Wiring Distance SBUS Modules to Panel
Total worst case
Current Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1852 ft
4688 ft
6000 ft
6000 ft
0.200
926
2344
3731
5906
0.300
617
1563
2488
3937
0.400
463
1172
1866
2953
SBUS Wiring Distance
SBUS Wiring Distance
0.400
463
1172
1866
2953
0.500
370
938
1493
2362
0.600
309
781
1244
1969
0.700
265
670
1066
1687
0.800
231
586
933
1476
0.900
206
521
829
1312
1.00
185
469
746
1181