Calculate the total worst case current draw for all
modules on a single 4-conductor bus
Add the individual worst case currents for each module
Model Number
Worst Case Draw
RA-2000 Fire Annunciator
.120 amps
SBUS Wiring Distance
SBUS Wiring Distance
5815XL
.150 amps
5824 Serial/Parallel Printer Interface Module
.040 amps
5880 LED I/O Module
.250 amps
5865 LED Fire Annunciator
.200 amps
RPS-1000 Intelligent Power Supply
.010 amps
5496 Intelligent Power Supply
.010 amps
VIP-50
.010 amps
VIP-VCM/VIP-VCM with VIP-SW16
.125 amps/.200 amps
VIP-RM/VIP-RM with VIP-SW16
.125 amps/.200 amps
Max current
per SBUS!
Max current
draw = 1 amp
per SBUS!