
Waterflow
Yes
Latching/Non
Latching
System Options
Alarm Verification
Yes
1-250 seconds
60-250 seconds
Dialer Phone line Programming
option
Line Monitor Enabled
Yes
Y/N
Y*
Содержание Silent Knight INTELLIKNIGHT 5600
Страница 2: ......
Страница 10: ...Model 5600 Installation Manual 6 151450 ...
Страница 16: ...Model 5600 Installation and Operation Manual 1 6 151450 ...
Страница 54: ...Model 5600 Installation and Operation Manual 4 24 151450 ...
Страница 82: ...Model 5600 Installation and Operation Manual 7 10 151450 ...
Страница 86: ...Model 5600 Installation and Operation Manual 8 4 151450 ...
Страница 102: ...Model 5600 Installation and Operation Manual 12 151450 ...
Страница 106: ......
Страница 108: ......
Страница 109: ......
Страница 110: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...